Technical data
34
1MRS751108-MUM
Protection Relay
Technical Reference Manual, General
REX 521
If the fault is considered too dangerous to maintain normal protection, an inoperative
IRF state is entered and no output relay operations are allowed. On the other hand
if, for example, one output relay is found faulty and the others healthy, normal
operations targeted to a healthy relay are allowed.
Even a total breakdown of the relay, for example, on loss of power supply, will be
detected as the IRF relay operates in a fail-safe mode, causing a signal when the
relay drops off. The serial communication will also indicate loss of contact to the
module. When the relay is in the IRF state, it tries to recover by restarting every five
minutes.
As long as the fault remains, the relay continues to perform internal tests. Should the
fault prove to be of temporary nature, normal operation is recovered after restart and
an event “IRF reset” (E30) is sent over the serial communication.
5.1.11.1. Fault indication
The self-supervision signal output operates on the closed circuit principle. Under
normal conditions the output relay is energized and the contact gap 3-5 is closed.
Should the auxiliary power supply fail or an internal fault be detected, the contact
gap 3-5 is opened.
A051908
Fig. 5.1.11.1.-1 Self-supervision output (IRF)
When a fault has been detected, the green READY LED indicator starts blinking, a
fault indication text is displayed on the HMI and an event “IRF activated” (E31) is
generated over serial communication.
IRF
IRF
5
4
3
5
4
3
Normal condition
Fault condition