Technical data
46
1MRS751108-MUM
Protection Relay
Technical Reference Manual, General
REX 521
5.1.16.1. Special features of alarm LEDs
It is also possible to activate alarm LEDs by writing to parameter Alarm LED
states from HMI, or by using serial communication. This works even if the
alarms are not enabled (enabling alarms, see “Alarm LEDs” on page 45). The value
written to that parameter is then logically combined together (by an OR function)
with alarms enabled as described in the previous section.
The actual state of the alarm LEDs can also be read from the parameter Alarm LED
states by using serial communication, or by reading the state from HMI
(Configuration\Display\Alarm LED states).
In the HMI, the state of the alarm LEDs is shown bit-wise starting from the right
with LED1. The LEDs that were activated by writing to parameter Alarm LED
states can be acknowledged by pressing the [C] button for 2 s in the main view.
Clearing a certain LED without affecting the other LEDs can be done by setting the
corresponding bit to 0 in parameter Alarm LED states. Writing to parameter
Alarm LED states from HMI is useful when testing if a certain LED lights up.
5.1.16.2. Writing signal names on alarm LED label
You can write or print the alarm LED signal names on a special label presented in
Fig. 5.1.16.2.-1. The transparencies for the label are delivered with the relay. The
label contains eight text rows, one for each alarm LED.
A051915
Fig. 5.1.16.2.-1 Alarm LED label
After an auxiliary supply break, the state of the alarm LEDs is
restored to the same state as before the break. This means that alarms
will be seen even if the alarm went off during the break and
regardless of the mode. The alarms can be acknowledged (cleared)
only from the main view by pressing the [C] button for 2 seconds
106
+0
-0,5
ABB OY
Distribution Automation
1MSC 971082
Alarm LED label
Hälytys-LED kilpi
REX 521
971082
971082