Cut Sheet
www.geindustrial.com BuyLog
™
Catalog
6-91
Rev. 11/13
Data subject to change
without notice
Molded Case Circuit Breakers
Section 6
High Interrupting Capacity Motor Circuit Protectors—SF250 Line 3-Pole
Terminal Lugs for
Rating Plug Frame Front Connection (Cu/Al)
Adjustable Instantaneous
65kAIC @480 Vac 100kAIC @480 Vac
Ampere
Trip Ampere Range
Product Current Product Product Product Wire
Rating Low High Number Sensor Number Number Number Range
70 205 700 SRPF250A70
90 265 900 SRPF250A90
100 295 1000 SRPF250A100
110 325 1100 SRPF250A110
125 370 1250 SRPF250A125 250 SFLA36AI0250 SFPA36AI0250 TCAL29 8-350 Cu
150 440 1500 SRPF250A150 8-350 Al
175 515 1750 SRPF250A175
200 590 2000 SRPF250A200
225 665 2250 SRPF250A225
250 736 2500 SRPF250A250
Motor Circuit Protectors
3-250A
Mag-Break Motor Circuit Protectors
Current Limiting, UL Component Recognized
1
Features
—Suitable for Reverse Feed
—UL Recognized File E-11592
—CSA Certified LR 40350
—IEC 947-2 690 Vac Max.
—SE 150 160 Ampere Max.
—SF250 250 Ampere Max.
—SG600 630 Ampere Max.
—SK1200 1250 Ampere Max.
—UL Current Limiting
High Interrupting Capacity Spectra
™
RMS Motor Circuit Protectors—SE150 Line 3-Pole
Terminal Lugs for
Rating Plug Frame Front Connection (Cu/Al)
Adjustable Instantaneous
65kAIC @480 Vac 100kAIC @480 Vac
Ampere
Trip Ampere Range
Product Current Product Product Product Wire
Rating Low High Number Sensor Number Number Number Range
3 11 39 SRPE7A3
7 22 90 SRPE7A7
7 SELA36AI0007 SEPA36AI0007 TCAL18
15 43 182 SRPE30A15
20 58 254 SRPE30A20
30 SELA36AI0030 SEPA36AI0030 TCAL18
25 73 332 SRPE30A25
30 87 415 SRPE30A30 14-3/0 Cu
40 118 501 SRPE60A40
50 148 637 SRPE60A50 60 SELA36AI0060 SEPA36AI0060 TCAL18
60 178 777 SRPE60A60 12-3/0 Al
70 206 863 SRPE100A70
80 236 999 SRPE100A80
100 SELA36AI0100 SEPA36AI0100 TCAL18
90 267 1138 SRPE100A90
100 297 1280 SRPE100A100
110 328 1426 SRPE150A110
125 374 1640 SRPE150A125 150 SELA36AI0150 SEPA36AI0150 TCAL18
150 450 1991 SRPE150A150
SE150 Add-on 3-Pole Limiters
Maximum Product kAIC Use With Breaker/
Ampere Rating Number @600 Vac MCP Frame
150 SAXSEL36150 65 SEL
150 SAXSEP36150 100 SEP
1
Per UL 489, interruption ratings are not printed on the product label (interruption ratings are established based on a tested combination of the motor circuit protector and a
properly sized overload relay and contactor).