Specifications
ABBRA INSTALLATION GUIDE Version.04 4/12/17 13 
4.4.7 Quick Arm (fig. 4.4, location 07) 
Here you determine whether the user will be allowed to 
perform quick arming or not. Once quick arming is 
permitted, the control panel does not request a user code 
before it arms the system. 
The two options are: quick arm ON and quick arm OFF. 
4.4.8 Bypass (fig. 4.4, location 08) 
Here you permit either manual bypassing of individual 
zones (through the USER SETTINGS menu), or allow the 
system to "force arm" (perform automatic bypassing) of 
open zones during the exit delay. If desired, press the 
arming key twice if you want to eliminate the delay beeps 
that continue during a force arming. If a zone is open and 
forced arming is not permitted, “NOT READY” is displayed 
and the system does not arm (the “Sad Melody” will 
sound). If "no bypass" is selected, neither manual 
bypassing nor force arming is allowed. 
Options: manual bypass, force arm and no bypass. 
In UL installations, "force arm" must not be selected. 
4.4.9 Exit Mode (fig. 4.4, location 09) 
Here you determine whether the exit delay will restart if the 
exit / entry door is reopened before the exit delay expires. 
Restarting the exit delay is helpful if the user re-enters 
immediately after going out to retrieve an item that he left 
behind. Three types of exit mode are available: 
Restart Exit - Exit delay restarts when the door is 
reopened during exit delay. The restart occurs once only. 
Off by door - When the door is closed, the exit delay is 
automatically terminated (even if the defined exit delay was 
not completed). 
Normal - The exit delay is exactly as defined, regardless of 
whether the door is open or closed. 
In UL installations, "normal" must be selected. 
4.4.10 Piezo Beeps (fig. 4.4, location 10) 
Here you determine whether warning beeps will sound or muted 
during exit and entry delays. An additional option is to mute the 
warning beeps only when the system is armed “HOME”. 
Options: enable beeps, off when home and disable beeps. 
4.4.11 Trouble Beeps (fig. 4.4, location 11) 
Under trouble conditions, the sounder emits a series of 3 
short beeps once per minute. Here you determine whether 
this special beeping sequence will be active, inactive, or 
just inactive at night (the range of “night” hours is defined in 
the factory). The 3 options are: enable beeps, off at night 
(8 PM through 7 AM) and disable beeps. 
4.4.12 Panic Alarm (fig. 4.4, location 12) 
Here you determine whether the user will be allowed to 
initiate a panic alarm by simultaneous pressing either the 
two panic buttons (on the keypad / wireless commander) or 
away + home (on a keyfob transmitter). Audible panic 
activates the siren and simultaneously transmits a message 
via telephone. Silent panic only transmits a message via 
telephone. The options are:  silent panic,  audible panic 
and disable panic. 
4.4.13 Swinger Stop (fig. 4.4, location 13) 
Here you determine how many times each zone is allowed 
to initiate an alarm within a single arming period (including 
tamper & power failure events of detectors, Abbra and 
wireless siren). If the alarms number from a specific zone 
exceeds the programmed number, the control panel 
automatically bypasses the zone to prevent recurrent siren 
noise and nuisance reporting to the central station. The 
zone will be reactivated upon disarming, or 48 hours after 
having been bypassed (if the system remains armed). 
The available options are: shut after 1, shut after 2, shut 
after 3 and no shutdown. 
In UL installations, No Shutdown must be selected. 
4.4.14 Cross Zoning (fig. 4.4, location 14) 
Do not use in UL installations. 
Here you determine whether cross zoning will be active or 
inactive. Cross zoning is a method used to counteract false 
alarms - an alarm will not be initiated unless two adjacent 
zones are violated within a 30-second time limit. This 
feature is active only when arming AWAY and only with 
zone couples from zone No. 18 to 27 (18 and 19, 20 and 
21, etc.). You may use any one of these zone couples to 
create a “cross-zoned” area. 
Note: If one of two crossed zones is bypassed (see Para. 
4.4.8), the remaining zone will function independently. 
Note: Every 2 crossed zones must be of the allowed 
zone type (Interior, Perimeter, Perimeter follower). 
The options are: cross zone ON and cross zone OFF. 
Cross zoning is not applicable in Entry/ Exit zones and 
24h zones (Fire, Emergency, 24h audible, 24h silent).                                                              
4.4.15 Supervision (fig. 4.4, location 15) 
Here you determine the time limit for reception of 
supervision reports from various supervised wireless 
devices. If any device does not report at least once within 
the selected time limit, an “INACTIVITY” alert is initiated. 
The options are: 1, 2, 4, 8, 12 hours and disable. 
In UL installations, the interval must not exceed 4 h 
and shall not be disabled. 
4.4.16 NOT READY (fig. 4.4, location 16) 
Here you determine if the system will be NOT READY 
status when there is a supervision failure. In the "in 
supervision" mode, the system will be in NOT READY 
status if during the last 20 minutes a supervision message 
was not received.  Options: normal and in supervision. 
4.4.17 AUX Button (fig. 4.4, location 17) 
Here you select the function of the AUX button on keyfob 
transmitters and wireless commanders MCM-140+. Three 
options are offered: 
Status: Pressing the AUX button will cause the control 
panel’s voice module to announce the system status. 
Instant: Pressing the AUX button while the exit delay is in 
progress will cause the system to arm “instant” (the entry 
delay is canceled). 
PGM / X-10: Pressing the AUX button will activate the 
PGM output or X-10 units (see further programming under 
“DEFINE OUTPUTS”, par. 4.7). 
4.4.18 Jam Detect (fig. 4.4, location 18) 
Here you determine whether jamming (interfering trans- 
missions, on the radio channel used by the system) will be 
detected and reported or not. 
If a jam detection option is selected, the system does not 
allow arming under the relevant jamming conditions. 
Jam Detection Options 
Option  Detection and Reporting when 
UL (20/20) 
(USA standard) 
There is continuous 20 seconds of 
jamming 
EN (30/60) 
(Europe standard)
There is an accumulated 30 seconds of 
jamming within 60 sec. 
class 6 (30/60) 
(British standard) 
Like EN (30/60) but the event will be 
reported only if the jamming duration 
exceeds 5 minutes. 
Disabled  (no jamming detection and reporting). 
4.4.19 Latchkey (fig. 4.4, location 19) 
Here you determine whether the system can be armed in 
the latchkey mode. If the system is armed this way, a 
“latchkey” message will be sent to specific telephones upon 
disarming by a “latchkey user” (users 5-8 or keyfob 
transmitters 5-8). This mode is useful when parents at work 
want to be informed of a child’s return from school. You 
can record a name for latchkey users. 
The options are: Latchkey ON and Latchkey OFF. 
In UL installations, this function shall not be used. 










