UK Intruder alarm panel Terxon MX – Installation instructions Perfect Security for the home and the office These installation instructions are an important product accessory. They contain important installation and operation information. Bear this in mind if you pass the product on to others. Store these installation instructions in a safe place for future reference. For a list of contents with page numbers, see page 3.
1 UK Introduction Dear Customer, Thank you for purchasing the Burglar Alarm Panel Terxon MX. You have purchased a product that has been designed and constructed according to the state-of-theart, which complies with the current standards of domestic and European regulations. The CE has been proven and all related certifications are available from the manufacturer upon request (www.abus-sc.eu).
1 2 3 4 5 6 7 8 9 Contents Introduction........................................................................................................................................2 Usage in accordance with regulations ..............................................................................................2 Contents ............................................................................................................................................3 Precautions....................................
UK 16.1 Program mode..........................................................................................................................32 16.2 Overview of program menu ......................................................................................................33 16.3 Settings in program menu ........................................................................................................46 16.4 Programming Partitions ..................................................................
4 Precautions !WARNING! !ATTENTION! To avoid fire and injury, please observe the following: Please observe the following regulations to ensure trouble-free operation of your device. • Securely fasten the device at a dry location in the building. • The alarm centre is supplied with 12V DC power by means of the internal transformer. • Ensure sufficient air circulation for the alarm centre. • Do not expose the device to temperatures less than -10°C or more than 55°C.
5 UK Scope of delivery and accessories required Required tools: Scope of delivery • • • • Flat screwdriver (small) Intruder alarm panel (“alarm centre”) LCD operating panel Installation Instructions Operating instructions Philips screwdriver Drill 6mm drill bit You also need: 4mm drill bit Alarm detector 6mm screws Signal transmitter 4mm screws 12V/7Ah rechargeable battery Wallplugs, filler, etc.
6 Notes on connection and extension options The burglar alarm panel is the basic device of an electronic security system for protecting your property (e.g.: apartment, house, garage, shops, etc.). In combination with other components such as detectors and signal transmitters, it secures the areas to be monitored. The alarm is triggered by unauthorised break-in attempts.
7 UK Notes on security system The Terxon MX burglar alarm panel enables you to configure each of the 8 (max. 32) alarm zones optimally to suit your operating conditions. Recommendations: The user and program codes must be different. For reasons of clear layout, use the following colour coding: • Distribute the external detectors in as small groups as possible to the zones (e.g., ground-floor detector to zone 1, etc.); activate detectors singly; if possible, use all zones of the alarm centre.
The diagram below shows the correct usage of soldered distributors when connecting more than one detector to an alarm zone: Sometimes it is necessary to combine several alarm contacts in a zone. Connect the contacts serially. NC alarm contact NC alarm contact (e.g. contact switch NC-Alarmkontakt (z.B. Öffnungsmelder) NO (normally open) contacts (e.g., for panic buttons) cannot be connected to this alarm centre.
8 Overview of housing components 1 UK 5 4 3 7 8 9 6 10 2
1 2 Connection of 230V mains supply with primary fuse (T 250V 250mA). 3 4 5 6 7 Connector strip for siren, flashlight, programmable outputs, loudspeakers, 12VDC power supply and alarm zones. Connection of tamper contacts of the housing of the alarm centre. 230V AC / 12V DC transformer Terminal connector strip for standby battery. Terminal connector strip for control units. Terminal connector strip for extra transistor outputs or the optional relay module.
9 UK 9.1 Notes on installation Alarm centre 9.2 Fix the alarm centre to a flat, dry, vibration-free and heatresistant surface. The cables for the power supply of the alarm centre, the alarm zones and the signalling equipment (siren, flashlight, any external loudspeakers, etc.) should be inconspicuous, if possible below the surface or in a cable channel. Control units The control units should also be mounted on a flat, dry, vibration-free surface. The mounting height is important.
10 Notes on wiring 10.1 Alarm centre 1 Terminal connector strip for tamper and alarm UK zones. COM A/T: Connections for detector tampering CCT 1…8: Connections for alarm zones 1–8 2 Terminal connector strip for 12V DC power supply of external equipment (e.g., detectors) AUX: 0V: +12V permanent voltage for detectors 0V ground 3 Terminal connector strip for loudspeaker, progr. outputs and siren tampering.
10.2 UK Control units The burglar alarm panel can operate with up to four control units connected via a BUS. The control units can be connected as a ring or star to the alarm centre.
COM interface 1A AUX fuse for the power supply NVM 2A BAT fuse for the battery charging Battery connectio Optional speaker Programmable floating relay output (NC/NO) / 24VDC@1A Kick Star Sir.tamper input AC connectio Programmable transistor output (OP). Max. power consumption of all transistor outputs 0.5A.
10.3 Detectors 10.3.2 Infrared sensitivity detector Infrared sensitivity detectors detect the infrared heat movement of living creatures and must not be used indoors. For transparency reasons, avoid using motion sensors with door/window contacts in a zone. 10.3.1 Door and window contacts UK Door and window contacts monitor the opening of doors and windows. To activate the entry/exit delay time, at least one contact should be mounted on the main entrance door on which a control unit is also mounted.
10.3.3 Smoke detector 10.3.4 Acoustic glass breakage sensor: This burglar alarm panel allows the connection of smoke detectors. For these, program zone type “fire” or “smoke detector”, depending on the function of the smoke detector. This programming result in a special acoustic warning for persons present (pulsed alarm tone). These glass breakage sensors evaluate acoustic signals resulting from glass breakage. Connection example: 10.3.
10.4 To deter burglars and alert the neighbourhood, we recommend connecting a siren and a flashlight to the alarm centre. The functioning principle of this alarm signalling combination is based on a permanent power supply of the siren and a rechargeable battery integrated in the siren housing. Note that these alarm devices should be mounted as high as possible (e.g. at roof height) and the cables should not be visible. Outdoor acoustic alarms can be a disturbance to the neighbourhood.
10.5 Dialler 10.6 Key switch The built-in telephone dialler of the alarm centre allows the most varied system messages to be transmitted to various numbers. If programmed accordingly, each zone permits the connection of a key switch for activating or deactivating the alarm centre. Important: If you are using a DSL splitter as part of your telephone connection then make sure that this is installed before the alarm centre. The high-frequency DSL signal can disturb the transmission.
10.8 Instead of using the additional transistor outputs, you can connect an optional relay module with eight changer relays. Note the information in the relay module. An optional 16Ohm loudspeaker is connected to the contacts LS and +. 10.9 The loudspeaker can be integrated directly in the housing of the alarm centre. In Variant A, the system can only detect whether the zone is opened and it always registers an opening as an alarm in this zone.
10.10 Connecting expansion modules 10.12 Walk test The 8-zone wire expansion modules and the 8-zone radio expansion modules are connected to the 4-wire bus as follows. The OP3 output must be appropriately programmed for the walk test (function 83, option 5). If the user activates the walk test function then the LED for motion detection is activated at the detector.
11 Single system or partitioned system UK The alarm centre can be operated as a single system or as a partitioned system. In the single system, all locations, and 3 sections of the locations, are simultaneously activated or deactivated. All control units, zones and outputs work for the entire system. If the alarm centre is functioning as a partitioned system then it provides 4 smaller, independent alarm centres.
FE - INPUT/OUTPUT If the burglar alarm panel is active, this zone first triggers an alarm following a specified delay time (entry delay). This zone type can be used for the door contact of your entrance. When you leave the premises, closing this zone can be used for ending the exit delay. This zone can be opened when you exit the program menu. 12 Term declaration Before starting to program the alarm centre, you should understand the terms used.
UK SD – FIRE ALARM This zone works just like a fire zone. In contrast to a fire zone, the connected fire alarms can be reset by briefly switching off the power supply and no alarm is triggered. However, the reset must be made via a switch output. The program menu can be exited only when this zone is closed. 13 General terms ZONE A zone consists of one or more detectors connected to the burglar alarm panel via an input CCT.
Note that you need two extra lines for connected the tamper line. In the next step, we connect the control unit to the system. Note that the jumper is not connected if only one control unit is used (see page 13). Connect the control unit to the alarm centre as shown. 14 Specimen Installation This specimen installation is intended to explain the use of Terxon MX. Here we use a system with two users. One user (de)activates the alarm system using code input, the other with a chip key.
UK Please read the operating instructions of the SE1000. Please take care that you use the pulse setting for the keyswitch.The circuit shown above enables you to activate/deactivate the alarm system by turning the key in either direction. Here too, the tamper line is not yet connected to the system. The setting of the relais outputs and additional switch outputs is shown later. In the following, we show you the wiring of the tamper line.
8. Now enter via the control unit: 0 and then the factoryset programming code 7890 The following shows on the display: Mult Syst? We will now change this to entry/exit. Enter 05. You see the following in the display: 9. Press Key 1 to create a partitioned system. Press Key 0 to create a single system like we do. Now press B to add area B to the sensor. Confirm your . setting by pressing the Enter key The “1” following the sub-areas stands for the time delay group (1 to 4).
UK Now we program additional transistor outputs for the LEDs of the key switch. The yellow LED should light in deactivated alarm state, and the red LED in activated alarm state of the alarm system. To program the first additional transistor output OP4 or the state of the red LED, enter 151 on the keypad. Confirm your input by . pressing the Enter key You see the following: If required, you can change the siren delay. You can select values from 0 to 20 min.
If you use a loudspeaker with the system, you can test it in the programming menu under item 094. You have now made all settings in the programming menu. Exit the programming menu by entering 099 and . You are now in the user menu. confirming with Now change the name to ANNA and press the Enter key . The display shows: We now add two users to the system. The first user (BERND) is to activate and deactivate the system by entering a code, the second (ANNA) using a chip key.
UK If you use the siren, transistor output OP1 (programming menu: menu item 081) must be set to “Bell” (00). Use the resistors provided to connect the SG1900 (1kOhm). Do not forget to change the connector of the internal battery from NC to Battery (–). Se also the operating instructions of the signalling equipment, which you should read carefully.
15 First-time usage If you want to create your own configuration of the system and do not need the example of installation pay attention to the next steps. Please take notice of the important terms concerning the alarm panel. You can now put the alarm panel into operation. UK 1. Connect the 12V battery (7.0 Ah) to the contacts of the alarm centre (note the colour code: red = +12V, black = 0V). 2. Using a screwdriver, short-circuit the two pins of the kick-start jumper (see p. 14). ) 3.
16 Programming UK 16.1 4. After you confirm your input with the Enter key , the alarm centre checks the current status of the system. If everything is correct, the alarm centre returns to normal operating state. You have exited the program menu. The alarm centre is now deactivated. Program mode All input in program mode is made via the keypad. The LCD display gives you information about your input. For further information about the programming items, see page 30.
Menu item 16.2 Overview of program menu Country setting (000 n ) Important: If you change the country setting, all system settings are reset to the country settings of the new country. Menu item 000 Setting (n) 0 1 2 3 4 5 6 7 8 9 X1 X2 X3 X4 X5 X6 X7 Program code (020 Menu item 020 Setting (nn) 00 01 02 03 04 05 06 07 08 09 10 nnnn Setting nnnn Menu item 021 nn ) Meaning No resistor NC Two resistors FSL Internal volume (022 n Menu item 022 Meaning Off Quiet...
Internal alarm (025 Menu item 025 UK n Setting 0 1 ) System reset (033 Meaning Local alarm following Until deactivated Menu item 033 n Setting 0 Meaning No program code necessary Program code necessary 1 n Alarm on failed Activation (027 Menu item 027 Setting 0 1 Panic reset (034 Meaning Internal Alarm Local Alarm Hide state display (028 Menu item 028 ) Setting 0 1 2 n Menu item 034 ) Menu item 035 Hide after 180 secs.
System auto active following alarm (040 n ) Menu item 040 Setting 0 1 2 3 4 Siren delay (041 Menu item 041 Setting 0 1 2 3 4 5 6 Siren duration (042 Menu item 042 Setting 1 2 3 4 5 6 Setting 1 2 3 4 5 6 n Setting 0 1…9 Menu item 047 ) n Setting 0 1 2 n Setting 0 1 2 n ) Meaning Control unit alarm Control unit + speaker Control unit + speaker + dialler Control unit lock (048 Menu item 048 ) Meaning Internal alarm Control unit Internal + control unit Partition A alarm Reaction (047 Meani
Length of access code (056 Menu item 056 UK Setting 0 1 Battery test (057 Menu item 057 n Menu item 063 Setting 0 1 ) Setting 0 1 Setting 0 1 2 3 In a partitioned system 0 1 ) n n Setting 1 2 3 4 5 6 Menu item 066 Setting A B C D Forbikobler correct (067 ) Menu item 067 Meaning Exit time + quiet tone Immediate Silent As exit mode for overall activated Exit time + tone Manual 36 Setting 0 1 ) Only control unit tone Control unit + speaker Control unit + speaker + comms n ) Meaning 1
Forbikobler entry time (068 Menu item 068 Setting 0 1 2 3 4 5 6 7 8 9 Setting 0 1 ) n Setting 0 1 Setting 0 1 Setting 0 1 2 3 In a partitioned system 0 1 2 3 4 Setting 0 1 2 3 In a partitioned system 0 1 2 n Menu item 075 ) n Menu item 076 Setting 0 1 2 3 In a partitioned system 0 1 2 3 4 5 ) Meaning Exit time plus quiet tone Immediate Silent As exit mode for overall activated Exit time Manual Last door Immediate Silent 37 ) Control unit Local Alarm External Alarm (control unit + siren
Alarm behaviour at Internal D (077 Menu item 077 UK Setting 0 1 2 3 In a partitioned system 0 1 2 Setting 1 2 3 4 5 6 Control unit Local Alarm External Alarm (control unit + siren +dialler) Setting 0 1 n Setting 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 Activate all 1 Deactivate all 1 Alarm 26 27 28 29 30 31 32 33 34 35 Active pulse 1 Active pulse 2 Active pulse 3 Active pulse 4 pulse 1 Inactive pulse 2 Inactive pulse 3 Inactive pulse 4 Fire Panic ) n ) nn Siren partition A Siren partitio
Control Unit Alarm (087 Menu item 087 Setting 0 1 Setting 0 1 Menu item 091 Menu item 092 Menu item 093 Meaning End test ) Meaning End test Setting Walk Test (097 Menu item 097 Setting programming Menu item 105 N nn A nn B nn C nn D nn ) ) Meaning End test n Meaning OFF 1 way 2 3 2 way Both Setting 0 1 2 3 4 5 6 n ) Meaning Fast format Contact ID SIA I SIA II SIA 3 Expanded SIA 3 Home „beep“ N nn ) Setting Meaning 00 OFF Daily at hour 01-24 Monthly at day 01-28 Every 01-24 hours
108 Dynamic test call (108 Menu item 108 UK Setting 0 1 n ) Menu item 116 Meaning OFF ON 109 Three Way Call – UK only(109 Menu item 109 Setting 0 1 n Setting 0 1 Menu item 117 n Setting 0 1 2 3 4 5 Menu item 118 Menu item 113 Setting 0 1 Setting 0 1 2 n Setting Max. characters Setting Max. characters 31 Setting Max. characters 31 n…n ) Meaning 0..9, C + D back/forwards n…n ) Meaning 0..
125 No signal „closed“ (125 Menu item 125 Setting 0 1 n ) 132 Transmit Sabo as burglary n ) (132 Meaning OFF No signal „closed“ when more than 1 zone is blocked Menu item 132 Setting 0 1 2 3 4 5 6 7 8 9 X1 Setting 0 1 2 3 4 n Setting 0 1 Menu item 131 Setting 0 1 2 3 Menu item 143 n ) Meaning Do not transmit resets Transmit SIA resets Setting 0 1 n SIA ) Meaning Standard Standard + reset Behaviour of Additional Switch Output 1 (151 nn ) Menu item 151 ) Meaning ON OFF 131 SIA Report m
UK 25 26 Alarm partition C Alarm partition D 30 31 32 33 34 35 36 37 Active pulse 1 Active pulse 2 Active pulse 3 Active pulse 4 Inactive pulse 1 Inactive pulse 2 Inactive pulse 3 Inactive pulse 4 Behaviour of Additional Switch Output 8 (158 nn ) Menu item 158 Setting See setting Menu item 159 Setting See setting Setting See setting Meaning for switch output 1 Time-confirmed alarm (160 Menu item 160 Meaning for switch output 1 Setting See setting Menu item 161 Meaning for switch output 1 Set
User reset after confirmed alarm (164 n ) Menu item 164 Setting 0 1 2 1 Meaning User/Installer User/User Installer/Installer Setting 00 01 – 12 Meaning Latched output Pulse duration seconds Switch output active stable (171 n n n n Menu item 171 Setting ABCD Menu item 172 Setting 00 01 – 12 Setting ABCD Switch output for fire (174 n n n ) Menu item 174 Setting 0 1 Switch output for panic (175 n n n Menu item 175 Setting 0 Menu item 183 in Setting 07 08 09 10 11 12 ) UK Meaning 7 seconds
Fast format channel 1 (191 nn ) Menu item 191 UK Setting 00 01 02 03 04 05 06 11 12 13 14 15 16 17 18 19 20 21 22 In partitioned system 23 24 25 26 30 31 32 33 34 35 36 37 Fast format channel 4 (194 Setting See setting Setting See setting nn Setting See setting Menu item 196 Setting See setting Setting See setting Setting See setting nn nn nn ) ) Meaning for channel 1 44 ) ) Setting Meaning Keys 1 + 3 zone selection Setting 1 2 3 4 n Setting 1 2 3 4 5 6 n Meaning Entry delay group
Entry delay group 2 (202 n ) See 201 Entry delay group 3 (203 n ) UK See 201 Entry delay group 4 (204 n ) See 201 45
16.3 UK Settings in program menu 4. Enter the zone name (max. 12 characters) via the keypad. 000 Country Settings Use this setting to configure the burglar alarm centre for the local country. When you load the country settings, all user-defined settings are discarded. If you only want to set the language of the control unit display, use menu item 126 (language). At the user level, do the following: 1. On the control unit, enter: 0 2. Enter the program code: 7890 The LCD display shows: Progr.Mode 3.
After entering the zone name, enter the zone property. Zone properties are explained on pages 19 and 20 of these instructions. Enter the zone property as follows: 3. Apart from the zone property and the area in which the zone is to be monitored, there are also zone attributes. Via the keypad, enter the zone attributes as follows: 1.
UK 4. Apart from the zone properties and zone attributes, you can make further settings for some zone properties. For example, for an “entry/exit” zone and an “entry to follow” zone, you have to define the entry delay time, and for a “shock sensor” zone, you have to define the sensitivity.. Enter the additional properties via the keypad as follows: X7 X7 5. Confirm your input. On the control unit, enter: . 6. The control unit acknowledges your input with a double “beep” tone and shows Installer Mode.
After the alarm, the user can switch off the alarm using the access code, although he can not reset the alarm centre. The user contacts the central station which identifies him and transmits a signal back to the alarm centre. The user can now carry out a reset. 022 Changing the volume for internal alarm For changing the zone termination for the inputs of the burglar alarm centre. From the program level, do the following: 1. On the control unit, enter: 022 2.
4. Confirm your input. On the control unit, enter: . 027 Alarm on failed activation To change the property of the alarm on failed activation, proceed as follows: 1. On the control unit, enter: 027 UK 5. The control unit acknowledges your input with a double “beep” tone and shows Installer Mode. 2. The LCD display shows: 027:Internal 029 Entry alarm delay 3. Via the keypad, select from the following items and press: 0 Proceed as follows to change the property of the entry alarm delay: 1.
030 Panic silent 5. The control unit acknowledges your input with a double “beep” tone and shows Installer Mode. To change the property of the silent panic alarm: 1. On the control unit, enter: 030 032 Control units and partitions 2. The LCD display shows: 030:PA audible If you have created a partitioned system then using this function, you can assign entry/exit zones, alarm zones and status displays of partitions to the control units. To change this feature, proceed as follows: 1.
1 UK 035 First alarm reaction acknowledge the message. EngReset OFF If a system error is displayed, you have to enter the program code to acknowledge the message. Proceed as follows to change the property of the first alarm reaction: 1. On the control unit, enter: 035 2. The LCD display shows: 035:Lock-out ON Note: Some events always require you to enter the program code. These are: Failure/fault of a control unit Failure of 12V power supply Low battery in the alarm centre 3.
5. The control unit acknowledges your input with a double “beep” tone and shows Installer Mode. 5. The control unit acknowledges your input with a double “beep” tone and shows Installer Mode. 037 Sabotage Report deactivated 039 Exit mode for overall activated (A) To change this feature, proceed as follows: 1. On the control unit, enter: 037 To change the property of the exit mode for overall activated: 1. On the control unit, enter: 039 2. The LCD display shows: 037:Day Tamp OFF 2.
5. The control unit acknowledges your input with a double “beep” tone and shows Installer Mode. 041 Siren delay Proceed as follows to change the property of the siren delay: 1. On the control unit, enter: 041 040 System Rearm UK To change the property of the siren duration: 1. On the control unit, enter: 040 2. The LCD display shows: 041:Bell Dly=0 2. The LCD display shows: 040:Rearm=Never 3. Via the keypad, select from the following items and press: 3.
042 Siren duration 044 Exit delay time A To change the property of the siren duration: 1. On the control unit, enter: 042 To change the property of the exit mode for overall active A: 1. On the control unit, enter: 044 2. The LCD display shows: 042:Bell On=20 2. The LCD display shows: 044:Exit A=20 3. Via the keypad, select from the following items and press: 1 2 3 4 5 6 3. Via the keypad, select from the following items and press: Bell On=1.
045 Entry/exit delay tone volume 5. The control unit acknowledges your input with a double “beep” tone and shows Installer Mode. To change the property of the entry/exit delay tone volume: 1. On the control unit, enter: 045 UK 047 Partition A alarm Reaction To change this feature, proceed as follows: 1. On the control unit, enter: 047 2. The LCD display shows: 045:EE VOL=5 3. Via the keypad, select from the following items and press: 0 1-9 2.
4. Confirm your input. On the control unit, enter: . 11. Enter the minute via the keypad. 5. The control unit acknowledges your input with a double “beep” tone and shows Installer Mode. 13. The control unit acknowledges your input with a double “beep” tone and shows Installer Mode. 12. Confirm your input with 050 CSID code 052 Block tamper To be able to use the remote reset function, you must set the alarm centres to installer reset (function 33 to 1) and assign the CSID code.
4. Confirm your input. On the control unit, enter: . 056 Length of access code To change the property of the length of the access code: 1. On the control unit, enter: 056 5. The control unit acknowledges your input with a double “beep” tone and shows Installer Mode. UK 2. The LCD display shows: 056: 4 Digit 054 BVVO monitoring 3. Via the keypad, select from the following items and press: To change the property of the BVVO monitoring: 1. On the control unit, enter: 054 0 1 2.
058 BVVO Sabotage reset 060 Entry/exit behaviour on internal active (B) Proceed as follows to change the property of the BVVO sabotage reset: 1. On the control unit, enter: 058 To change the zone property of the entry/exit zone at internal active (B): 1. On the control unit, enter: 060 2. The LCD display shows: 058: BVVOtamp OFF 2. The LCD display shows: 060: B=FE =FE 3. Via the keypad, select from the following items and press: 0 1 3.
changes its zone property during internal activation to entry/exit and starts the delay time if the zone triggers and during active internal activation. UK 2 4. Confirm your input. On the control unit, enter: . 3 5. The control unit acknowledges your input with a double “beep” tone and shows Installer Mode. 4 062 Behaviour of exist mode internal active (B) 5 To change the property of the exit mode for internal active (B): 1. On the control unit, enter: 062 unlimited.
2 alarm and the external siren are activated. B=Full On alarm, the control units, the internal signalling, the external sirens and the telephone dialler are activated. 066 Forbikobler partitions To change this property (only possible in partitioned systems): 1. On the control unit, enter: 066 2. The LCD display shows: 066:Forbi 1 abcd 4. Confirm your input. On the control unit, enter: . 3. Via the keypad, select from the following items and press: 5.
5. The control unit acknowledges your input with a double “beep” tone and shows Installer mode. 2. The LCD display shows: 069: Lock Timed 3. Via the keypad, select from the following items and press: 068 Forbikobler entry time UK This function sets the time that the Forbikobler system allows for entry. An optional output for a door lock can be connected during this time. To change the property of the Forbikobler entry time: 1. On the control unit, enter: 068 0 2.
4. Confirm your input. On the control unit, enter: . 072 Behaviour of exit mode internal (C) To change the property of the exit mode for internal active (C): 1. On the control unit, enter: 072 5. The control unit acknowledges your input with a double “beep” tone and shows Installer Mode. 2. The LCD display shows: 072: C=Low Tone 071 Entry to follow behaviour on internal active (C) 3.
075 Exit delay time internal C Key switch (see command) To change the property of the exit delay time for internal active C: 1. On the control unit, enter: 075 4. Confirm your input. On the control unit, enter: . UK 5. The control unit acknowledges your input with a double “beep” tone and shows Installer Mode. 2. The LCD display shows: 075: E C=10 3. Via the keypad, select from the following items and press: 073 Alarm behaviour for internal (C) To change the alarm property for internal active (C): 1.
076 Behaviour of exit mode internal (D) 5 To change the property of the exit mode for internal active (D): 1. On the control unit, enter: 076 D=Lock Set Key switch (see command 39) 4. Confirm your input. On the control unit, enter: . 2. The LCD display shows: 076: D=Low Tone 5. The control unit acknowledges your input with a double “beep” tone and shows Installer Mode. 3.
UK 079 Exit delay time internal D 080 Forbikobler door bell To change the property of the exit delay time for internal active D: 1. On the control unit, enter: 079 Proceed as follows to change the property of the Forbikobler door bell: 1. On the control unit, enter: 080 2. The LCD display shows: 079: Exit D=10 2. The LCD display shows: 080: Chime OFF 3. Via the keypad, select from the following items and press: 3.
081 Relay output OP1 To change the behaviour of relay output OP1 on the alarm centre PCB: 1. On the control unit, enter: 081 07 2. The LCD display shows: 081: Bell 3. Via the keypad, select from the following items and press: 00 01 02 03 04 05 06 08 Bell This output is activated at local and external alarms. Set the siren delay and duration in menu items 41 and 42. EE Follow This output is activated if the entry/exit delay is active.
15 UK 16 Set Comp1 This output is active for 10 seconds after the system has been activated. 26 Unset Comp1 This output is active for 10 seconds after the system has been deactivated or after an alarm has been deactivated. 27 17 System Alarm This output is activated when the alarm centre has detected an alarm. In a partitioned system Bell Partition A This output is active when an alarm has 18 been detected in partition A.
33 34 35 1. On the control unit, enter: 085 Unset 4 This output is activated for a definable time period (command 170) if the alarm centre is deactivated completely (A) or internally (B), (C) or (D) (command 171). Fire This output is activated if a fire alarm is triggered. The output remains active until the alarm is deactivated. 2. The LCD display shows: 085: Burg=Latched 3. Via the keypad, select from the following items and press: 00 01 PA This output is activated if a fire alarm is triggered.
087 Control unit alarm 5. The control unit acknowledges your input with a double “beep” tone and shows Installer Mode. To change the properties of the connected control units: 1. On the control unit, enter: 087 UK 2. The LCD display shows: 087:Dual Key OFF 090 - 097 Test function see 16.6 3. Via the keypad, select from the following items and press: 098 Factory settings 0 1 To restore the factory settings: 1. You must be in program mode.
3. The LCD display shows: 101: Comms=OFF 103 Format Report 4. Via the keypad, select from the following items and press: Proceed as follows to change the property of the format report: 1. On the control unit, enter: 103 0 1 2 3 Comms=OFF The alarm centre does not use any communication devices. Comms=Single Single report. The alarm centre reports to a programmed telephone number (command 115) with an access number (command 117).
105 Test call To change the properties of the test call: 1. On the control unit, enter: 105 UK 2. The LCD display shows: 105:Day Hour=00 3. Via the keypad, select from the following items and press: 00 A nn B nn C nn D nn OFF Day Hour Daily test call to the alarm centre at the required time 01-24. Month Day Monthly test call to the alarm centre on the required day 01-28. Freq Hour The alarm centre makes a test call every nn hours (e.g. every 12 hours).
109 Three way call – UK only 112 Call until answer - download To change the settings of the three way call: 1. On the control unit, enter: 109 To change the settings: 1. On the control unit, enter: 112 2. The LCD display shows: 109:ThreeWayOFF 2. The LCD display shows: 112:Rings=5 3. Via the keypad, select from the following items and press: 3. Via the keypad, select from the following items and press: 0 1 ThreeWayOFF Three way call is switched off. ThreeWayON Three way call is switched on.
5. The control unit acknowledges your input with a double “beep” tone and shows Installer Mode. The alarm centre interprets a call as a message from a remote PC. 10 to 90 seconds later, the remote PC calls again once and the alarm centre answers immediately on the first call. (Set command 112 to a larger number of calls than other end devices on the line) UK 115 Telephone number 1 To change the settings: 1. On the control unit, enter: 115 2. The LCD display shows: 115:Tel No 1 3.
118 RemoteTel No 1 123 Reset report To change the settings: 1. On the control unit, enter: 118 To change the settings: 1. On the control unit, enter: 123 2. The LCD display shows: 118:DL Tel No 1 2. The LCD display shows: 123:Restore OFF 3. Via the keypad, enter the telephone number. Use key A to enter a 4-second pause (shown by a comma). 3. Via the keypad, select from the following items and press: Restore OFF The alarm centre does not communicate any resets.
125 No signal „closed“ 5. The control unit acknowledges your input with a double “beep” tone and shows Installer Mode. To change the settings: 1. On the control unit, enter: 125 UK 2. The LCD display shows: 125:Omit > 1 OFF 128 External alarm 3. Via the keypad, select from the following items and press: All radio transmitters are monitored via the radio expansion unit. If a radio zone has not communicated with the radio expansion unit for more than 2 hours then this reports a monitoring error.
129 Deactivate external 132 Transmit tampering as burglary To change the settings: 1. On the control unit, enter: 129 To change the settings: 1. On the control unit, enter: 132 2. The LCD display shows: 129:ExtUnset OFF 2. The LCD display shows: 132:TA = BA OFF 3. Via the keypad, select from the following items and press: 3.
143 Contact ID report Rst 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 30 31 32 33 34 35 36 37 To change the settings: 1. On the control unit, enter: 143 UK 2. The LCD display shows: 143:Mode=Bas+Res 3.
153 Additional outputs 160 Time-confirmed alarm Additional output 3 To change the settings: 1. On the control unit, enter: 160 154 Additional outputs Additional output 4 2. The LCD display shows: 160:Confrm t=30 155 Additional outputs 3. Via the keypad, select from the following items and press: Additional output 5 156 Additional outputs Additional output 6 000999 157 Additional outputs Additional output 7 158 Additional outputs Additional output 8 4. Confirm your input.
3. Via the keypad, select from the following items and press: 162 Confirm external sirens To change the settings: 1. On the control unit, enter: 162 UK 0 2. The LCD display shows: 162:Conf Ext OFF 3. Via the keypad, select from the following items and press: 0 1 1 Conf Ext OFF External siren is on for unconfirmed alarm (command 89=1) Conf Ext ON External siren is on for confirmed alarm (command 89=1) 2 4. Confirm your input. On the control unit, enter: . 4. Confirm your input.
2. The LCD display shows: 171: Set 1 ABCD 2. The LCD display shows: 173: Unset 1 ABCD 3. Via the keypad, enter the activation level. A = overall active, B, C and D for internal active B, C or D. 3. Via the keypad, enter the activation level. A = overall active, B, C and D for internal active B, C or D. 4. To confirm, press: 4. To confirm, press: 5. The LCD display shows: 170: Set 2 ABCD 5. The LCD display shows: 173: Unset 2 ABCD 6. In the same way, enter activation level 2 via the keypad. 6.
07-12 3. Use the keypad to define: 00=OFF 01=ON 4. To confirm, press: UK 4. Confirm your input. On the control unit, enter: . 5. The LCD display shows: 175: PA 2 ON 5. The control unit acknowledges your input with a double “beep” tone and shows Installer Mode. 6. In the same way, enter the Fire 2 option via the keypad. 183 Change display 7. Continue until all outputs are entered. To change the settings: 1. On the control unit, enter: 183 8.
Not Used Fire PA Burglar Open/Close Alarm Abort Technical Alarm Alarm Confirmation RF Low Battery RF Supervision Loss RF Jamming AC Fail Tamper Alarm Open Close Zone Omitted Medical Keybox AntiMask Smoke Detector Comms Acknowledge Battery Fault System Alarm In a partitioned system Alarm partition A 23 Alarm partition B 24 Alarm partition C 25 Alarm partition D 26 Pulse Set 1 30 Pulse Set 2 31 Pulse Set 3 32 Pulse Set 4 33 Unset 1 34 Unset 2 35 Unset 3 36 Unset 4 37 00 01 02 03 04 05 06 07 08 09 10 11 12 13
201 Prog. entry delay time 1 4. Confirm your input. On the control unit, enter: . UK Define entry delay time 25.40 mm seconds. Proceed as follows: 5. The control unit acknowledges your input with a double “beep” tone and shows Installer Mode. 1. On the control unit, enter: 201 2. The LCD display shows: 201: Entry 1=20 192 Fast format channel 2 3. Via the keypad, enter the entry delay time. See command 191. Default setting: Panic to follow 4. Confirm your input by pressing. . 5.
16.4 3. Programming from exit mode, alarm reaction and exit time: B C D Partition A Exit Com. 39 Com. 62 Com. 72 Com. 76 mode Alarm Com. 47 Com. 63 Com. 73 Com. 77 reaction Exit time Com. 44 Com. 65 Com. 75 Com. 79 Programming Partitions If you are using a partitioned system then you can use the following commands for programming the partitions. 1. Use the commands 01 to 16 and X17 to X32 to assign a partition to each zone. 4. You can assign siren outputs to each partition using commands 81 to 84.
16.5 UK Examples for a partitioned system The following example shows a building with an entry area and two office areas. The two office areas are occupied by two different companies. The entry area is used by both companies. With a partitioned system, two separate alarm centres are simulated by one alarm centre.
16.6 EEPROM Fail Fire Zone nn Fire Zone nn OK Fire OK Excess Keys Test functions 090 Event memory The alarm centre stores the last 250 events. Each event is stored with date and time. The event memory can be viewed via the program menu. Keyboard Missing Keyboard Restore Keyboard Tamper Keyboard Restore Fire Zone Alarm Medical Zone Alarm Key Sw Set # 1. On the control unit, enter: 090 2. The LCD display shows the latest events first. 3. You can page forwards and backwards in the event memory.
UK Fire Z -- Rstr Soak Fail Z -Bell Tamper Rst Bell Tamper System Rearmed System Startup Tamper Z -Tamper Z -Restore Tech Z -Alarm Tech Z -Restore Tel Line Fault Tel Line Restrore User-Change UserUser-- Delete User-U -- Off-Site U -- On-Site User-System Reset User-- # Set User-- # Unset User-Time/Date User Zone # Omit User Zone # Unomit Global Tamper Global T.
097 Walk test 3. Once more press to check the connected expansion modules (max. 3). If the walk test is activated, you can trigger all zones of the alarm centre to check their function. Activate the walk test and then trigger all zones in sequence. You should also test the tamper contact. Proceed as follows: 1. On the control unit, enter: 097 To exit the programming menu, re-press 099 to exit the program menu: . 1. On the control unit, enter: 099 . 2. To exit the menu, press: . 3.
16.
TELCO2 FAULT RESTORE ZONE OMIT LR BB 573 SIA Code AT AR BC BT BT BJ YP YQ YM YR YT YR OR OR CID Code 301 301‡ 406 380 380 380 311 311‡ 311 311‡ 305 305 SIA Code CL OP OS CS CID Code 401 401 409 409 SIA Code RS TA TR TA TR XQ RH LB LS JA JT XT JV JX CID Code 412 137 137‡ 137 137‡ 380 627 628 461 625 384 - Summary Event AC LOST AC RESTORE ALARM ABORT ANTI MASK ZONE OPEN (2) ANTI MASK ZONE TAMPER (2) ANTI MASK ZONE RESTORED (2) AUX TROUBLE AUX RESTORED BATT MISSING BATT RESTORED LOW BATT LOW BATT REST
17 Technical data Voltage supply External voltage supply: 230V AC +/-10% (ambient temperature 20°C) External power consumption: 1.0A maximum Internal voltage supply: 19VAC / -10% Internal power supply: 2.0A maximum CPU power consumption: 150mA maximum Power consumption of control unit: 35mA maximum Emergency power supply: 12V DC, 7.0Ah lead rechargeable battery Outputs Transistor outputs: 12V DC, 0.
18 Troubleshooting The alarm centre shows no reaction although mains and battery power are present. The display shows one or more open zones (although all alarm contacts seem to be at rest) and the alarm centre cannot be activated or there is no permanent error tone. The alarm centre reports continuous tampering. The triggering of a sensor does not result in an alarm. External alarm does not start. Tamper alarm is not triggered although a tamper contact was opened on an alarm sensor.
19 Index of Programming Functions Date and time.................................................57 Deactivate external .......................................77 Download mode ............................................73 Dynamic test call...........................................72 Entry alarm delay ..........................................50 Entry to follow behaviour on internal active (B) ...............................................................
Siren delay .....................................................54 Siren duration................................................55 Software version ...........................................89 Status display................................................50 Switch open/close.........................................75 System Rearm ...............................................54 System Reset.................................................51 System Sabotage Reset................................
20 System plan This system plan provides information on components installed in your alarm system, their location and functioning, as well as any modifications. The system plan is always a component on the alarm system and should be stored in a safe place.