Installation User guide

64
UK
097 Walk test
If the walk test is activated, you can trigger all zones of the
alarm centre to check their function. Activate the walk test
and then trigger all zones in sequence. You should also
test the tamper contact. Proceed as follows:
1. On the control unit, enter: 097 .
2. The LCD display shows: 097: Walk Test
3. Trigger a zone. The buzzer of the control unit
emits a two-note tone. The LCD display shows:
A:ZONE nn
4. If you trigger a tamper alarm, the control unit
display shows: T:ZONE nn
5. To end the walk test, press: .
199 Measuring the resistance
The alarm centre can measure the resistance values of
the zones and display them. You can therefore see if the
right resistors have been used. Proceed as follows:
1. On the control unit, enter: 199 .
2. The LCD display shows the values.
3. To change from zone to zone, press key 1 and
key 3.
Meaning of display
Entry Meaning
NO No resistor used, zone open
2K1 2.2 KOhm resistor used
4K7 4.7 KOhm resistor used
Corresponding value in KOhm
991 Software version
Using this function, the installer can read out the software
version of the alarm centre and check whether the alarm
centre is partitioned.
1. On the control unit, enter: 991 .
2. The LCD displays the software version.
To exit the programming menu, re-press .
099 to exit the program menu:
1. On the control unit, enter: 099 .
2. To exit the menu, press:
.
3. The control unit acknowledges your input with a
long “beep” tone and displays the date and time
again.