Specifications

7-46
22
22
44
ZZZZ
+
1818
Exit Termination
A
zone with the Exit Termination zone type behaves like a zone with the Exit(OP)/Entry
zone type. However, the difference is that an exit delay time is ended immediately if this
zone is opened or closed during the exit delay time.
When you enter the protected area, the entry delay time of Group 1 starts as usual.
22
22
44
ZZZZ
+
1919
Latch Keyswitch
A
zone with the Latch Keyswitch zone type is used for activating/deactivating one or
more areas. The area remains active as long as the zone is open, and is deactivated
as soon as the zone is closed.
22
22
44
ZZZZ
+
2020
Entry Follower + Stay (Internal)
If armed, this zone works like a zone type Entry Follower. If stay armed this zone type
works like an exit/entry zone of Group 1.
22
22
44
ZZZZ
+
2121
Keyswitch Delay
A
zone with the Keyswitch Delay zone type is used for activating/deactivating
one or more areas. This zone type is comparable to zone type Key switch,
except that the area is first activated following expiry of the entry/exit delay
time of Group 1.
22
22
44
ZZZZ
+
2222
Latch KSW Delay
A zone with the Latch KSW Delay zone type is used for
activating/deactivating one or more areas. The area remains active as long as
the zone is open, and is deactivated as soon as the zone is closed. This zone
type is comparable to zone type Blockschloss, except that the area is first
activated following expiry of the entry/exit delay time of Group 1.