FURM50000 (EN) Wireless smoke alarm device BOM – No.
(EN) Installation and Operating Instructions
Wireless smoke alarm device FURM50000 (EN) Installation and Operating Instructions EN 1 EN
0359 ABUS Security-Center GmbH & Co. KG Linker Kreuthweg 5 86444 Affing, Germany 14 0359-CPR-00297 EN14604:2005+Corr:2008 Wireless smoke alarm device Model No.
1. Contents 1. CONTENTS ...................................................................................... 3 2. PREFACE AND INTENDED USE ............................................................ 6 3. LIMITATION OF LIABILITY .................................................................. 6 4. SYMBOL DESCRIPTION...................................................................... 7 5. SAFETY INFORMATION ..................................................................... 7 5.1 5.2 5.
9.1 WHAT SHOULD YOU DO IF YOU HEAR THE FIRE ALARM SOUND FROM THE DETECTOR OR FROM THE ALARM CONTROL PANEL? ............................................................ 12 9.2 10. 10.1 10.2 10.3 11. 11.1 11.2 11.3 11.4 11.5 WHAT SHOULD YOU DO IN THE EVENT OF A FALSE ALARM? .......................... 12 PREPARATION ........................................................................... 13 INSERTING OR CHANGING THE BATTERY ................................................. 13 LEARNING IN ...............
16. DECLARATION OF CONFORMITY .................................................. 29 17. DISPOSAL ..................................................................................
2. Preface and intended use Dear customer, Thank you for purchasing this wireless smoke alarm device. This device is built with state-of-the-art technology. These instructions contain important installation and operation information. Follow the directions and instructions in this manual to ensure safe operation. Store these instructions in a safe place for future reference. These instructions are part of the device.
warnings. No liability can be accepted for resulting damage. No part of the product may be changed or modified in any way. If you do not follow these instructions, your guarantee claim becomes invalid. We want you to work only with devices that incorporate state-of-the-art technology. For this reason, we reserve the right to make technical modifications. We reserve the right to make changes to these instructions without prior notice. © ABUS Security-Center GmbH & Co. KG, 03 / 2014 4.
5.2 Very high electromagnetic radiation can cause malfunctions. Therefore, avoid installation near devices which produce electromagnetic radiation. Battery warning Warning Information on handling batteries The device contains alkaline batteries with 0% cadmium (Cd) and 0% mercury (Hg) 5.3 EN Make sure that batteries are kept away from small children. Children may put batteries in their mouths and swallow them. This can cause serious harm to their health.
5.4 5.5 Do not use flammable liquids for cleaning the device. Packaging Warning Keep children away from the packaging - there is a risk of suffocation. Remove all packaging material before using the device. Functioning of the device Warning To ensure the perfect functioning of the device, please observe the following points: Do not cover the device. Do not paint over the device or cover it with wallpaper. Do not, on any account, open or repair the device.
7. Technical data Item No. Conforms to Smoke detection Power supply FURM50000 EN 14604: 2005+corr:2008 Optical using (scattered light principle) 4.5 V DC, 3 AA alkaline batteries Replacement batteries: ABUS recommend Duracell MN1500, Eveready Energizer E91 < 3.2 V Approx. 30 days before discharge Approx. 2 years 122 mm x 50 mm (Ø x H) Only approved for indoor use -10 °C - +65 °C Average relative humidity approx. 75% – noncondensing II (EN 50131-1 + A1:2009) IP 20 2 (EN 50131-1 + A1:2009) 868.
7.1 Compatible devices FUAA500XY FU80XY FU500X FUAA1001X CASA1001X FU821X AZ4120 AZ4220 7.2 Secvest Secvest 2WAY Secvest 868 Secvest IP IP alarm module Wireless universal module Terxon MX 8 zone wireless extension Terxon LX 8-zone wireless extension RoHS EC Directive The device complies with the RoHS directive.
9. Optical and acoustic alarms Simple installation Battery compartment check - the detector can only be fitted to the mounting plate when the battery is inserted. Behaviour in case of fire 9.1 What should you do if you hear the fire alarm sound from the detector or from the alarm control panel? Warning 9.2 EN Leave the premises immediately. Every second counts - there is no time to get dressed or gather valuable belongings. Use the emergency escape routes.
10. Preparation 10.1 Inserting or changing the battery Remove the mounting plate, see Fig. 1 Fig. 1 Insert 3 AA alkaline batteries (check polarity!) see Fig. 2 The activity LED now flashes 8 times. This indicates that the detector is working. Note Use good quality batteries ABUS recommend Duracell MN1500, Eveready Energizer E91. There may be a smoke detector symbol shown on the battery packaging. Look out for this when buying.
Important A fault has occurred if the activity LED flashes 1 x per second and the detector beeps every 10 seconds. Check the batteries. Reinsert or replace the batteries. 1 2 1 = Batteries, 2 = DIP switch Fig. 2 1 = Test button and activity LED Fig.
10.2 Learning in The detector transmits its identity to the receiver either wirelessly or using infrared via the activity LED. Switch the wireless alarm control panel or the receiver to learning mode. See the relevant receiver instructions for more details. Wireless option: Press and hold the test button for 3 seconds. When the alarm sounds, the detector is sending its identity by wireless.
a) b) Fig 4 Fig 4a Fig 4a shows both DIP switches in the OFF position. DIP 1 = OFF, DIP 2 = OFF 11. Selecting the location 11.1 Factors influencing performance The smoke alarm device can do 3 things: Detect smoke Generate an alarm if it has detected smoke Transmit a radio signal to the receiver if it has detected smoke. Warning The environmental conditions around the detector can influence all 3 factors.
Warning All optical smoke detectors which work in this way have the following problems: They do not detect radiant heat. They do not detect heated air. Other forms of particles can imitate smoke or cause light to be dispersed (e.g. dust, water droplets, insects or steam) They are unable to detect smoke if air movement around the detector is restricted. However, the benefits of optical smoke alarm devices are: They are robust and reliable. They do not require large and expensive batteries.
reflected by metal constructions, wire grating, heat retaining window foils, wiring, metal piping and other metallic objects. Electrical devices and other wireless transmitters can also disrupt radio signals. 11.
Locate the detector sufficiently high enough in areas where smoke accumulates For level ceilings, locate it directly on the ceiling in the centre of the room. For sloping ceilings, locate at least 50cm below the apex Where the detector cannot be attached to the ceiling, then locate it as high as possible on a wall, but with a distance of at least 30 cm from the ceiling.
11.3 Where not to locate Do not attach the detector in areas which smoke will be slow to reach. Avoid “dead” zones. These are corners between wall and ceiling. Fig. 5 Avoid the angle at the apex of a steeply sloping ceiling.
900mm Horizontal distance from peak. Fig. 6 Avoid areas where there is lots of dust. Dust can also collect both on, and inside, the detector. Smoke might no longer reach the smoke chamber as a result. Avoid places where draughts can keep smoke away from the detector, such as near windows, doors or ventilation shafts, ventilators or air conditioners.
Rooms with lots of vapour and steam, e.g. swimming pools and washing areas. Condensation can form both on, and inside, the detector. Areas in which there are a lot of insects, e.g. attic space or greenhouses Places with a high level of dust or dirt. Areas where the air can be contaminated with solvent, e.g due to thinner, petrol or turpentine. External areas. Smoke and foreign bodies can carry over great distances. 11.
Fig.
Fig. 9 11.5 Things the detector is not able to do The smoke alarm device is designed for use in a small house or apartment block, in an apartment or in an office. The following restrictions apply: The smoke alarm device is not able to detect a fire if smoke does not reach the smoke chamber. Smoke from fires in walls, in lofts, on roofs or on other floors will not reach the detector quickly enough in order to trigger the alarm in sufficient time to allow the occupants to escape without injury.
If an occupant is hard of hearing, sleeping in another room or under the influence of drugs or alcohol, then they are not able to hear the alarm and are not in a position to react to the alarm. The detector is not able to warn in a preventative manner. Avoid risks to safety such as smoking in bed, incorrect storage of flammable materials, overloaded circuits and allowing children to play with matches. 12.
13. Fix the mounting plate in place Attach the detector on to the mounting plate. Use During normal operation the detector is silent. When the activity LED is activated (see chapter 10.3 LED display), it flashes once every 60 seconds. If smoke is present in the atmosphere, then it can take up to 9 seconds before the device detects the smoke, goes into alarm status and activates the sounder. The detector transmits a radio signal to the receiver for every alarm.
13.2 Testing Place the alarm control panel or the receiver into walk test mode See the relevant receiver instructions for more details. Press and hold the test button for three seconds (see Fig 3). The sounder will begin to emit the alarm sound at the end of the three seconds. The detector transmits a radio signal to the alarm control panel or the receiver. Check whether the receiver has received the alarm.
The detector should be regularly dusted and cleaned. Clean the detector carefully when you change the batteries or following a false alarm. 15. EN Guarantee ABUS products are designed and manufactured with the greatest care and tested according to the applicable regulations. The warranty only covers defects caused by material or manufacturing errors at the time of sale.
16. Declaration of conformity “ABUS Security-Center GmbH & Co.
Batteries Your product uses batteries which are subject to the European directive 2006/66/EC and may not be disposed of with domestic waste. Find out about the regulations for the separate collection of batteries which apply in your country. Proper disposal of batteries helps prevent harm to health and the environment.