Instructions / Assembly

54
PROGRAMMING
T-SERIES
TRANSITION TEMPERATURE SETTING
Adjusts how gradually your device will shift between
levels when triggered ON by the AUTO Mode’s
temperature trigger. This will determine how much the
probe temperature needs to increase to step up to the
next level setting.
The higher the transition setting is, the wider the
temperature gap is between levels. The lower the
transition setting is, the smaller the temperature gap is
between levels. If this figure is set to zero, your device
will jump to your maximum level when triggered ON.
Press the up or down button to set a transition
threshold between 0°F and 20°F (0°C and 10°C). When
the sensor temperature first reaches or crosses the
temperature trigger point, the level will increase by one
(exiting OFF Mode). Each time the threshold level is
crossed, the level will ramp up by one until it reaches
the level set in ON Mode.
EXAMPLE
In this example, your high temperature trigger is set at
80°F, the OFF Mode level is 0, and the ON Mode level
is 6. If the transition threshold is set to 0°F, then once
the sensor temperature reaches or exceeds 80°F, the
devices will trigger to run at level 6. However, if the
transition threshold is set to 2°F, then the devices will
trigger to run at level 1 when the temperature reaches
or exceeds 80°F. It will then ramp up to level 2 when the
temperature reaches or exceeds 82°F, level 3 at 84°F,
etc. From 90°F on, it will run at level 6, the level set in
ON Mode.