System information
43
Table 15 — PIC 5 Alarm Codes (cont) 
ALARM 
CODE
(ALARMRST)
ALARM TEXT 
DESCRIPTION
RESET TYPE
ACTION TAKEN BY 
CONTROL
POSSIBLE CAUSE
INTEGRATED STARTER MODULE ALARMS (CONT)
Alm-406
ALM-406 ISM Fault — 
Overload Trip
Manual Unit shuts down.
Any phase current > 108% RLA for 
excessive time period. Alarm can 
result from significant load side cur-
rent imbalance when running at full 
load.
Check ISM_HIST screen.
Check for consistent entering con-
denser water temperature and 
water flow rates.
Check MOTOR RATED LOAD 
AMPS and STARTER LRA RAT-
ING in ISM_CONF screen.
VFD applications only: Any phase 
current > 120% for excessive time 
period.
Check ISM Status under the Main-
tenance Menu.
Alm-407
ALM-407 ISM Fault — 
Motor Locked Rotor Trip
Manual Unit shuts down.
Any LINE CURRENT > MOTOR 
LOCKED ROTOR TRIP for exces-
sive time while running after the 
LOCKED ROTOR START DELAY 
has expired.
Check MOTOR LOCKED ROTOR 
TRIP and MOTOR CURRENT CT 
RATIO in ISM_CONF screen.
Check motor nameplate data. 
Check ISM_HIST screen.
Check motor wiring and motor wind-
ing resistance.
Temporarily enable SINGLE 
CYCLE DROP OUT to capture 
power disturbances.
Check ISM Status under the Main-
tenance Menu.
Alm-408
ALM-408 ISM Fault — 
Starter Lock Rotor Trip
Manual Unit shuts down.
Any LINE CURRENT > MOTOR 
LOCKED ROTOR TRIP for exces-
sive time while running after the 
LOCKED ROTOR START DELAY 
has expired.
Check MOTOR LOCKED ROTOR 
TRIP and MOTOR CURRENT CT 
RATIO in ISM_CONF screen.
Check motor nameplate data.
Check ISM_HIST screen.
Check motor wiring and motor wind-
ing resistance.
Temporarily enable SINGLE 
CYCLE DROP OUT to capture 
power disturbances.
Check ISM Status under the Main-
tenance Menu.