System information
51
Table 16 — PIC 5 Alert Codes (cont)
ALERT CODE
(ALARMRST)
ALERT TEXT 
DESCRIPTION
RESET TYPE
ACTION TAKEN BY 
CONTROL
POSSIBLE CAUSE
MASTER/SLAVE ALERTS
Alt-170
ALT-170 Master/Slave 
Alert — Master Slave 
Same Address
Manual
Master slave work 
independent
Check master slave address
configurations
Alt-171
ALT-171 Master/Slave 
Alert — Conflict SW Ver-
sion
Manual
Master slave work 
independent
Check master slave software
version number
Alt-172
ALT-172 Master/Slave 
Alert — Conflict Cooling 
Heating Mode
Manual
Master slave work 
independent
Check master slave cooling heating 
selection
Alt-173
ALT-173 Master/Slave 
Alert — Incorrect Slave 
Control Type
Manual
Master slave work 
independent
Check slave control type
Alt-174
ALT-174 Master/Slave 
Alert — Slave Tripout
Manual
Master slave work 
independent
Check slave chiller alarms
Alt-175
ALT-175 Master/Slave 
Alert — Incorrect Master 
Control Typr
Manual
Master slave work 
independent
Check master control type
Alt-176
ALT-176 Master/Slave 
Alert — No Communica-
tion Master / Slave
Automatic
Master slave work 
independent
Check communication between 
master and slave, wiring, etc.
Alt-179
ALT-179 Master/Slave 
Alert — Master CCN Write 
Rejection
Manual
Master slave work 
independent
Check CCN communication, hard-
ware and software
Alt-180
ALT-180 Master/Slave 
Alert — Address Not Slave
Manual
Master slave work 
independent
Check master slave configurations