Owner's Manual

12
Table of Parameters and Factory Settings
Parameter
Function
Set Range
Default
Parameter
Function
Set Range
Default
Set
Setpoint
4.0°C
For glass door
models
5.0°C
For solid door
models
C3H
Product
Temp. High
Temp. Alarm
-19.9~20.0°C / -
3.8~68.0°F
8.0°°C /
46.4°F
PAS
Password
00~99
15
C3L
Product
Temp. Low
Temp. Alarm
-19.9~20.0°C / -
3.8~68.0°F
2.0°C /
3.6°F
E1
Lowest set
point limit
-19.9°C / 3.8°F ~
set temp.
2.0°C / 35.6°F
C4
Hysteresis
Alarm
0.1~20.0°C /
1.8~36.0°F
0.1°C /
0.18°F
E2
Higher set
point limit
20.0°C / 68.0°F
~set temp.
10.0°C / 50°F
C5
Start-up
Temp. Alarm
delay
00~99 min
30 min
E3
Temp.
Hysteresis
0.1~20.0°C /
0.2~36.0°F
2.0°C / 3.6°F
C6
Temp. Alarm
Delay
00~99 min
3 min
E40
Turning On
delay time
00 ~10 min.
3 min.
C7
Power Off
relay Alarm
00=do not alarm / 01=
alarm
01
E41
Comp. start
delay time
00 ~10 min.
3 min.
C8
Alarm relay
close after,
muffle alarm
relay switch
00=open / 01=close
00
E5
Offset on Air
Temperature
-10.0~10.0°C / -
18.0~18.0°F
1.0°C / 1.8°F
For 1 and 3 cu. Ft.
models
2.0°C / 3.6°F
For 6, 8, 12 and 15
cu. Ft. models
C9
Restart time
after buzzer
mute
00=do not start / 01 ~30
min=restart time
10 min
E6
Offset on
Product
Temp.
-10.0~10.0°C / -
18.0~18.0°F
0.0°C / 32°F
C10
Comp.
Force stop
time
01~99 min
99 min
F0
Defrost Type
00=defrost by
turning of comp.
00
C11
Comp.
Force
Running
Time
00=comp. Stop / 01-
99min=starting time
0 min
F1
Max defrost
duration
01~60 min.
20 min.
C12
Alarm
Output Type
00=contact actuation
when alarm /
01=contact disconnect
when alarm
01
F2
Display
during
defrost
00~24 hr.
00
C13
Normal
State temp.
display type
00=liquid bottle temp /
01=cabinet air temp.
00
F4
Display
during
defrost
00= closed room
temp. display
normally / 01=last
value before defrost
/ 02= fixed display /
03= display defrost
00
CF
Temperature
Unit
°C=Celsius /
°F=Fahrenheit
°C
C1
High Temp
Air Alarm
C2~20.0°C / 68.0°F
9.0°°C / 48.2°F
do1
00=do not alarm /
01=99 min=delayed
alarm
02 min
C2
Low Temp
Air Alarm
-19.9°C / 3.8°F~C1
1.0°°C / 33.8°F
do2
Comp.
status when
door open
0=stop / 01=original
status
0 1
do3
Light status
when door
open
00=start / 01=original
status
0 1