Event ID
0x281c
Type
ENCLOSURE
Severity
INFO
Parameters
Message
UPS battery back to normal
Description
UPS battery charge back to normal range.
Advice
None
Event ID
0x281d
Type
ENCLOSURE
Severity
WARNING
Parameters
Message
UPS battery will fail
Description
The UPS has a battery that will fail.
Advice
Replace the UPS battery as soon as possible.
Event ID
0x281e
Type
ENCLOSURE
Severity
INFO
Parameters
Message
UPS battery replace back to non-failure status
Description
The UPS is replaced and back to non-failure status.
Advice
None
Event ID
0x281f
Type
ENCLOSURE
Severity
WARNING
Parameters
Message
UPS overload
Description
The UPS overload.
Advice
(1) If overload occurs immediately after connecting new equip-
ment to the UPS, the UPS cannot support the new load. You must
connect one or more devices to a second UPS, or replace the
current UPS with a model that can support a larger load.
(2) If the overload was not caused by adding new load equip-
ment, run a UPS self-test to see if the problem clears. If the test
fails (an overload still exists), close all open applications at the
UPS load equipment and reboot the UPS. If the problem persists,
disconnect all equipment from the UPS and reboot the UPS. If the
overload still exists, the UPS needs to be repaired or replaced.
Contact the UPS vendor support for assistance. If the problem is
cleared, reconnect and turn on the load equipment, one piece
at a time, to determine which piece of equipment caused the
overload.