Technical data

32 Chapter 2 Planning for Installation and Operation
2.4.2 Temperature and Humidity Requirements
Table 2.8 lists the temperature and humidity requirements for the AMS200 subsystem.
Table 2.8 Environmental Specifications
Item Specification
In operation (°C) 10 to 40
In non-operation (°C) -10 to 50
In transport/storage (°C) -30 to 60
Temperature
Temperature change rate (°C/h) 10 or less
In operation (%) 8 to 80
In non-operation (%) 8 to 90
Humidity
Maximum wet bulb temperature (°C) 29 (non-condensing)
In operation (m) -300 to 3,000 Altitude
In non-operation (m) -300 to 12,000
2.4.3 Input Power and Insulation Performance Specifications
The following tables list the input power and insulation performance specifications for the
AMS200 rack-mount models and the AMS200 floor model.
Conductors shall be provided with 30 A over current protection in accordance with Article
240 of the National Electrical Code, ANSI/NFPA 70, and the Canadian Electrical Code, Part 1,
CSA C22.1, Section 14.
Table 2.9 Input Power and Insulation Performance Specifications for Rack-Mount Model
Rack-Mount Model Item
Model
RKS RKAJ RKAJAT
Input voltage (V) AC 100/200 (100-120/200-240)
Frequency (Hz) 50/60 ± 1
Number of phases, cabling Single-phase with protective grounding
Steady-state current (A) (Note1) (Note2)
4.0×2/2.0×2 2.6×2/1.3×2 2.4×2/1.2×2
Breaking current (A) 16.0 10.0
Steady state (VA) 800 or less 520 or less 480 or less Required power
Starting state (VA) 800 or less 560 or less 480 or less
Input power
specification
Heat value (kJ/h) 2,880 or less 1,875 or less 1,730 or less
Insulation Insulation withstand voltage AC 1,500 V (10 mA, 1 min)
performance Insulation resistance DC 500 V, 10 M Ω or more
Note 1: Power current of Nx2 described above is required for operation by a single power supply unit.
Note 2: It indicates the current consumption in the usual state. When a power supply failure occurs, the power
consumption is provided by the single power supply for the subsystem.