Quick Reference Guide

Dual 300W Forward Phase Dimmer | 009-2118-00 45 Perseverance Way, Hyannis MA 02601
Copyright ©2022 Savant Systems, LLC | 220124 4 of 4 Savant.com | 508.683.2500
NOTES
Circuit Test Instructions
Use the instructions below to test that the dimmer module is functioning correctly. The setup requires the following:
Forward Phase Companion Dimmer Module.
Resistive loads with maximum amperage of 2.5 Amps.
15 amp circuit breaker.
Breaker test panel. The type of dimmer module determines the type of breaker panel (plug-on neutral or not).
120V AC source
1. Plug a feeder breaker and a Forward Phase Dimmer Companion Module into the circuit breaker test panel. The feeder breaker should not
exceed 15A.
2. Connect the output of the feeder circuit breaker to the INPUT
screw port on the dimmer module.
3. Connect a supported type load to Output A on the dimmer module.
4. Connect a second supported type load to Output B on the dimmer
module.
5. Connect the unused side of each load to the neutral bus bar in the
breaker panel.
6. On modules that contain a neutral pigtail wire, connect the neutral
wire to the neutral bus bar.
7. Apply power to the breaker panel (not shown in diagram)
8. Toggle the feeder circuit breaker On.
9. To test, toggle the CIRCUIT POWER switches A and B to ON and
verify both loads switch On.
10. Toggle the CIRCUIT POWER switches to AUTO and verify the loads
switch O .
PANEL CIRCUIT
BREAKER
OUTPUT
OUTPUT
A
B
INPUT
CIRCUIT POWER
ON
AUTO
PAIR
AB
FORWARD PHASE
DIMMER
Neutral Bus Bar
Neutral pigtail wire from
the companion module
Load B
2.50 Amps
Load A
2.50 Amps
2
3
4
5
6
9 10
1
8
IMPORTANT!
When making connections, observe all general electrical best practices including wire sizing guidelines.
The GPM-QP2FPD05-21 and GPM-Q2FPD05-21 modules can accept up to a #14 AWG wire. See the Branch Circuit Minimum Size of
Conductors table on the previous page for wire sizing information
Dual 300W Forward Phase Dimmer | 009-2118-00 45 Perseverance Way, Hyannis MA 02601
Copyright ©2022 Savant Systems, LLC | 220124 1 of 4 Savant.com | 508.683.2500
A
PAIR
F
DO NOT
PRESS ON
SCREEN
REMOVE AFTER
INSTALLATION
CIRCUIT POWER
A
B
FORWARD PHASE DIMMER
GPM-QPFPD05
MODULE INPUT:
LOAD INPUT:
I
NDO
OR USE ONLY
#14-8 AWG Cu ONLY
HOME AUTOMATION EQUIP
120VAC 5A MAX TOTAL
120VAC 60Hz
120VAC 60Hz
IC ID: 10798A-QP2FPD05
FCC ID: PUU-QP2FPD05
E523609
YYWW
LOAD OUTPUT:
OUTPUT
INPUT
OUTPUT
A
B
C
B
D
E
G
A
Multi-Page LCD screen can display the following:
Energy usage in watts at the output.
Percentage of brightness at the output.
Firmware, Mac Address, and FCC/IC Info.
Real time Bluetooth status connectivity icon.
B
Manual Load Switches - Toggle to the ON position to switch
load on. Toggle switch to AUTO for normal operation. Switch
A controls output A and Switch B controls output B.
C
PAIR Button - The PAIR button is a multi-use button. The
duration that the button is pressed and held determines the
function that gets initiated.
Press and Release - Cycles through the screens available on
the LCD (POWER > DIMMER > INFO 1 > INFO 2).
Press and hold - Press and hold for 2 seconds to put module
into pairing mode. Press and hold for 5 seconds to reset.
D
Input Power Connection - Connect the 120V AC output from
the companion breaker to this input.
E
Output Connections - The connections are labeled OUTPUT A
and OUTPUT B. Connect each output to a separate load. See
the Wiring section (page 2).
F
120V AC Connection - Plugs into the 120V AC bus bar in the
breaker panel. The voltage on this connection powers the
module.
G
Neutral - The model number of the module determines the
type of neutral connection on the module:
Plug-On Neutral - Positioned on the bottom of the
module is a neutral clip that plugs directly onto the
neutral bar.
Pigtail Neutral - A neutral wire protrudes from the
module’s rear and gets wired to the neutral bar in the
breaker panel
Minimum Supported Release
Savant OS da Vinci 10.2
Supported Load Types
Standard
Confi guration
Dimmable circuits – Incandescent, halogen,
magnetic low-voltage transformer, and
forward phase dimmable fl uorescents
Regulatory
Safety and Emissions
FCC Part 15 UL ICES 003
Contains FCC ID: PUU-QP2FPD05
Contains IC: 10798A-QP2FPD05
RoHS Compliant
Recommended Load Center Types
All QO™ compatible modules fi t into ¾ inch load centers
Dimensions and Weights
Height Width Depth Weight
Module
(QO)
1.48 in.
(3.76 cm)
5.00 in.
(12.70 cm)
2.63 in.
(6.68 cm)
.5 lbs
(.23 kg)
Shipping
1.71 in.
(4.34 cm)
7.50 in.
(19.05 cm)
4.30 in.
(10.92 cm)
1.0 lbs
(.45 kg)
Features
Each output can control dimming loads up to 300 VA (volt-
ampere). See the Branch Circuit Minimum Size of Conductors table
on page 2.
All QO™ style dimmer modules are compatible with Schneider
Electrics Square D™ QO™ load centers.
Modules are forward phase (leading edge) type dimmers.
Built-in energy monitoring; +/- 3% accuracy / 1 sec sample time.
Communicates over the air using Bluetooth Low Energy (BLE)
technology.
Color LCD display for easy identifi cation and load status.
Dual 300W Forward Phase Companion Module Dimmer
Quick Reference and Installation Guide
Specifi cations
Box Contents Descriptions
(1) Forward Phase Dimmer Module
GPM-QP2FPD05-21 QO™ Plug-on Neutral -or-
GPM-Q2FPD05-21 QO™ Pigtail
(1) Product Information and Regulatory Insert (009-1950-xx)
(1) Quick Reference Guide (this document)
Electrical and Safety Characteristics
Screw Tighten Torque 3.0 Nm
Wire / Conductor Type Copper (Cu) only
Pollution Degree 2
Purpose of Control
Operating Control, Smart Relay Control
Module or the equivalent
Software Class A
Impulse Voltage 2500V
Standards
Wireless
Bluetooth Low Energy (BLE)
2.4 GHz radio frequency
Environmental
Temperature 32° to 104° F (0° to 40° C)
Humidity 5% to 85% Relative Humidity (non-condensing)
Location Indoor Use Only
Construction of Control
Open Type Independently mounted for fl ush mounting
Power
Input Power
(powers the module)
120V AC (+/-10%) @ 60 Hz, 0.1A (max)
Input Power
(from external source)
120 AC per input - 15A (max)
Load Power
300VA 2.5A @ 120V AC per channel
600VA 5.0a @ 120V AC per channel
(when just one channel is used)
Features of Automatic
Action
Type 1 Action