Installation Manual

Reusable mechanical connectors and ared joints are not allowed indoors.
(EN Standard Requirements).
Mechanical connectors used indoors shall have a rate of not more than 3g/year at 25%
of the maximum allowable pressure. When mechanical connectors are reused indoors,
sealing parts shall be renewed. When ared joints are reused indoors, the are part
shall be re-fabricated. (UL Standard Requirements)
When mechanical connectors are reused indoors, sealing parts shall be renewed. When
ared joints are reused indoors, the are part shall be re-fabricated. (IEC Standard Requirements)
Mechanical connectors used indoors shall comply with ISO 14903.
Safety
Precautions
Amount of refrigerant
to be charged (kg)
Installation height
(m)
Installation height
(m)
Minimum room
area (m²)
Amount of refrigerant
to be charged (kg)
Minimum room
area (m²)
1.0 0.6 /1.8 /2.2 9 /1 /1
1.05 0.6 /1.8 /2.2 9.5 /1.5 /1
1.1 0.6 /1.8 /2.2 10.5 /1.5 /1
1.15 0.6 /1.8 /2.2 11.5 /1.5 /1
1.2 0.6 /1.8 /2.2 12.5 /1.5 /1
1.25 0.6 /1.8 /2.2 13.5 /1.5 /1
1.3 0.6 /1.8 /2.2 14.5 /2 /1.5
1.35 0.6 /1.8 /2.2 16 /2 /1.5
1.4 0.6 /1.8 /2.2 17/2 /1.5
1.45 0.6 /1.8 /2.2 18 /2 /1.5
1.5 0.6 /1.8 /2.2 19.5 /2.5 /1.5
1.55 0.6 /1.8 /2.2 21 /2.5 /2
1.6 0.6 /1.8 /2.2 22 /2.5 /2
1.65 0.6 /1.8 /2.2 23.5 /3 /2
1.7 0.6 /1.8 /2.2 25 /3 /2
1.75 0.6 /1.8 /2.2 26.5 /3 /2
1.8 0.6 /1.8 /2.2 28 /3.5 /2.5
1.85 0.6 /1.8 /2.2 29.5 /3.5 /2.5
1.9 0.6 /1.8 /2.2 31/3.5 /2.5
1.95 0.6 /1.8 /2.2 33 /4 /2.5
2.0 0.6 /1.8 /2.2 34.5 /4 /3
2.05 0.6 /1.8 /2.2 36 /4 /3
2.1 0.6 /1.8 /2.2 38 /4.5 /3
2.15 0.6 /1.8 /2.2 40 /4.5 /3
2.2 0.6 /1.8 /2.2 41.5 /5 /3.5
2.25 0.6 /1.8 /2.2 43.5 /5 /3.5
2.3 0.6 /1.8 /2.2 45.5/5 /3.5
2.35 0.6 /1.8 /2.2 47.5/5.5 /4
2.4 0.6 /1.8 /2.2 49.5 /5.5 /4
2.45 0.6 /1.8 /2.2 51.5 /6 /4
2.5 0.6 /1.8 /2.2 54 /6 /4
2.55 0.6 /1.8 /2.2 56 /6.5 /4.5
2.6 0.6 /1.8 /2.2 58 /6.5 /4.5
2.65 0.6 /1.8 /2.2 60.5/7 /4.5
2.7 0.6 /1.8 /2.2 63 /7 /5
2.75 0.6 /1.8 /2.2 65 /7.5 /5
2.8 0.6 /1.8 /2.2 67.5 /7.5 /5
2.85 0.6 /1.8 /2.2 70 /8 /5.5