MTU Instruction
for Mini-Max Electronic Gas Volume Corrector
the red wire from the black cable into
Terminal 2. Tighten the screw on the
side. Insert the red wire from the gray
cable (if used) into Terminal 3. Tighten
the screw on the side.
Step 6 – Press the terminal block back
onto the connector on the circuit board.
Make sure that it seats fully. This
completes the wiring of the MTU.
Mini-Max Configuration
Notes
The Mini-Max must be properly
programmed to have the corrected and
uncorrected outputs available on TB1.
Per the Mini-Max Operator’s Guide:
Item No. 093 should be set to
Code 0. This will select the
Corrected output to be on for TB1
slot 2.
Item No. 094 needs to be
programmed to Code 2 in order to
select the Uncorrected output to be
on TB1 slot 3.
Item 096 and 097 should be set to
Code 2, which will set the display
to 6 digits and match the reading
length stored in the MTU.
Item No. 115 should be left at the
default of 0 which will give a pulse
width of 0.0625 Sec.
Item No. 090 and 092 need to be
programmed to match the scaling
in the MTU. Ex. Code 1 = CU FT x
10; Code 2 = CU FT x 100.
Other settings may be needed for the
Mini-max to operate correctly. See the
Mini-Max Operators Guide for further
instructions.
Page 93