Technical data
EDITION JUNE 2005
LPG VALVES & EQUIPMENT
DIVISION
The features described in this illustration do not bind the manufacturer.
GSE 35
67.0776 (above gr.)
67.0794 (undergr.)
Multiservice Valve
equipped with a pressure
gauge in glycerine bath,
0÷25 bar scale, and a fixed
level gauge to ensure
80% of tank filling.
It allows optional
installation of an outlet devi-
ce with excess flow.
GS 41
67.0773
(above gr.)
Multiservice Valve
with vertical outlet
and fixed liquid level tube
which ensures 85% max. filling
of the tank. It incorporates an
excess flow valve, which closes
when the flow reaches a rate of
42÷54 Kg/h propane (a first
stage propane regulator with
40 Kg/h capacity and 2 bar
setting point can be attached).
Multiservice Valves
Part number
Container Outlet Excess flow Closing Flow-CE
Wrench Grip
Fixed level gauges
Master gauge Relief
Connection Connection device (Propane) (mm) with dip tube insp. flange devices
67.0775 (GS 50 above gr.) 3/4” – 14 NPT W20x 1/14” LH Inlet Built-in 30 (square) Yes
67.0792 (GS 50 undergr.) for both for both for both for both Yes
N/a
67.0776 (GSE 35 above gr.) 3/4” – 14 NPT 885” – 14 NGO- Installed onto 30 (square) Yes
67.0794 (GSE 35 undergr.) for both LH-INT for both
outlet connector
for both Yes
N/a
67.0773 (GS 41 above gr.)
3/4” – 14 NPT
UNI ISO 228/1-
Inlet Built-in 40 (hex.) N/a N/a
G 3/4-B
67.0774
(GS 89 above gr.)
1 1/4”– 11.5 UNI ISO 228/1-
Inlet Built-in 40 (hex.) N/a N/a
NPT G 3/4-B
67.0796 (GS 90 undergr.)
1 1/4”– 11 1/2 UNI ISO 228/1-
Inlet Built-in 40 (hex.) N/a
Liquid pressure
NPT G 3/4-B relief valve
(2)
ORDERING INFORMATION
GS 89
67.0774 (above gr.)
Multiservice Valve with
vertical outlet and fixed liquid
level tube which ensures 85%
max. filling of the tank. It
incorporates an excess flow
valve, which closes when the
flow reaches a rate of 42÷54
Kg/h propane (a first stage
propane regulator with 40
Kg/h capacity and 2 bar
setting point can be attached).
GS 50
67.0775 (above gr.)
67.0792 (undergr.)
Multiservice Valve equipped with
a pressure gauge in glycerine
bath, 0÷25 bar scale, and a fixed
level gauge to ensure 80% of tank
filling. It incorporates an excess
flow valve, which closes when the
flow reaches a rate of 37,5÷45
Kg/h propane (a first stage propa-
ne regulator with 40 Kg/h capaci-
ty and 1,5 bar setting point can be
attached).
GS 90
67.0796
(above gr.)
Multiservice Valve with vertical outlet. It incorporates an excess flow valve, which closes when the flow
reaches a rate of 42÷54 Kg/h propane (a first stage propane regulator with 40 Kg/h capacity and 2 bar
setting point can be attached). It is a special underground fitting equipped with a pressure relief device that
enables liquid discharge at 14 bar.
* see page Spe1, item 16.0.950.0039/0052. Two models depending on the capacity required – please specify when ordering
** please specify length of dip tube, tank capacity and diameter when ordering
(1)
Data valid when upstream pressure 2 bar and first stage 40 kg/h regulator connected – excess flow valve performance.
(2)
Pressure relief device designed to discharge liquid in case of overpressure – The device starts to discharge liquid at 14 bar with a capacity of 1500 lt/h water.
Between
42-54 kg/h
propane
(1)
Available
on all types
with tubes
in different
lengths**
www.cavagnagroup.com
Ae1