User's Manual
59
Brand of ACOEM
3.7.5.7 Tabs 2 and 3 for “Defect factor” measurement type:
Tab “Defect factor”:
Measurement time (s): 1 to 20
Tab “Alarm”: same as for Overall
Recommended values are
Alarm type: High
Alarm threshold: 6 DEF
Danger threshold: 9 DEF
3.7.5.8 Tabs 2 and 3 for “Kurtosis” measurement type:
Tab “Kurtosis”:
High-pass filter*: Value in Hz
Low-pass filter*: Value in Hz
* High and low pass filters are keyboard inputs.
High pass: from 50 Hz to half of the value of the low-pass filter.
Low pass filter: from twice the high-pass filter to 20 kHz. Minimum value is 500 Hz
Cycle time (s): 1 to 5
Tab “Alarm”: same as for Overall
3.7.5.9 Tabs 2 and 3 for “Position” measurement type:
Tab “Position”:
Peak hold: Yes or No.
Measurement time (s): 1 to 20
Tab “Alarm”: same as for Overall