Specifications
8
SmartReader Plus 3
FEATURES
• Eight channels
• Monitor current
and voltage (single
or 3-phase)
• Determine energy
consumption
Eight-Channel AC Current and Voltage Data Logger
The SmartReader Plus 3 easily and accurately records AC current and voltage.
Simply connect ACR’s current probes (which  are  clamped  around the power
leads) and ACR’s  voltage  transducer to  the data  logger and  begin  recording.
From the data collected, you can even determine  energy consumption (kWh)
using ACR’s  powerful,  versatile  and  easy  to  use  software,  TrendReader
®
Standard. 
PRODUCT SPECIFICATIONS
No. of Channels:
Eight - One for ambient temperature
- Four for AC current (with ACR current probes)
- Three for AC voltage (with ACR voltage trans-
ducers, single phase or 3-phase) 
Current Ranges*:
5, 25, 100, and 250 Amps -
With A60FL (60 Hz) and 
A65FL (50 Hz) current probes
10, 50, 250, and 500 Amps -  With A70FL (60 Hz) and A75FL
(50 Hz) current probes
*Up to 3000 Amps with the ACR CT-50-2 current transformer
Nominal Voltage Ranges:
120 V (1 phase, 60 HZ)
480 V (3 phase, 60 HZ)
Accuracy:
Voltage Channels: +/- 0.5% F.S.
Current Channels: +/- 3.5% F.S. 
a
bove the lowest 10% of range
Memory Size:
32 KB, 128 KB and 1.5 MB
Common Specifications:
See page 6
Software Specifications:
See page 34
Remote & Network Communications:
See page 38
Accessories:
ACR AC Current Probes
ACR AC Voltage Transducers
ACR CT-50-2 Current Transformer
Order Information
MODEL MEMORY  CATALOG #
SRP-003 32 KB 01-0010
SRP-003-128K 128 KB 01-0114
SRP-003-1.5M 1.5 MB 01-0143