Specifications
Diagnostic Guidelines
By means of pressure reading:
60
 Pressure 
Data 
Circuit 
Too low 
A little low 
Normal 
A little high 
Too high 
Probable cause 
High side 
Low side 
Ɣ
Ɣ
1.  Overcharged with refrigerant. 
2.  Non-condensable gases in refrigerant circuit (e.g. air) 
3.  Obstructed air-intake / discharge. 
4.  Hot air short circuiting in outdoor unit. 
High side 
Low side 
Ɣ
Ɣ
1.  Poor compression / no compression (compressor 
defective) 
2.  Reversing valve leaking. 
High side 
Low side 
Ɣ
Ɣ
1.  Undercharged with refrigerant. 
2. Refrigerant leakage. 
3.  Air filter clogged / dirty (indoor unit). 
4.  Indoor fan locked / seized. 
5.  Defective defrost control, outdoor coil freeze up (heating). 
6.  Outdoor fan locked / seized (heating). 
High side 
Low side 
Ɣ
Ɣ  1.  Outdoor fan blocked (cooling). 
2.  Outdoor coil dirty (cooling). 
3.  Indoor fan locked / seized (heating). 
4.  Indoor air filter clogged / dirty (heating). 
5.  Non-condensable gases in refrigerant circuit (e.g. air) 
High side 
Low side 
Ɣ
Ɣ
1.  Air intake temperature of indoor unit too high. 