Technical data
Diagnosis
Operating Manual
103ID 442281.00
WE KEEP THINGS MOVING
13
13.3.36 *ParaModul ERROR:update firmware!
13.3.37 *ParaModul ERROR: file not found
Resolution Level Response
The versions of configuration and firmware
do not match.
— The configuration does not start.
Possible cause Test Measure Acknowledgement
Old firmware version — Apply a suitable configuration or firm-
ware.
—
Resolution Level Response
The Paramodule file can not be read. — The configuration does not start.
Possible cause Test Measure Acknowledgement
May have been
switched off during the
A00 action.
— • Apply a suitable configuration via
POSITool and then save it (A00)
• Attach a suitable Paramodule.
—
Faulty or unformatted
Paramodule
— Replace the Paramodule. —