12.2 Replacing an application
This chapter provides you with a guide to the simple change of an application
without extra aids. Only the Paramodule must be replaced. In the Paramodule,
the action A00 save values stores the programming and the parameterization of
the inverter safe from a power failure.
The following conditions apply to the replacement:
The hardware configuration (option boards, motor settings, etc.) stored on the
Paramodule corresponds to the drive which will use the data of the Paramod-
ule in the future.
The programming and parameterization stored on the Paramodule was test-
ed beforehand.
After the Paramodule has been exchanged and the drive has been tested, set
up the drive again (referencing, parameter optimization, etc.).
Proceed as shown below:
4 Plug Paramodule into the inverter to be installed!
Inverter to be installed
5 Remove the inverter to be replaced and install the new inverter. Adhere to
the mounting instructions!
6 Schließen Sie die Versorgungsspannung an.
Ö During startup the inverter loads the configuration from Paramodule and
continues using the application of the previously installed inverter.
7 Validate the Safe Torque Off safety function.
See also operating instructions ASP 5001, ID 442181.
Ö The inverter has been replaced.
Replacing the application
1 Start the action A00 save values. Wait until the action has been concluded
with the result 0:error free.
2 Turn the power supply of the inverter off. Wait until the indication on the dis-
play disappears.