13.3 Events
13.3.1 31:Short/ground.
13.3.2 32:Short/gr.int
Resolution Level Response Fault counter
The hardware short-circuit switch-off is ac-
tive. The output current is too high.
Malfunc-
tion
The motor continues to coast. The brake chopper
cuts out. Any existing brakes are engaged if they
were not released via F100 independent of the de-
vice controller.
Z31
Possible cause Test Measure Acknowledgement
Interwinding fault Check the motor. Replace the motor. Switch the device on/off
or programmed ac-
knowledgement
Fault in motor cable Check the cable Replace the cable
Connection fault Check the connection, e.g. whether
V or W is connected to PE at X20 U.
Correct the connection.
Resolution Level Response Fault counter
An internal test is performed when the con-
troller part power supply is switched on. An
existing short-circuit causes a malfunction.
Malfunc-
tion
The inverter cannot be enabled. Z32
Possible cause Test Measure Acknowledgement
There is an internal de-
vice fault.
— Please contact our service depart-
ment, see section 1.4 Further sup-
port
Switch the device on/off
or programmed ac-
knowledgement