Technical data

Diagnosis
Operating Manual
82ID 442281.00
WE KEEP THINGS MOVING
13
13.3.16 47:TorqueLimit
Resolution Level Response Fault counter
The maximum torque permitted for static
operation is exceeded in the control
types of servo control, vector control or
sensorless vector control (E62 act. pos.
T-max, E66 act. neg. T-max). Note that
in many cases, operation at the torque
limit is desirable.
Can be pa-
rameterized in
U20 and U21
The parameterized malfunction reaction in the
A29 parameter.
Z47
Possible cause Test Measure Acknowledgement
Incorrect parameteriza-
tion
Check whether the torque moments
in E62 and E66 correspond with your
projection.
Correct the setting of the parameters
in C03, C05, C06, C130 and C230.
Can be acknowledged for mal-
function level by switching the
device off/on or programmed
acknowledgement.
Drive overloaded Check the load situation of your
drive.
Rectify any existing blockages.