Technical data

Diagnosis
Operating Manual
88ID 442281.00
WE KEEP THINGS MOVING
13
9:ECS5000failure ECS 5000 was detected, installed
and failed.
Uninstall and reinstall the option.
Replace the option.
Switch the device on/off or
programmed acknowledge-
ment
10:24Vfailure Failure of 24V supply for XEA 5001
or LEA 5000.
Check and, if necessary, correct the
24V supply of the option.
Switch device off/on
11:SEA5001failure SEA 5001 was detected, installed
and failed.
Uninstall and reinstall the option.
Replace the option.
Switch the device on/off or
programmed acknowledge-
ment
12:REA5001failure REA 5001 was detected, installed
and failed.
Uninstall and reinstall the option.
Replace the option.
Switch the device on/off or
programmed acknowledge-
ment
13:PN5000 Failure1 PN 5000 was detected, installed and
failed. Basic hardware tests have de-
tected an error.
Check whether the PN 5000 ac-
cessory was correctly installed.
Check whether suitable EMC
measures were taken.
Check whether only PROFINET-
certified components were con-
nected to the inverter.
Check whether the cabeling and
connections correspond to the
PROFINET standard.
Contact the service department,
see section 1.4 Further support.
Switch device off/on
14:PN5000 failure2 PN 5000 was detected, installed and
failed. Basic software tests have de-
tected an error.
Switch device off/on
15:PN5000 failure3 PN 5000 was detected, installed and
failed. The watchdog function of the
PN-5000 monitoring system has de-
tected an error.
Switch device off/on
17:opt.2 too old for SDS 5000: Option board with old
hardware version (XEA 5001: from
HW 10, REA 5000: from HW 19)
Install the projected option.
Adjust the projection.
Switch device off/on
Cause Description Measure Acknowledgement