Safety Instructions

3 of 3
rPP20 Relay Pack
POWER/RELAY PACK
FAMILY INSTRUCTIONS
Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitycontrols.com © 2019 Acuity Brands Lighting, Inc. All rights reserved. Rev. 05/08/2020
912-00056-002 FCC ID: 2ADCB-RMODIT IC: 6715C-RMODIT IFETEL: RCPACRM18-1879 Acuity Brands Lighting Inc. RMODIT
WIRING (DO NOT WIRE HOT)
USER BUTTON
On the side of the controller is a lighted user button. This button can be used for testing and re-programming purposes.
User Button (also functions as LED
indicator)
UL924 Test (ER model only)
Use this test to confirm that the lighting load is properly connected and
provides the necessary output in event of loss of power.
1. Press and Release the button.
2. Relay will close and dimming output will go to full brightness for 4
seconds.
3. After 4 seconds expires, the device returns to its previous state and the
indicator LED shuts off.
LED Diagnostics
The LED is illuminated whenever the button is depressed, and blinks to
confirm the start of maintenance mode. Depress the button from the side to
view LED and confirm that the device is operational.
Maintenance Mode
Use this mode if you are unable to Identify this device within the Clairity Pro application.
1. Press and hold button for 10 seconds, then release. LED will begin to flash rapidly
after 10 seconds and stop flashing when the button is released.
2. Immediately press and hold button again for 10 seconds, then release. LED will
begin to flash rapidly after 10 seconds and stop flashing when the button is released.
3. The LED will flash twice to confirm entry into Maintenance Mode.
For 60 minutes, the device becomes identifiable in the Clairity Pro app and available
for direct connection from mobile app to device (without requiring Group Monitor to be
present, in case of a fault or connectivity issue with the Group Monitor).
Clairity Pro can then be used to perform functions such as:
* Reprogram device settings
* Reset device network settings
* Firmware update
* General troubleshooting and diagnostic functions
UL924 Sequence of Operation
ER Units: When normal power sense leads
have absense of voltage
EM Units: For 90 minutes following any
complete AC power interruption 30 ms:
Relay is closed and 0-10V dimming is at high
end trim level
Device ignores wireless lighting control
commands
24VDC output is disabled
Do NOT wire while connected to live power,
damage may occur.
Legend
BLK Unswitched Hot 120-277V
WHT Neutral
BLU Switched Output
VIO 0-10V Dim
GRY 0-10V Common
RED (Terminal) +24VDC
BLK (Terminal) DC Common
GRN Ground
RPP 24V
RPP 24V
LOAD
}
Normal
+24 VDC
}
Legend
BLK Unswitched Hot 120-277V
WHT Neutral
BLU Switched Output
VIO 0-10V Dim
GRY 0-10V Common
RED (Terminal) +24VDC
BLK (Terminal) DC Common
GRN Ground
RPP DS 24V
RPP DS 24V
LOAD
}
Normal
+24 VDC
}
RPP DS 24V EM
120 V -
277 V
EMERGENCY
0-10 VDC Ballast
or LED Driver
}
RPP D/DS 24V EM
Emergency
Legend
BLK– 120-277VAC Emergency Hot
WHT Emergency Neutral
BLU– Switched Output
VIO 0-10V Dimming (+)
GRY 0-10V Common (-)
GRN Ground
RED (Terminal) +24VDC
BLK (Terminal) DC Common
+24 VDC
}
RPP DS 24V ER
120 V -
277 V
}
Normal
EMERGENCY
0-10 VDC Ballast
or LED Driver
}
Emergency
RPP D/DS 24V ER
Legend
RED 120-277VAC Emer. Hot
WHT/RED Emer. Neutral
BLK Unswitched Norm. Hot
WHT Norm. Neutral
BLU Switched Output
VIO 0-10V Dim (+)
GRY 0-10V Com (-)
RED (Terminal) - +24VDC
BLK (Terminal) - DC Com
GRN Ground
- Optional Test Switch
(by others)
+24 VDC
}
Legend
RED – 120-277VAC Emergency Hot
WHT/RED – Emergency Neutral
BLK – Unswitched Norm. Hot*
WHT – Norm. Neutral*
BLU – Switched Output
VIO – 0-10V Dim (+)
GRY – 0-10V Com (-)
RED (Terminal) - +24VDC
BLK (Terminal) - DC Com
GRN – Ground
- Optional Test Switch
(by others)
* Emergency on EM devices
USING 24 VDC TERMINALS (24V models only)
Strip jacket to correct length, then
insert rmly into terminal hole.
Gently pull to conrm that terminal
has securely captured wirelead.
Strip length: 3/8”
Solid or tinned
leads only
16-20 AWG
Connecting Wire to 24V Terminals
1.
2.
Max screwdriver size: 2mm
Insert precision slotted
screwdriver into terminal slot.
Gently press screwdriver into
terminal, then gently pull wire
to remove.
Removing Wire from 24V Terminals
1.
2.