Operation Manual
DHW CONNECTION
General remark
• The circuit illustrations are basic principle diagrams only.
Essential recommendation for safety
• The hot water output may reach temperatures in excess of 60°C, which can cause
scalding! It is therefore necessary to install a thermostatic mixing valve after the
appliance.
Essential recommendations for the correct operation of the appliance
• Flush the system before connecting the domestic hot water circuit. Refer to the
installation instructions.
• Make sure to install a pressure reducing valve set at 4.5 bar if the mains supply
pressure is in excess of 6 bar.
• The installation must be fitted with an approved safety group, comprised of a 7 bar
safety valve, a check valve and a shut-off valve.
Typical installation
Description
1. Isolating valve
2. Pressure reducing valve
3. Check valve
4. DHW expansion vessel
5. Safety valve
6. Drain valve
7. Draw-off tap
8. Grounding
9. Thermostatic mixing valve
Cold water
Hot water
1 2 3
1
1
8
4
5
6
7
9
EN
23
EN
BNE : 664Y6000 •D
INSTALLATION