Technical data

TECHNICAL AND INSTALLATION
9
6. TECHNICAL DATA
Type SLE 130 SLE 160 SLE 210 SLE 240 SLE 300
Code 06604801 06604901 06605001 06605101 06605201
Unvented Kit Smart Pak1 (12ltr) SP2 (18ltr)
Total Capacity (ltrs) 130 161 203 242 293
Heating Fluid Capacity (ltrs) 55 62 77 78 93
Domestic Water Capacity (ltrs) 75 99 126 164 200
Primary press. drop (mbar) 17 22 37 45 51
Immersion heater connection 1½” BSP 1½” BSP 1½” BSP 1½” BSP 1½” BSP
Primary fluid connections 1” BSP 1” BSP 1” BSP 1” BSP 1” BSP
Domestic water connections ¾” BSP ¾” BSP ¾” BSP ¾” BSP ¾” BSP
Dimension: A (mm) 525 725 997 1244 1550
B (mm) 960 1160 1435 1680 1988
C (mm)* 1460 1660 1935 2180 2488
Weight empty (kg) 55 65 75 87 102
Weight full (kg) 185 226 278 329 395
Heating surface (m²) 1.03 1.26 1.54 1.94 2.29
Primary fluid flow (ltrs/hr) 2100 2600 3500 4200 5300
Absorbed Power (kW)** 23 31 39 53 66
Start-up time from 10 to 85°C(min) 22 22 20 20 20
* Dimension C is the approximate total height with mains kit fitted including expansion, please be aware
that this kit is adaptable should there be a restriction on the height. Please contact ACV UK Ltd technical
support for any assistance.
** The boiler outputs shown are the minimum to provide the domestic performance figures detailed. Should
a lower capacity boiler be used the performance will be reduced.