Specifications

EN • 19
ENGLISHFRANCAISNEDERLANDSESPAÑOLITALIANODEUTSCH
664Y3000.A
INSTALLATION
DOMESTIC HOT WATER CONNECTION
PRESTIGE SOLO + SMART TANK
- Rinse the installation before connecting the domestic
hot water circuit.
- Fill the tank before filling the heating circuit.
Before any work on the boiler, it is important to
disconnect the power supply.
It is important to carry out all the electrical
connection before changing the MCBA
parameters.
1. T h e 12 k Ω NTC sensor must be inserted into the
dywell and connected on terminals 3 and 4. (See
the picture below].
.
2. Connect the DHW pump to the dedicated
connector on the internal wiring (See the picture
below].
Optional accessories
Code Description
10800107
Collector 2 circuits DN32 :
Whith integrated wall brackets.
10800107
High temperature kit DN32:
Including: one circulation pump,
two isolating valves, check valve,
two thermometers.
10800142
Connection kit DN32 to the manifold:
Including: two fl exible 1"1/2 hoses and
1"1/4 reduction fi ttings.
5476G003
NTC sensor 12kΩ:
Senses the temperature in the external hot
water tank.
(Delivered with the kit 10800079)
factury
setting
typical
setting Description
Domestic hot water temperature
setting (to be adjusted between 60
and 80°C).
00 : DHW Mode “OFF”
01 : DHW Mode “ON”
12 : Tank with NTC sensor
13 : Tank with control thermostat
prestige
12
4
5
6
7
3
8
1. Cold water supply tap
2. Check valve
3. Safety group
4. Pressure reducing valve
5. Domestic hot water expansion vessel
6. Thermostatic mixer
7. Drawoff tap
8. By-pass
4 5 61 2 31 2 3 4 5 6 7 8 9 10 11 12 13