Examples of Use
Use of Binary Inputs
According to the state of four binary inputs of the Adash 3600-MAIN unit, up to 5 alarms can be set up,
for instance by assigning as follows:
Binary inputs status Alarm Limit Measured machine status
---------------------------------------------------------------------------------------------------------------
active BIN1 ALARM 1: 15 mm/s run-up
active BIN2 ALARM 2: 10 mm/s operating condition
active BIN3 ALARM 3: 15 mm/s coast down
active BIN4 ALARM 4: 12 mm/s increased power
No input active ALARM 0: 0 mm/s machine does not run
Note.
The 0 mm/s value corresponds to the state “ALARM OFF”.
If two binary inputs are activated simultaneously, the input with higher ordinal number has higher
priority (the BIN2 input precedes the BIN1 input etc.).