User's Manual Part 6

E-8 Appendix E Alarm Report Monitor (ARM2000)
Once connected to COM1, enter AT and press Enter. (You will see OK displayed
at this point and will not see any characters.) Then enter the following AT
commands.
•“AT& F
•“AT& A0
•“AT& B1
•“AT& K0
•“AT& M0
•“AT& N3
•“AT& W
After you enter these commands, your PCARM modem is ready for communication
with the internal modem of the remote ARM. Exit HyperTerminal. (You do not
need to save this session).
Remote Programming of a Remote-ARM Unit
To program the remote-ARM unit with the phone number to dial out to the PCARM
modem when an alarm condition occurs, make sure that the remote-ARM unit is
connected to an analog dial-up line and is powered up. Call from the PCARM,
taking the following steps. (Make sure the US Robotics 56K modem is installed in
the PCARM before programming.)
1
Click Start.
2
Click Programs.
3
Click Accessories.
4
Click HyperTerminal.
5
Double click HyperTerminal.exe.
6
Type connection name (TEST, for example) and click Enter.
7
Type the phone number of the line to which the remote-ARM unit is
connected.
8
Click OK.
9
Click Connect.
When a connection is established to the remote-ARM unit, the HyperTerminal
status bar will indicate the connection time.
10
After a connection is established, type P and then press the Enter key.
A prompt appears on the screen asking you to enter the phone number:
(ENTER PHONE NUMBER)