User's Manual Part 6

E-26 Appendix E Alarm Report Monitor (ARM2000)
When you are at the Device View screen, if an event occurs on another device, a
New Event dialog box will pop up over the Device View screen. The New Event
dialog box offers the following choices:
Go To
Select to display the device that is alarming.
System View
Select to display System View screen.
Continue
Select to continue with the device that is presently displayed.
Acknowledging Alarms
Alarms and Clears are both acknowledged in the same manner. Simply position the
cursor over the ACK button and click the left mouse button. If the system has been
configured as an open system and the Require Initials on Acknowledgment option
has been enabled, the Enter Initials dialog box will be displayed. Simply enter your
initials followed by the enter key and the alarm is acknowledged. In tracked and
secured systems, an operator with a security level of one or greater must be logged
on in order to acknowledge and alarm or clear. If no one has logged on prior to
clicking the acknowledge button, the Log on dialog box will be displayed. The ESC
key will cancel the log on procedure without acknowledging the alarm.
Disabling Channels
Individual alarm channels can be disabled to allow equipment maintenance without
causing false alarms. To disable an alarm channel, position the cursor over the
desired disabled channels LED and click the right mouse button. A dialog box will
then pop prompting to enter a reminder time. Enter the desired timer (in minutes)
for the disabled reminder to pop up. Enter 0 if no reminder is required.
Enabling Channels
To enable the channel, position the cursor over the desired channels LED and click
the right mouse button. This will cause a confirmation dialog box to be displayed.
To enable the channel, click the Enable button or press the E key. To cancel, click
the Cancel button or press the ESC or C key.
Alarm View Dialog Box
The Alarm View dialog box has been provided as a quick way of viewing the last
two events that occurred on a given channel. To display the Alarm View dialog
box, position the cursor over the desired channels LED and click the left mouse
button. This is a non modal dialog box, clicking another channel or anything else
on the screen will close the dialog box and perform the selected function. If the
selected channel has no alarms an error box will be displayed.