User Manual

ADCP-75-158 Preliminary Issue A June 2003 Section 3: Host Unit Installation
Page 3-4
© 2003, ADC Telecommunications, Inc.
3 WDM MOUNTING PROCEDURE (OPTIONAL ACCESSORY)
A bi-directional wavelength division multiplexer (WDM) system is available as an accessory
item for the Digivance system. If the application does not require the use of a WDM system,
skip this section and proceed to Section 4.
At the HU, the WDM system consists of a WDM host module and a WDM host module
mounting shelf. Each host module can support two HU’s and each host module mounting shelf
can hold two host modules. A fully loaded host module mounting shelf can therefore support
four HU’s.
When multiple HU’s require connection to a WDM system, the host module mounting shelf and
the HU’s should be mounted in the equipment rack as shown in Figure 3-2. This configuration
allows the pigtail leads from the two host modules to be connected directly to the optical ports
on any one of the four HU’s.
Figure 3-2. Typical WDM and HU Configuration
The WDM host module mounting shelf may be mounted in either a 19-inch or 23-inch EIA or
WECO equipment rack. Four #12-24 screws are provided for securing the mounting shelf to the
rack. Use the following procedure to install the host module mounting shelf in the equipment
rack and to mount the host modules in the host module mounting shelf:
1. The host module mounting shelf is shipped with the mounting brackets installed for 19-
inch EIA rack installations. If installing the mounting shelf in a 19-inch EIA rack, proceed
to step 5. If installing the mounting shelf in a 19-inch WECO rack, a 23-inch EIA rack, or
a 23-inch WECO rack, proceed to step 2.
WDM MOUNTING
SHELF
(WITHOUT MODULES)
18652-A
POWERWORX
FUSE PANEL
HOST UNITS