6.3.7. Setting the power up default status
This command enables to set the power up default status individually for each power outlet. Settings can
be "always On", "Always Off" or "Last memorized Status" before power failure.
Command to be sent to the ePowerSwitch 8XS:
DPxy=z[CR]
Reply from the ePowerSwitch 8XS:
DPxy=z[CR]
Explanations:
Parameter Value Function/Remark
x address of the ePowerSwitch 1 to 16
specifies the number of the ePowerSwitch 8XS
y number of the Power Outlet 1 to 8 specifies the number of the power Outlet
z default status after Power up
ON set power up default status of the power outlet to ON
OFF set power up default status of the power outlet to OFF
LAST set power up default status of the power outlet to last
memorized status
Examples:
DP37=LAST Set Power Up Default Status of the Power Outlet #7 of ePowerSwitch #3 to last
memorized status
DP165=OFF Set Power Up Default Status of the Power Outlet #5 of ePowerSwitch #16 to OFF
The ePowerSwitch 8XS accepts lower case and upper case commands.
The ePowerSwitch 8XS sends its reply only after having received a valid command terminated by
the character [CR].
6.3.8. Reading out the power up default status
This command enables to read out the power up default status individually for each power outlet.
Command to be sent to the ePowerSwitch 8XS:
DPxy[CR]
Reply from the ePowerSwitch 8XS:
DPxy=z[CR]
Explanations:
Parameter Value Function/Remark
x address of the ePowerSwitch 1 to 16
specifies the address of the ePowerSwitch 8XS
y number of the Power Outlet 1 to 8 specifies the number of the power outlet
z default status after Power up
ON power up default status of the power outlet is ON
OFF power up default status of the power outlet is OFF
LAST power up default status of the power outlet is last memorized
status
The ePowerSwitch 8XS accepts lower case and upper case commands.
The ePowerSwitch 8XS sends its reply only after having received a valid command terminated by
the character [CR].