Service manual
Table Of Contents
- Installation, Operation & Service Manual
- UHA-Series
- Tubular Unit and Utility Heaters
- (Low Profile Range)
- Manuel d’installation, d’operation, et de service
- UHA-Series
- Aérothermes Utilitaires à échangeur tubulaire
- (Gamme compacte)
- TABLE OF CONTENTS
- SECTION 1: Heater Safety
- SECTION 2: Installer Responsibility
- SECTION 3: Critical Considerations
- SECTION 4: Clearances to Combustibles
- SECTION 5: National Standards and Applicable Codes
- SECTION 6: Heater installation
- SECTION 7: Venting
- 7.2.1 United States Requirements
- 7.2.2 Canadian Requirements
- 7.3.1 Standard Vented Heaters (Models UHA[X] 30 - 125)
- 7.3.2 Separated Combustion Heaters (Models UHA[X]S 30 - 125)
- 7.7.1 Maximum Vent Lengths Table
- 1. Seal any unused openings in the venting system.
- 2. Inspect the venting system for proper size and horizontal pitch, as required by the NFPA 54/ ANSI Z223.1 - latest revision, National Fuel Gas Code (US) or Standard CSA B149.1 Natural Gas and Propane Installation Code (Canada) and these instruction...
- 3. Close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building. Turn on clothes dryers and any exhaust fans, such as range hoods and bathr...
- 4. Follow the lighting instructions. Place the appliance being inspected in operation. Adjust thermostat so that the appliance will operate continuously.
- 5. For any appliance having a draft hood, test for draft hood appliance spillage at the draft hood relief opening after five minutes of main burner operation. Use the flame of a match or candle.
- 6. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliances to their previous conditions...
- 7. If improper venting is observed during any of the above tests, the venting system must be corrected by a contractor qualified in the installation and service of gas-fired equipment or your local gas supplier. If the venting must be resized, use ap...
- Figure 9: Vent and Roof Detail
- Figure 10: Standard Vented Heater - Vertical and Horizontal Vent Termination
- Figure 11: Standard Vented Heater - Common Vertical Vent Termination
- Figure 12: Separated Combustion Heater - Vertical and Horizontal Vent Termination
- Figure 13: Concentric Vent Box
- Figure 14: Concentric Vertical and Horizontal Vent Termination - Separated Combustion Heater
- SECTION 8: Air Supply
- SECTION 9: Gas Piping
- SECTION 10: Wiring
- SECTION 11: Operation and Maintenance
- 11.1.1 Louvers
- 11.1.2 Electrical Checks
- 11.1.3 Gas Supply
- 11.1.4 Mechanical Checks
- 11.2.1 Before Operating the Heater
- Figure 16: Automatic Burner Control Sequence
- Figure 17: Gas Valve for Models UHA[X][S] 30 - 45
- Figure 18: Gas Valve for Models UHA[X][S] 60 - 125
- 11.2.2 Start-Up the Gas Valve (All Gases)
- 11.2.2.1 Check Burner Gas Pressure
- 1. Remove the plug in the outlet (burner) pressure test point and connect a pressure tap and a manometer.
- 2. With the burner firing, measure the pressure on the manometer. To adjust the burner pressure, remove the regulator cover from the valve and turn the regulator adjustment screw to set the required burner pressure as stated in the Technical Data Tab...
- 11.2.2.2 Check Gas Rate
- 1. After burner pressure adjustment, allow the heater to operate for at least 15 minutes and then re-check settings. Adjust pressure setting if necessary.
- 2. Check gas flow rate at gas meter.
- 3. Turn off heater and electrical supply.
- 4. Remove the manometer and refit all covers to the valve and tighten the screw of the outlet pressure tap.
- 11.2.2.1 Check Burner Gas Pressure
- 11.2.2 Start-Up the Gas Valve (All Gases)
- SECTION 12: User Instructions
- SECTION 13: Servicing
- 1. Open the hinged door and remove from the hinges. Set door aside. See Page 46, Section 15.2.
- 2. Remove burner side panel. Electrode and flame probe should remain attached. See Page 47, Section 15.3.
- 3. Remove burner assembly from cabinet via four screws, two on top and two on bottom. Clean any deposits from the main burner which may have formed in the injectors or venturi of the burner.
- 4. Check condition of ignition electrode and flame probe. Clean off any deposits which may have formed, check condition of ceramic insulators. Replace as required. See Page 47, Section 15.3.
- SECTION 14: Troubleshooting
- SECTION 15: Replacement Parts
- See warnings and important information on Page 37, Section 13 before removing or replacing parts.
- Burner Components All serviceable burner parts are accessed by the hinged door on the side of the heater.
- 15.1 Gas Valve
- 15.2 Burner Injectors
- 15.3 Ignition Electrode and Flame Probe
- 15.4 Heat Exchanger
- 15.5 Louver and Louver Springs
- 15.6 Flue Blower Vertical Installation
- 15.7 Pressure Switch
- Pull off 3 way connector. Spring open plastic clips of mounting cradle. Replace with correct type of pressure switch for model. The pressure switches are color coded for each pressure setting. Carry out a start-up after working on or changing a press...
- The control mounts to the heat exchanger plate. Pull out ignition cable and wiring from board, noting their positions. Release the four mounting standoffs. Refit in reverse. Ensure correct location of ignition cable and all other wiring.
- The axial fan unit for the heater is supplied completely assembled and balanced.
- SECTION 16: Specifications
- SECTION 17: ADDISON® UHA-Series Warranty

UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
16 of 55
Vents and air intakes must be adequately
supported so that the heater does not bear the
weight of the pipes.
For vent termination See Page 18, Figure 9 through
Page 21, Figure 14.
7.3.1 Standard Vented Heaters
(Models UHA[X] 30 - 125)
The vent must be fitted with a low resistance
t
erminal. See Page 18, Figure 9 through Page 19,
Figure 11. Standard vented heaters do not allow
outdoor air intake for combustion air.
7.3.2 Separated Combustion Heaters
(Models UHA[X]S 30 - 125)
The heaters are designed to be installed as
separ
ated combustion heaters. The vent and air
intake are run as separate pipes to the wall or roof
terminals. See Page 20, Figure 12. As an option, the
vent and air intake are run as separate pipes to a
concentr
ic vent box and a concentric vent/air intake
pipe penetrates the wall or roof. See Page 20,
Figure 13 and Page 21, Figure 14.
For seperated combustion installation, the vent and
air int
ake must be fitted with an individual and
correctly sized sealed system and the vent and air
intake must terminate at approved wall and roof
terminals.
Seperated combustion units may not be common
v
ented.
7.4 Unvented Operation
WARNING
Carbon Monoxide Hazard
Heaters may be installed
vented or unvented.
Vented heaters must be
vented outdoors.
Unvented heaters must be
installed according to the
installation manual.
Failure to follow these
instructions can result in
death or injury.
The heater must be vented when installed in
residential buildings.
For unvented operation in commercial installations,
suf
ficient ventilation must be provided in the amount
of 4 cfm per 1000 Btu/h firing rate (United States);
3 cfm per 1000 Btu/h firing rate (Canada).
7.5 Horizontal Venting
Horizontally vented heaters must be individually
v
ented, no common venting.
Vent pipe must be sloped ¼" (.6 cm) for every 1'
(.3 m) away from heater. For vent lengths greater
than 1
0' (3.0 m), condensation will form. Insulation is
recommended and condensation drains may be
desired. For vents pitched up towards the vent
terminal, place the condensation drain within 10'
(3.0 m) of the heater.
In noncombustible walls only, vent terminal
(P/N 02537801-1P) may be used.
For 4'' (10 cm) vents in either combustible or
noncomb
ustible walls, use vent terminal (P/N
90502100) or equivalent insulated vent terminal.
Follow the manufacturer's instructions for proper
installation.
Instead of an insulated vent terminal, a listed thimble
with 2" (5 cm) air g
ap may be used with a 4" (10 cm)
vent cap (P/N 90502102).
In the State of Massachusetts, the following
r
egulations apply to horizontally-vented heaters
certified for installation in structures used in whole or
in part for residential purposes (UHA 30-75 only)
and where the side wall exhaust vent termination is
less than seven (7) feet above finished grade in the
area of the venting, including but not limited to decks
and porches:
Installation of Carbon Monoxide Detectors: At the
time of inst
allation of the side wall horizontal vented
gas fueled equipment, the installing plumber or
gasfitter shall observe that a hard wired carbon
monoxide detector with an alarm and battery back-
up is installed on the floor level where the gas
equipment is to be installed. In addition, the
installing plumber or gasfitter shall observe that a
battery operated or hard wired carbon monoxide
detector with an alarm is installed on each additional
level of the dwelling, building or structure served by
the side wall horizontal vented gas fueled
equipment. It shall be the responsibility of the
property owner to secure the services of qualified
licensed professionals for the installation of hard
wired carbon monoxide detectors
• In the event that the side wall horizontally vented
g
as fueled equipment is installed in a crawl
space or an attic, the hard wired carbon
monoxide detector with alarm and battery back-
up may be installed on the next adjacent floor
level.
• In the event that the requirements of this
subdivision can not be met at the time of
completion of inst
allation, the owner shall have a










