UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
18 of 55
Do not operate a summer exhaust fan. Close
fireplace dampers.
4. Follow the lighting instructions. Place the
appliance being inspect
ed in operation. Adjust
thermostat so that the appliance will operate
continuously.
5. For any appliance having a draft hood, test for
dr
aft hood appliance spillage at the draft hood
relief opening after five minutes of main burner
operation. Use the flame of a match or candle.
6. After it has been determined that each
appliance connect
ed to the venting system
properly vents when tested as outlined above,
return doors, windows, exhaust fans, fireplace
dampers and any other gas-burning appliances
to their previous conditions of use.
7. If improper venting is observed during any of
the abo
ve tests, the venting system must be
corrected by a contractor qualified in the
installation and service of gas-fired equipment
or your local gas supplier. If the venting must
be resized, use appropriate tables in (US)
Appendix G of NFPA 54/ANSI Z223.1 - latest
revision, National Fuel Gas Code (US) or
Standard CSA B149.1 Natural Gas and
Propane Installation Code (Canada) to
determine minimum size. All vent corrections
must be in accordance with the appropriate
local codes and the NFPA 54/ANSI Z223.1 -
latest revision, National Fuel Gas Code (US) or
Standard CSA B149.1 Natural Gas and
Propane Installation Code (Canada).
Figure 9: Vent and Roof Detail
Roof
Vent
Terminal
Listed Thimble
Flashing
or Rain Collar
Vent
2" (5 cm) Air Gap
to Combustible
Material
Figure 10: Standard Vented Heater - Vertical and Horizontal Vent Termination
Model Vent Diameter Part Number
UHA[X] 30 - 125 4" (10 cm) 90502102