Service manual

Table Of Contents
UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
46 of 55
15.2
Remove four screws to remove
manifold.
Ensure gas tight fitting of injectors.
Ensure correct alignment with
burners.
Ensure all pipe joints are gas tight.
Burner Injectors
MODEL UHA[X][S] 30 UHA[X][S] 45 UHA[X][S] 60 UHA[X][S] 75 UHA[X][S] 100 UHA[X][S] 125
Orifice Quantity 2 3 4 5 6 7
Natural Gas (G20)
Orifice Marking 49 49 49 49 46 46
P/N 91930049 91930049 91930049 91930049 91930046
91930046
Propane (G31)
Orifice Marking 56 56 56 1.15 mm 1.25 mm 1.25 mm
P/N 91930056 91930056 91930056 91930115 91930125 91930125