Service manual

Table Of Contents
SECTION 15: REPLACEMENT PARTS
51 of 55
15.9.1 Fan Removal and Replacement
WARNING
Severe Injury Hazard
Turn off gas and electrical supply before
service.
Fan can start automatically at any time.
Failure to follow these instructions can
result in severe injury or product damage.
Description Part Number Quantity
Axial Fan UHA[X][S] 30 12011910 1
Axial Fan UHA[X][S] 45 12011911 1
Axial Fan UHA[X][S] 60 12011920 1
Axial Fan UHA[X][S] 75 12011921 1
Axial Fan UHA[X][S] 100 and UHA[X][S] 125 12011922 1
15.9.2 To Replace the Fan Assembly
To replace the fan assembly, reverse the procedure
sho
wn above.
Check that the fan blades are free to rotate
bef
ore turning on the power to the fan.
Strictly comply with the color code of the fan
wir
es to ensure correct operation. See Page 28,
Section 10.5 wiring diagram.
Use only gen
uine replacement parts sold and
supplied by Addison.
15.10 Limit Switches
15.10.1 Removal and Replacement
1. Remove the electrical connections to the
switch.
2. Unscrew the two screws securing the
switch.
3. Fit a new switch with two screws.
4. Reconnect the electrical connections and test
oper