Accenta/Optima Engineer’s Manual G Zones en" 0 5 1 6 2 7 3 8 4 9 Chime Omit Reset Prog Set Power Attack Tamper Day ACCENTA PA Accenta /! mini Accenta /! mini 8SP399A - Accenta mini panel with remote LCD keypad and communicator outputs.
Table of Contents Accenta/Optima Engineer’s Manual Contents Introduction............................................................................................................ 1 Features .................................................................................................................. 1 Installation Design ................................................................................................ 2 Fixing the Control Panel .........................................................
Accenta/Optima Engineer’s Manual Table of Contents Menu Options ....................................................................................................... 18 0 = Walk Test ....................................................................................................................... 18 1 = Alarm Test ..................................................................................................................... 19 2 = Test Outputs .................................................
Accenta/Optima Engineer’s Manual Features Introduction This manual provides information on Installation design, panel fixing, wiring, power up and programming of the intruder panels. Features 2 4 8 zones programmable for Security, 2 zones for Fire. PA input. Tamper input. Outputs for External Siren (Bell) and Strobe. 4 Access level Codes, User 1, User 2, Engineer and Duress, all programmable. 3 fully selectable part set programs. Chime on any security zone.
Accenta/Optima Engineer’s Manual Installation Installation Design The purchase of this alarm system represents a major step forward in the protection of the property and its occupants. It is important to plan the installation before proceeding following the procedures and advice contained in this manual. Plan the position of each part of the alarm system and the cable runs. Detectors should be sited with particular regard to the degree of coverage required.
Accenta/Optima Engineer’s Manual Control Panel Fixing the Control Panel CAUTION: When positioning the control panel make sure that it is located in a dry place away from damp areas. NOTE: The Accenta mini enclosure is illustrated here, however the procedures for the other panels is similar. S R Q 1. Remove the front cover(s) from the base assembly. 2. Disconnect the transformer wires from the board, these are marked AC.
Accenta/Optima Engineer’s Manual PCB PCB There are four fuses mounted on the circuit board, all are 20mm anti-surge. F1 1.6A - to protect the positive (+Ve) line of 12V battery F2 1A - to protect the Speaker 13V supply F3 1A - to protect the Siren (Bell) & Strobe supply F4 1A - to protect the RKP 13V supply As supplied, wire links are fitted across the PA and Tamper terminals to represent a closed circuit.
Accenta/Optima Engineer’s Manual Connecting Keypads !"#$# % $ & &' # & ( ) * Figure 5. Connecting LED keypads to panel TB1 TB2 TB1 TB2 +13V 0V sound tamp tamp comms +13V 0V sound tamp tamp comms Keypad PCB Keypad PCB Panel Board Figure 6.
Accenta/Optima Engineer’s Manual Remote Keypad Fitting the Remote Keypad 1 Separate the RKP baseplate from the main assembly by slackening the retaining screw. 2 Cut away the required thin wall sections around the edges of the baseplate for cable entry. 3 The baseplate mounting holes are 60 mm centres (LED keypad) or 75 mm (LCD keypad) which allow it to be fixed to a single gang electrical metal box. As an alternative, the baseplate may be fitted directly to the wall using screws and wall plugs.
Accenta/Optima Engineer’s Manual Zones Fire Zone Zones 7 and 8 may be programmed as fire zones. This will automatically exclude the availability of the zone from programs and normal security applications. Panel Board J2 1 2 3 4 5 7 6 8 PA + TAMP +13V 0V - Fire detector Note: Fire detector with relay base for output to intruder system. Figure 8. Fire Zones The fire zone detects fires all the time and will operate whether the system is Set or Unset.
Accenta/Optima Engineer’s Manual PA Circuit PA Circuit It is recommended that no more than 10 normally closed type personal attack button may be wired in series and then connected to the PA circuit. Operational in Unset and Set, the PA circuit will cause a full alarm condition when activated. PA is indicated on the control panel or RKP. PA buttons may be fitted near the front door or in a bedroom. Panel Board J2 1 3 2 4 5 7 6 8 PA + TAMP - +13V 0V Panic Button Panic Button Figure 9.
Accenta/Optima Engineer’s Manual Bell Box External Siren (Bell Box) Output The external siren (bell box) is usually installed in a high position from where the siren could be seen and heard. Terminal TADB are for connection to the external siren. These terminals provide a power/hold-off supply, sounder trigger and tamper circuit to protect the external siren housing.
Accenta/Optima Engineer’s Manual Bell Box (cont’d) Panel J6 + - Board T Black Blue - D A + - B Board T + - D A Yellow Red + 1A Black - Green + Red B F3 Blue D Red A Green T White Yellow White - + BELL/STROBE Board B Reson8 Reson8 Figure 12. Twin External Bell-box Wiring 13V Supply Output The 13V output is to power detectors which require a voltage supply (PIR detectors etc).
Accenta/Optima Engineer’s Manual Remote Signalling Remote Signalling Input and Outputs NOTE: These outputs are not applicable to the Optima compact panel. These terminals have been provided for connection to remote signalling equipment such as a digital communicator, or speech dialler. 13V 0V: These terminals provide a 13V supply for the communicator up to a total load of 200mA. OUTPUTS (J3): These outputs are programmed as active low output.
Accenta/Optima Engineer’s Manual Remote Signalling (cont’d) Important Notes 1. Each output has been configured as active low. 2. Where the communicator is powered from an external source, not the panel and the outputs are being used without relays, the panel and external power supply will require a common negative supply rail. 3.
Accenta/Optima Engineer’s Manual Factory Conditions Factory Set Condition User code1 User code2 Duress Code Engineer Code External siren Bell Duration External siren Bell Delay Rearm Count Program 1 Zone 1 Zone 2 Zone 3 - 8 Exit time Entry time Exit mode Timed Timed inhibit Immediate 30 seconds 30 seconds Timed Program 2 Zone 1 Zone 2 Zone 3 - 8 Exit time Entry time Exit mode Timed Timed inhibit Immediate 30 seconds 30 seconds Disabled Program 3 Zone 1 Zone 2 Zone 3 - 8 Exit time Entry time Exit mode
Accenta/Optima Engineer’s Manual Mains Connection Mains Connection The mains power should be connected using 3-core cable of not less than 1 mm sq. from a fused spur to the mains connector inside the control panel. The 2 A fused spur must be located close to the control panel. NOTE: The mains supply must be connected by a technically competent person and according to current IEE regulations.
Accenta/Optima Engineer’s Manual First Power Up First Power Up NOTE: For Optima compact, fit the top cover on to the base and connect the speaker wires. 1 2 Check that the factory fitted links are connected to terminals PA, TAMP and T-A. Fit the battery wires to the battery terminals (BATT). "# ! $ % && ' Figure 15.
Accenta/Optima Engineer’s Manual Engineer Program Mode Engineer Program Mode The panel may be programmed to suit a wide variety of installations. Once the Engineer program mode has been accessed, each configuration may be changed in any order. Before entering Engineer program mode the system should be in the Day mode, with the Day and Power indicators lit.
Accenta/Optima Engineer’s Manual Defaulting Entering/Exiting Engineer Program Mode NOTE: The factory configured engineer’s access code is 9999. If however this code is changed then enter the appropriate code. Press PROG LCD Indications LED Indications Attack/PA Enter Your Code 0>Walk test To exit Engineer program mode press RESET Defaulting Panel to Factory Settings CAUTION: All configurations of the panel are reset to factory default conditions. To default to factory settings: 1.
Accenta/Optima Engineer’s Manual Menu Options Menu Options The full menu structure for the panel can only be accessed while in Engineer program mode. The structure is shown in the following table: MENU OPTIONS 0 = Walk Test 7 = Timers 1 = Alarm Test 8 = Codes 2 = Test Outputs C = View Event Log 3 = System Flags O = Omit Allow & Double Knock 4 = Time and Date P = Set up Programs 6 = Zone Names Table 2. Menu Options Enter Engineer program mode. Press [PROG] [9] [9] [9] [9].
Accenta/Optima Engineer’s Manual Alarm Test 1 = Alarm Test This function tests the alarm function of the Bell, Strobe or Sounder. Pressing the appropriate button [1-3] toggles the function ON or OFF. Using the [up arrow] also selects the appropriate alarm function. Pressing the [0] button turns all alarm outputs to OFF. Pressing the [SET] button toggles the selected alarm output. Pressing the [RESET] button turns off all outputs and leaves the function.
Accenta/Optima Engineer’s Manual Test Outputs 2 = Test Outputs NOTE: These tests are not applicable to Optima compact panels. This function tests all the outputs on the system. The outputs are:1 = Fire, 2 = PA, 3 = Intruder, 4 = Set, 5 = Abort. Pressing the [0] button turns all outputs to OFF. Pressing the [SET] button toggles the selected alarm output. Pressing the appropriate button [1-5] toggles the function ON or OFF. Pressing the [RESET] button turns off all outputs and leaves the function.
Accenta/Optima Engineer’s Manual Test Outputs 3 = Set Up System Flags The System Flags are divided into Flags 1, 2 or 3. LCD Keypad: • Press [up arrow] to display menu Set Up System Flags. • [up arrow] Set Up System Flags Press [3] or [SET] to display the next screen. [3] or [SET] System Flags 1, 2 or 3? LED Keypad: • Press [3]. LED’s 1, 2 and 3 are ON. [3] 1 2 4 3 5 6 7 8 Flag 1 NOTE: Pressing the [9] button sets all flags ON. Pressing the [0] button sets all flags OFF.
Accenta/Optima Engineer’s Manual System Flags Flag 1 - Options There are eight options under Flag1 which are described below: 1 = Silent PA When this flag is set to ON, operating PA will cause a silent PA alarm. Pressing the [1] button toggles the flag ON or OFF. 2 = RKP PA When this flag is set to ON, the keypad PA buttons are enabled. Pressing the [2] button toggles the flag ON or OFF.
Accenta/Optima Engineer’s Manual System Flags (cont’d) Flag 2 NOTE: Pressing the [9] button sets all flags ON. Pressing the [0] button sets all flags OFF. Pressing the [RESET] button leaves the function. [2] LCD Keypad: Single Key Set • Press [2] to select System Flag 2. Press [1-2] Yes or [SET] to toggle flag on or off. • Press [up arrow] or [2] to go to second option [up arrow] or [2] of Flag 2.
Accenta/Optima Engineer’s Manual Time & Date 4 = Set Up Time and Date LCD Keypad: This option allows the Time or Date to be modified. Pushing button [4] selects the option and the first screen appears as typically below: The Time can be modified in hours, minutes and seconds in the format HH:MM:SS. The number keys on the keypad 0-9 are used for this function. As each digit is modified the cursor moves to the next one.
Accenta/Optima Engineer’s Manual Timers 7 = Set Up Timers This option allows the Bell Time, Bell Delay and Rearm Count to be changed. NOTE: The [OMIT] key takes you back to the first digit. 71 = Set Up Bell Time This is the duration that the external bell output is active. The range is 01-99 minutes. The default is 15 minutes. [up arrow] LCD keypad: To change the Bell Time from 15 to 20 minutes: 7>Set Up Timers • Press [up arrow] for menu Set Up Timers.
Accenta/Optima Engineer’s Manual Timers (cont’d) 72 = Set Up Bell Delay This delays the activation of the Bell for the required time. The range is 00-99 minutes. The default is 00 minutes. NOTE: The Bell Delay delays the bell for one rearm period only. After rearm all alarms are immediate. LCD keypad: To change the Bell Delay time from 00 to 12 minutes: • Press [up arrow] for menu Set Up Timers. • [up arrow] 7>Set Up Timers [7] or [SET] Press [7]or [SET]. Option 1 Set up Bell Time appears.
Accenta/Optima Engineer’s Manual Timers (cont’d) 73 = Set Up Rearm Count After an alarm the panel will automatically rearm itself when the external siren (Bell) timer has expired. Any zones which still remain open at that time will be automatically omitted . The default is 3 rearms. 0 = no rearms 1-8 = number of rearms [up arrow] 9 = always rearm 7>Set Up Timers LCD keypad: To change the Rearm Count: • Press [up arrow] for menu Set Up Timers. • Press [7]or [SET]. Option 1 Set up Bell Time appears.
Accenta/Optima Engineer’s Manual Codes (cont’d) 8 = Set Up Codes There are four codes used in the system, all are 4 digit and can be set to any number from 0000 to 9999. The access codes ensure that only authorised users can operate the system. User 1 and 2 codes The user 1 and user 2 codes have the same operation for testing, Setting and Unsetting, but user 1 code which is usually considered to be the Manager’s code has the authority to add, change or delete the user 2 code and duress code.
Accenta/Optima Engineer’s Manual Codes (cont’d) LED Keypad: To change User code: • [8] Press [8] to edit user code. LED’s 1-4 are on. 1 • 2 1 Enter the new 4-digit code. • • Upon the last keypress the new code is saved. To leave menu press [RESET] twice. 4 5 6 7 8 7 8 7 8 [1] or [SET] Press [1] or [SET] to edit user code 1. LED’s 1-4 are on.
Accenta/Optima Engineer’s Manual Event Log C = View Event Log 1 = LCD Keypad: The event log gives a display of all the events that have taken place. The events are arranged by date and time. Up to 250 events can be stored in the memory. When the log reaches 250 events and another event takes place, the first event drops out. The system is known as FILO (First In Last Out). To view the event log: C>View • Press the [up arrow] until you come to the first screen. Event Log • Press [CHIME] or [SET] .
Accenta/Optima Engineer’s Manual Event Log (cont’d) 2 = LED Keypad: The LED keypad is limited to show the last eight set periods with the eighth being the oldest. Zone, PA and Tamper indicators will be lit to show zone in alarm . Flashing LED indicates the first zone in alarm. Day indicates the status of the panel at the time of the alarm. • • • • Press [CHIME] to enter into Event Log menu. LED’s 1 and 2 are on. Press [2] for LED keypad. The first zone to activate is indicated by a flashing LED.
Accenta/Optima Engineer’s Manual Omit Allow & Double Knock LED Keypad: Press [CHIME] to toggle double knock status on or off. Press [9] to turn all double knock zones on. Press [0] to turn all double knock zones off. • Press [OMIT] to enter into menu. LED’s 1 and 2 are on. [OMIT] 1 • 4 3 Press [1] to select Double Knock. 5 6 7 8 6 7 8 [1] 1 • 2 2 4 3 5 Press zone number [1-8] to choose a particular zone.
Accenta/Optima Engineer’s Manual Omit Allow & Double Knock LED Keypad: Press [CHIME] to toggle omit allow status on or off. Press [9] to turn all omit allow zones on. Press [0] to turn all omit allow zones off. [OMIT] • Press [OMIT] to enter into menu. LED 2 is on. • Press [2] to select Omit Allow. 1 • 3 4 5 6 7 8 6 7 8 7 8 7 8 [2] 1 • • 2 Press zone number [1-8] to choose a particular zone. Press the [zone number] or [CHIME] to toggle the omit allow status on or off.
Accenta/Optima Engineer’s Manual Programs P = Set Up Programs The panel uses three setting routines known as programs. Each program may have a different Exit Mode. These are 0 = Disabled, 1 = Timed, 2 = Final Door or 3 = Silent Timed. Zones can also be assigned different functions in different programs. Refer to the following diagram for the programming structure.
Accenta/Optima Engineer’s Manual Programs (cont’d) LCD Keypad: NOTE: Pressing the number toggles the zone ON or OFF While in Engineer program mode, to set up zones as used, • Press [PROG] to give a choice of programs or press [up arrow] until P>Set Up Programs is displayed then press [SET]. • [PROG] P>Select Program 1 2 or 3 Select program 1, 2 or 3. [Number] • The first screen to appear is Program Edit Used Zones. • Press [1] or [SET]. The first zone can now be set as used or unused.
Accenta/Optima Engineer’s Manual Programs (cont’d) 2 = Timed Zones A zone programmed as Timed would be used to protect the main entry/exit door of the entry route. LCD Keypad: NOTE: Pressing the number toggles the zone ON or OFF While in Engineer program mode, to set up zones as timed, • Press [PROG] to give a choice of programs or press [up arrow] until P>Set Up Programs is displayed then press [SET]. • Select program 1, 2 or 3.
Accenta/Optima Engineer’s Manual Programs (cont’d) 3 = Inhibit Zones This is a zone which, on setting the panel, allows access to the entry/exit zone. However, if the panel is set and a time inhibited zone is triggered before an entry/exit timed zone then an alarm will be generated immediately.
Accenta/Optima Engineer’s Manual Programs (cont’d) Immediate (Intruder) Zone This is a zone which will, when enabled as used and then activated, go into alarm when the panel is set. To assign a zone as immediate, remove the timed or timed inhibit function and make sure that it is enabled in the Used Zones section. 4 = Entry Time This is the time allowed to enter the premises via the entry route and unset the system. The programmable range is 00-99 seconds. The actual time is multiplied by 10.
Accenta/Optima Engineer’s Manual Programs (cont’d) 5 = Exit Time This is the time allowed to leave the premises via the exit route before the system sets. The programmable range is 00-99 seconds. The actual time is multiplied by 10. If the Exit Time is interrupted within the last 10 seconds, then the Exit Time will restart at 10 seconds after the interruption has cleared. 00 = 5 seconds [PROG] 01 = 10 seconds P>Select Program 03 = 30 seconds 1 2 or 3 99 = 990 seconds (16.
Accenta/Optima Engineer’s Manual Programs (cont’d) 6 = Exit Mode This program determines the way the panel functions during the exit time. There are four settings: 0 = Disabled A disabled program is not available for use and cannot be selected at setting time. Program 1 cannot be disabled. 1 = Timed A timed program will become Set as the Exit timer expires. 2 = Final Door A final door program will be set five seconds after a timed zone is closed if the rest of the zones are clear to set.
Accenta/Optima Engineer’s Manual Programs (cont’d) LED Keypad: While in Engineer program mode, to set the Exit Mode , • Press [PROG] to give a choice of programs.LED’s 1, 2 and 3 are flashing. [PROG] 1 • • Select program 1, 2 or 3. If program 2 is selected, LED 2 is ON. 2 3 5 6 7 8 5 6 7 8 5 6 7 8 6 7 8 6 7 8 [2] 1 2 3 Press [6] to enter into Exit Mode edit. The Exit Mode can now be changed. 4 [6] 1 Enter [0, 1, 2 or 3] for required Exit Mode.
Accenta/Optima Engineer’s Manual Operating System Operating the System This section gives a brief description of how to set and unset the system as well as how to reset after an alarm. For further information please refer to the Gen 4 Series User Guide. Setting the System Tuesday LCD Keypad: • The system shows the day mode display. The system is unset. The Power and Day LED’s are ON. • Enter your 4-digit code (0123 default) and check that the system is clear (no zone indicators on).
Accenta/Optima Engineer’s Manual Operating System (cont’d) Unsetting the System LCD Keypad: • Enter the premises by the agreed entry route. Thesystem produces an entry tone. The Power LED is ON and the Day LED is OFF indicating that the system is set. • Enter your 4-digit code (0123 default). • The system unsets with a double beep. The Day LED comes ON indicating that the system is unset. • After 30 seconds the Day Mode display appears. LED Keypad: • Enter the premises by the agreed entry route.
Accenta/Optima Engineer’s Manual Operating System (cont’d) Engineer Reset - LCD Keypad: After a tamper an engineer reset is required if the Engineer Reset flag is enabled. • Enter your user code [0123] default. If the system has to be set by an engineer the message Engineer Restore Required is displayed. [user code] Engineer Restore Required Contact Engineer • [engineer code] Enter your 4-digit engineer code (9999 default). Restored by Engineer • The system resets and goes into day mode.
Accenta/Optima Engineer’s Manual Faults Faults Fault conditions are often the result of minor installation errors. Whenever working close to the mains supply or connector, you should exercise extreme caution. Always isolate the mains supply before removing the control panel covers. Codes As supplied the default user code is 0123 and the engineer code is 9999. Both codes can revert back to default settings. See Defaulting Panel to Factory Settings and Defaulting User Code 1 and Engineer Code.
Accenta/Optima Engineer’s Manual Specs Specifications 8 zones +ve loop, programmable function in each program Tamper -ve loop, internal sounders in Day - Full alarm in Set PA +ve loop, always active External siren (Bell Box) output 12V, adjustable timer (1 - 99 mins) or continuous Strobe output 12V latching External speaker 16 ohm (2 maximum) 260mA each Exit /Entry Timers seconds Programmable (05 - 990 seconds) Set output 0V in Day (sinking 400mA) 12V in Set (sourcing 10mA) Current consump
Accenta/Optima Engineer’s Manual Event Log Appendix 1 - Event Log Messages KEYPAD TEXT DESCRIPTION Zone events INTRUDER Intruder zone activated (opened) ENTRY START Entry time started ZONE OMITTED Zone has been omitted for one set period FIRE ZONE Fire zone activated (opened) ZONE EXCLUDED Zone has been omitted for one set period User Events CODE ENTRY User has entered code SET PROGRAM User has set the system with program 1, 2 or 3 SYSTEM UNSET User has unset the system System Events CLE
Accenta/Optima Engineer’s Manual 48
Accenta/Optima Engineer’s Manual Library Appendix 2 - Library Kitchen Landing Living Room Lounge Patio Porch Stairs Study Utility Room Window 1 Window 2 Window 3 Attic Back Door Basement Bathroom Bedroom 1 Bedroom 2 Bedroom 3 Conservatory Dining Room Fire Zone Front Door Garage Hall 49
Accenta/Optima Engineer’s Manual 50
Accenta/Optima Engineer’s Manual Servicing/Parts Servicing Organisation Details Servicing Organisation name: Telephone number: Date of Installation: Account Number: Parts 8SP399A 8SP400A 8EP396A 8SP419A 8SP420A 8EP417A 8EP416 8EP276 8EP289 IS215T Accenta mini panel with LCD keypad Accenta mini panel with LED keypad Optima compact panel Accenta panel metal enclosure with LCD keypad Accenta panel metal enclosure with LED keypad Accenta LCD remote keypad Accenta LED remote keypad Informa Extension speaker
Accenta/Optima Engineer’s Manual Engineer Program Mode [PROG] [9] [9] [9] [9].