Setup guide

Section 2 – Installing the Control
2-13
Worksheet 3: Auxiliary Relay Output Current Load
Total Current
Device Model # Device Current X # of Units = Standby Alarm
XXXXXX
XXXXXX
XXXXXX
XXXXXX
XXXXXX
XXXXXX
Auxiliary Relay Output Subtotal
(terminals 5, 6, or 7 & 18 – 350mA max.)
4. In Worksheet 4, enter the total calculated subtotals of all listed outputs from Worksheets 1 through 3, then add
to get the combined current.
Worksheet 4: Total 5110XM Current Load
Total Current
Standby Alarm
Auxiliary Power Subtotal
Bell Output Subtotal
Auxiliary Relay Output Subtotal
5110XM PCB Current (Includes 2-wire smoke detector and LED indicator PCB
currents)
155mA 235mA
Total Current Load
(350mA max. standby; 1.0A max. alarm)
NOTE: Limit the total power supply standby current to 210mA when a 60-hour standby time is desired.
Determining the Size of the Standby Battery
Use the worksheet below to calculate the required battery capacity.
DO NOT use Gates batteries (sealed lead-acid type). These batteries require a different charging voltage than is
supplied by the panel.
Use Worksheet 5 to determine the required backup battery capacity and use the Battery Selection Table to determine
the battery model number. A dual battery harness is supplied that allows two batteries to be wired in parallel for
increased capacity.
5. Using the total calculated from Worksheet 5, calculate the battery capacity required for the
installation.
Worksheet 5: Battery Capacity Calculation Worksheet
Capacity Formula Calculated Value
Standby Capacity Total standby current X 24 or 60 hours X 1.1 contingency factor.
Alarm Capacity Total alarm curr. X 0.1 (6 min)
Total Capacity Add standby and alarm capacities (14AH max.)
6. Use the Battery Selection Table to select the appropriate battery for the installation.