Setup guide

5110XM Installation and Setup Guide
4-2
FIELD
TITLE and DATA ENTRIES EXPLANATION
0
320
Supervisory on Open/Short
0 = trouble on open/supervisory on short
1 = supervisory on open/supervisory on short
If
1, the system produces a supervisory condition on both an open and a
short. If
0, the system produces a trouble condition on an open and a
supervisory condition on a short.
Backup TouchTone
(Backup Dialer)
0 = pulse
1 = touchtone
Select the dialing method for the backup dialer.
0
330
0
340
Auxiliary Relay Function
Selection
0 = trouble/supervisory
1 = alarm, silenced by Silence/Reset
Button or User Code + OFF
2
= smoke detector reset
3 = battery save
4 = alarm, silenced by User Code + # + 67
Select the condition that will trigger the auxiliary relay.
NOTES:
Smoke detector reset triggers the relay momentarily (approximately 6
seconds) on the second
User Code + OFF entry.
Battery save is used to disconnect power from non-critical loads 4 hours after
AC loss.
When option 1 or 4 is selected, program fields
85 and 86 to select which
zones will trigger the auxiliary relay. When option 1 is selected, program
auxiliary relay timeout in field
31.
0
400
PABX Access Code
Enter 0-9; #11 for , #12 for #, #13 for a
2.5-second pause.
This field is used to enter up to four numbers representing the prefix needed
to obtain an outside Telco line. If not required, enter nothing and proceed to
next field.
0
410
Primary Phone Number
Enter 0-9; #11 for , #12 for #, #13 for a
2.5-second pause.
Enter the primary central station phone number, up to 12 digits. This is the
phone number the control will use to transmit Alarm and status messages to
the central station. Do not fill unused spaces.
NOTE: Backup reporting is automatic only if a secondary phone number is
entered.
0
420
Secondary Phone Number
Enter 0-9; #11 for , #12 for #, #13 for a
2.5-second pause.
Enter the secondary phone number, up to 12 digits. The secondary phone
number
is used if communication on the primary number is unsuccessful, or if
split/dual reporting is desired. Do not fill unused spaces.
0
430
Subscriber’s Account Number
Enter 0-9; #11 for B, #12 for C, #13 for D,
#14 for E, or #15 for F
Enter a 3- or 4-digit (depending on report format) primary subscriber account
number. If a 3-digit account number is to be used, enter data only in the first 3
locations, and enter
in the fourth location.
Phone Sys
(Main Dialer)
0 = pulse
1 = touchtone
Select the dialing method for the main dialer.
0
450
0
460
Report Format
0 = 3+1, 4+1 ADEMCO Low Speed;
1 = 3+1, 4+1 Radionics Standard;
2 = 4+2 ADEMCO Low Speed;
3 = 4+2 Radionics Standard;
6 = 4+2 Express;
7 = Contact ID;
8 = 3+1, 4+1 ADEMCO Low Speed
Expanded;
9 = 3+1, 4+1 Radionics Expanded
Enter the reporting format for both the primary and secondary telephone
numbers.
NOTE: The Fire Bell Silence message is always sent in Contact ID regardless
of the choice selected for this field.