Setup guide
Section 4 – Data Field Descriptions
4-3
FIELD
TITLE and DATA ENTRIES EXPLANATION
470
Split/Dual Reporting
0 = backup reporting only
1 = alarm, alarm restore, reports to primary,
all others to secondary
2 = all except test reports to primary, test to
secondary
3 = alarm, alarm restore, reports to primary,
all reports to secondary
4 = all except test reports to primary, all
reports to secondary
5 = all reports to both primary and secondary
Select the type of split/dual reporting for system communication.
0
490
Periodic Test Report
0 = none
1 = 24 hours
2 = weekly
3 = 30 days
Select the desired test report interval.
Must be a 1 for UL commercial fire installations.
NOTES: Program the Test Report Code in field 64 and the Off-Normal Test
Report Code in field
84.
0
500
Sescoa/Radionics Select
0 = disable
1 = enable
If disabled, selects Radionics, which uses hexadecimal 0-9, B-F reporting.
If enabled, selects Sescoa, which uses only numeric reporting (0-9).
NOTE: The selection applies to both primary and secondary phone numbers.
0
540
Program Mode Entry Report
Code
Enter the report code when the program mode is accessed.
0
550
Program Mode Exit Report Code
Enter the report code when the program mode is exited.
0
560
Zone Assignment/Alarm Report
Codes
See the SECTION 5: Menu Mode Programming for detailed information on
zone programming.
0
570
Zone Type 18 Delay Enable
0 = disable, ignore delay in field 78
1 = enable, use delay in field 78
If enabled, the system uses the delay programmed in field
78 before a
supervisory condition is annunciated for zone type 18. The fault condition
must be present for the entire delay.
To Program System Status, Trouble, and Restore Report Codes (54, 55, 58 – 74)
The following is a set of guidelines to be used for programming report codes. The actual digits that you enter depend upon the particular
installation, and should be in agreement with you and the central station office receiving the signals. Use these guidelines to program this
entire section.
With a 3+1 or 4+1 Standard Format: Enter a code in the first box: 1–9, A, B, C, D, E, or F. Enter "#+10" for A (this reports a “0” on some
receivers), "#+11" for B, "#+12" for C, "#+13" for D, "#+14" for E, "#+15" for F.
An entry of "0" in the first box will disable a report.
An entry of "0" in the second box will result in automatic advance to the next field when programming.
With an Expanded or 4+2 Format: Enter codes in both boxes (1st and 2nd digits) for 1–9, or A–F, as described above.
An entry of "0" in the first box will disable a report.
An entry of "0" in the second box will eliminate the expanded message for that report.
With ADEMCO Contact ID Reporting: Enter a digit in the first box to enable the zone to report. Use a different digit for each zone until
you have used up available digits. If the number of zones exceeds the number of available digits, begin with digit 1 again. This is an
"enabling" code only and is not the actual code sent to the central station office. Entries in the
second boxes will be ignored. For system
status (non-alarm) codes, enter a “1” in the first box for all the system conditions you want to send to the central station.
An entry of "0" in the first box will disable a report.
0
580
Supervisory Report Code
Enter the report code for a supervisory condition.
Note: In Low Speed format (4+2), the field 58 Supervisory Report Code is
sent for a Zone Type 18. The values entered in
56 Zone Programming are
overridden.
0
590
Supervisory Restore Report
Code
Enter the report code for the restore of a supervisory condition.