Setup guide
Section 4 – Data Field Descriptions
4-5
FIELD
TITLE and DATA ENTRIES EXPLANATION
0
790
Main/Backup Dialer Enable
0 = disable
1 = enable
This field has two entries, one for each dialer (main and backup). Enter
1 if
the dialer is being used.
0
820
Alpha Programming
See the SECTION 5: Menu Mode Programming for detailed information on
alpha programming. Alpha programming can also be done in field
56.
0
840
Miscellaneous Report Codes
This field has three 2-digit entries. The first is for Fire Walk Test Start, the
second for Fire walk Test End, the third for Off-Normal Dialer Test. See the
box above field
57 for programming information.
0
850
Zones 1-7 Bell & Auxiliary Relay
Activation
0 = none
1 = bell only
2 = auxiliary relay only
3 = bell and auxiliary relay
Select which output, if any, each zone activates upon an alarm, trouble or
supervisory condition. There are seven entries in this field, one for each zone.
0
860
Zones 10-12, 95 and 96 Bell &
Auxiliary Relay Activation
0 = none
1 = bell only
2 = auxiliary relay only
3 = bell and auxiliary relay
Select which output, if any, each zone activates upon an alarm, trouble or
supervisory condition. There are six entries in this field, one for each zone.
NOTE: The first entry does not pertain to any zone and must always be
programmed with a
0. The second entry pertains to zone 10.
0
940
Download Phone Number
Enter 0-9; #11 for , #12 for #, #13 for a
2.5-second pause.
Enter the download phone number, up to 12 digits. This is the phone number
the control will use to connect to the central computer for downloading. Do
not fill unused spaces.
0
950
Ring Detection Count
Enter 0 to disable ring detection.
Enter
1-9, #10, #11, #12, #13, #14 for ring
counts of 1-14.
Enter #15 to select Answering Machine
Defeat Mode
Enter the number of rings before the control panel picks up the phone line.
In the Answering Machine Mode, the caller should let the phone ring once,
wait for a hang up, and call again within 30 seconds. The system, upon
hearing one ring followed by nothing, does not answer the first call, but
readies itself to pick up on the first ring of the next incoming call that is
received within 30 seconds (i.e., the downloader calling again).
Must be
0 for UL commercial fire installations.
0
960
Initializes Download ID and
Subscriber Account Number for
Downloading
No entry is required.