Menu Mode Programming
General Information
The Menu Mode Programming is an interactive mode through which much of the system’s zone and alpha programming
is done. In this mode, there are “question and answer” prompts. These require a 2-line alpha keypad (6160).
Fields 56 is used to program zone numbers, zone types, and alarm report codes. This field can also be used for
entering alpha descriptors for zones (however, we recommend entering descriptors in menu mode 82.
Field 56 Zone Programming
Enter the programming mode and press 56. The following prompt displays:
PROMPT
EXPLANATION
Enter Zn Num.
(00 = Quit) 01
Zone 01 entered
Zone Number (Zn): Enter the zone number that you wish to program (or [0][0] to leave zone
programming).
Zn ZT RC
01 09 10
Press []. A summary display will come up, showing the status of that zone's program.
If it is programmed satisfactorily, press [#] to back up one step and enter another zone number, if
desired.
If the zone is not programmed, or you want to change it, press [
]. A prompt for Zone Type will
appear.
Zone Type
01 Zone Type
Fire 09
Zone Type 09 entered
Zone Type (ZT): Each zone must be assigned to a zone type, which defines the way in which
the system responds to faults in that zone.
Enter the zone type code (or change it, if necessary). Zone types are listed below.
00 = Not Used 08 = 24 Hr Auxiliary Alarm
(DO NOT USE)
17 = Fire Waterflow
06 = 24 Hr Silent
(DO NOT USE)
09 = Fire, no verification. 18 = Fire Supervisory
07 = 24 Hr Audible Alarm
(DO NOT USE)
16 = Fire, with verification 19 = 24 Hour Trouble
When the display shows the zone type you want, press [] to advance.
01 Report Code
1st 00 2nd 00
Report Code (RC): The report code consists of 2 hexadecimal digits, each in turn consisting of
2 numerical digits. For example, for a report code of "3C", enter [0][3] for "3" and [1][2] for "C".
Enter the numbers and press [] to advance to the Summary Display.
NOTE: Report codes for Fire Alarms cannot be disabled and are always sent to the central
station regardless of the report code entered.
Zn ZT RC
01 09 3C
Accepted report code
Typical Summary Display. A summary of the programmed values for the selected zone will be
displayed.
If all is okay, press [].
Program Alpha?
0 = No 1 = Yes
Alpha Programming: For all zone types, the next request is to enter Alpha descriptors for the
zones. The entry may be done now (enter 1), or may be done at a later time via
82
mode
(enter 0).
See Field 82 Alpha Programming for the detailed procedure later in this section.