Setup guide

5110XM-SIMP-V2
ADEMCO 5110XM SIMPLIFIED WIRING DIAGRAM
N.O.
N.C.
2k
N.O.
N.C.
N.O.
N.C.
2k
N.O.
N.C.
2k
2k
N.O.
N.C.
2k
12
9
10
11
13 19
2017 1815 1614
The combined standby current drawn from aux power and relay power
cannot exceed 350mA.
The combined alarm current drawn from aux power, relay power, and
bell cannot exceed 1.0A.
TROUBLE
(YELLOW)
ALARM
(RED)
SUPERVISORY
(YELLOW)
SILENCE
(YELLOW)
LINE FAULT
(YELLOW)
COMM FAIL
(YELLOW)
RED
BLACK
GREEN
ZONE 1 +
ZONE 2 +
ZONE 1/ZONE 2 -
ZONE 3 +
ZONE 4 +
ZONE 3/ZONE 4 -
ZONE 5 +
ZONE 5 -
YELLOW
+
GND
DATA IN
2-WIRE SMOKE DETECTOR LOOP
DATA OUT
BATT TROUBLE
(YELLOW)
AC POWER
(GREEN)
MAIN
DIALER
LINE
SEIZE
(GREEN)
WARNING
SOUNDER ACTIVATES ON ALARMS,
SUPERVISORIES AND TROUBLES
SOUNDER SILENCE SWITCH
PUSH ONCE TO SILENCE,
PUSH AGAIN TO RESET
2k
MODEL
EOLR20
HORN
BELL
LED INDICATOR BOARD
PLUG BOARD INTO THE
J5 9-PIN HEADER.
J5
24 5232221 786
FIRE CKTS: Supervise using 2k EOLR.
Use polarized sounding devices.
Ratings: 10 - 14VDC, 1.0A max.
See note 1, see instructions for compatible devices.
120VAC, 60Hz
CONNECT TO
A DEDICATED
CIRCUIT
CONNECT TO
PROPER EARTH
GROUND.
WHT
BLK
BLUE
BLUE
NOTE: USE WIRES RATED
FOR 90C OR HIGHER.
18VAC, 40VA
CONNECT TO
AC POWER
TERMINALS 1, 2
MAINTAIN
MINIMUM 1/4"
SPACING FROM
OTHER WIRING.
(NOTE 6)
GREEN
2A CIRCUIT
BREAKER
ALL CIRCUITS ARE POWER LIMITED EXCEPT
THE OUTPUT OF THE POWER TRANSFORMER
AND BACKUP BATTERIES
ALL POWER-LIMITED WIRING MUST BE
SEPARATED FROM OTHER WIRING BY
AT LEAST 1/4 INCH (6.4.MM).
AUX RELAY HAS PROGRAMMABLE FUNCTION
(NOT SUPERVISED)
JUMPER W3 INT ACT: 10-14VDC ON TERMINAL 6
350mA MAX (STANDBY) /1A MAX (ALARM),
POWER-LIMITED (SEE NOTE 2).
USE TERMINAL 18 FOR GROUND RETURN.
JUMPER W3 CUT: NO VOLTAGE ON TERMINAL 6.
RELAY CONTACT RATING: 30 VAC/VDC,
2A MAX RESISTIVE LOADS.
POLE/RELAY +
N.C.
GREEN
N.O.
AC Input Power
AC
AC
RJ31X
MAKE CONNECTIONS TO SEPARATE
TELEPHONE LINES USING CABLE SUPPLIED.
SUPERVISION IS PROGRAMMABLE.
USE BATTERY CABLES
SUPPLIED
12V LEAD ACID BATTERY
7 AH MIN/14 MAX.
SEE INSTRUCTIONS FOR
REQUIRED CAPACITY AND
BATTERY MOUNTING
BACK-UP
DIALER
LINE
SEIZE
(GREEN)
MAIN DIALER
PHONE JACK
BACK-UP DIALER
PHONE JACK
BATT +
ZONE NOTES
BATT -
BLACK
RED
ALL ZONES ARE CLASS B AND PROVIDE STYLE B SUPERVISION.
ZONE RESISTANCE (EXCLUDING EOLR):
+ZONES 1-4: 300 OHM MAX.
+ZONE 5: 100 OHM MAX.
ZONE RESPONSE: 300-500 MILLISECOND (ALL ZONES).
ZONE 5 RATINGS: +10-14VDC
+2mA MAX FOR 2-WIRE SMOKE DETECTORS. UP TO 16 DETECTORS OF
TYPE SPECIFIED IN INSTRUCTIONS MAY BE USED.
2K EOLR IS ADEMCO MODEL EOL20.
PROGRAM USING DELAY TIME MARKED ON DETECTORS.
EARTH
GROUND
RELAY
POWER
JUMPER
AUXILIARY
RELAY
BELL +
BELL CIRCUIT SUPERVISION JUMPER
INTACT: SUPERVISED USING 2K EOLR
DO NOT CUT.
BELL -
BLUE
BLUE
TO FACILITY GROUND
TO POWER SUPPLY ENCLOSURE
TO PC BOARD TERMINAL 8
TO CABINET DOOR (NOT SHOWN)
SEE AC
TRANSFORMER
CONNECTIONS
ABOVE
(SUPERVISED)
For commercial fire, bell timeout must be a minimum
of 6 minutes.
All Earth Grounds must be wired to cabinet ground post. Use
minimum AWG16 wire.
Each output may be selected for Style Y supervision or no
supervision. Supervision may be disabled by cutting jumper W2
and programming Zone 6 for no response.
For approved Special Application Notification Appliance Circuits,
the maximum line impedance allowed when the system is fully
loaded to 1.0A for devices that can operate at a minimum of
8VDC is 2.0 ohms. For devices that can operate at a minimum
of 9VDC the maximum line impedance is 1.0 ohms.
2k EOLR is Ademco model EOL20.
1.
6.
No more than one (1) wire per terminal may be connected.
5.
Use only 14-22 AWG wire.
4.
3.
2.
NOTES
W3
(RED)
W2 (WHITE)
OPTIONAL
REMOTE
KEYPADS
AUX POWER RATING: 10-14VDC,
350mA MAX, POWER LIMITED
NOT SUPERVISED (SEE NOTE 2).
6150 OR 6160 MAY BE USED
IN CONJUNCTION WITH THE
CONTROL PANEL'S LED
INDICATORS AND
SILENCE/RESET BUTTON.
ONLY A 6160 MAY BE USED TO
PROGRAM PANEL.
CABINET GROUND POST
EARTH GROUND INFORMATION
(SEE NOTE 6)
(NOTE 6)
RJ31X
AUX POWER
REFER TO SOC LABEL FOR DETAILED INFORMATION