Installation Manual

6
Function Code options – advanced menu
Note: Default settings for Function Codes 1-28 are automatically determined by the HVAC equipment. It may take up to 40 seconds to enter
setup, and 30 seconds to exit setup.
Function # Name Options Notes
1 Power Failure
Automatic Recovery
1 = Disabled
2 = Enabled
3 =Not supported
2 Temperature Sensing
Location
1 = Average
2 = Sense at Indoor Unit
3 = Not supported
3 Ventilation Air 1 = Not supported
2 = Indoor Unit doesn’t intake outdoor air through LOSSNAY
3 = Indoor Unit does intake outdoor air through LOSSNAY
4 Power Voltage 1 = 230V
2 = 208V
3 = not supported
5 Indoor Unit Automatic
Operation
1 = On
2 = Off
3 = Not supported
7 Change Filter Duration 1 = 100 Hours
2 = 2500 Hours
3 = Not Used
Unit Function Option defaulted to most common setting at power up by
Gateway (via Indoor Unit)
8 Auto Fan (Speed
Setting)
1 = Quiet
2 = Standard
3 = High Ceiling
9 Number of Air Outlets
(PLA Only)
1 = 4 directions
2 = 3 directions
3 = 2 directions
10 High Performance
Filter Installed
1 = Not Supported
2 = Supported
3 = Not Supported
Either setting 1 or 3 could be used when the unit does not support this feature.
11 Airflow Direction
Settings
1 = No Vanes (or Vane # 3 for PLA)
2 = Vane # 1 setting
3 = Van # 2 setting
15 Frost Prevention
Temperature Offset
1 = 36°F (2°C)
2 = 37°F (3°C)
3 = Not Supported
23 Airflow Oscillate Mode 1 = Not Available
2 = Available
3 = Not Supported
24 Heat Mode
Temperature Offset
1 = On
2 = Off
3 = Not Supported
25 Heat Mode Fan Option 1 = Extra Low
2 = Stop
3 = Selectable Fan Speed
27 Cooling Mode Fan
Option
1 = Selectable Fan Speed
2 = Stop
3 = Not Supported
28 Display System Error 1 = Enable
2 = Disable
3 = Not Supported