9,67$ 3 36 6HULHV 9,67$ 3 6HULHV 6HFXULW\ 6\VWHPV ,QVWDOODWLRQ DQG 6HW 8S *XLGH 1 OFF ARMED 4 MAX READY 7 INSTANT READY 2 AWAY 5 TEST 8 CODE 0 3 STAY 6 BYPASS 9 CHIME # ARMED READY ON OFF 1 OFF 2 AWAY 4 MAX 5 7 INSTANT READY TEST 8 CODE 0 3 STAY 6 BYPASS 9 CHIME # ® K5305-1V1 4/02
RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide Proper Coverage for the Protected Premises. Recommendations For Smoke And Heat Detectors With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted below.
Table Of Contents • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Section 1. Features and Installation Highlights........................................................................................ 1-1 Capabilities ....................................................................................................................................................................... 1-1 Functions .....................................................................................
Section 5. Zone Programming ........................................................................................................................ 5-1 About Zone Programming................................................................................................................................................. 5-1 ∗56 Zone Programming Procedure ...................................................................................................................................
S E C T I O N 1 Features and Installation Highlights • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • This manual applies to the following controls: VISTA-20P, VISTA-20PS, VISTA-20PCN, VISTA-20PSCN, VISTA-15P, VISTA-15PCN Features and procedures apply to all, except where differences are noted. References to VISTA-20P apply to both the VISTA-20P and VISTA-20PS, unless noted for VISTA-20PS only.
Installation and Setup Guide Compatible Devices • Supports up to 8 Addressable Keypads: 6150 Fixed-Word Display Keypad, 6160 Alpha Keypad, 6150V Fixed-Word Display Voice Keypad, 6160V Alpha Display Voice Keypad, 6150RF Keypad/Transceiver • Supports 4219, 4229 addressable hardwire zone expander modules (VISTA-20P = up to five for up to 40 expansion zones; VISTA-15P = up to 2 for up to 16 expansion zones) • Supports 5881 series receiver and 5800 series transmitters • Output relays and/or Powerline Carrier De
S E C T I O N 2 Mounting and Wiring the Control • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • This section describes the procedures for mounting and wiring this control and its peripheral devices. In the following subsections, procedures are listed in the left column, while notes and pertinent explanations are provided in the right column. Cabinet and Lock Notes 1. • The cabinet can be closed and secured without a lock by using 2 screws in the cover's edge.
Installation Instructions Mounting Board with RF Receiver Notes 1. • Do not mount the cabinet on or near metal objects. This will decrease RF range and/or block RF transmissions from wireless transmitters. • Do not locate the cabinet in an area of high RF interference (revealed by frequent or prolonged lighting of the LED in the receiver after it is operational (random flicker is OK) 2. 3. a.
Mounting and Wiring the Control Wiring to Keypads Notes 1. • • • • 2. 3. Connect keypads to the control’s keypad terminals as shown on the Summary of Connections diagram. Determine wire gauge using the Wiring Run Chart below. Set keypad addresses. Refer to the address setting instructions included with the keypads and set each keypad device address according to the chart at right. Program the keypad addresses, partition assignments and sound options in data fields *190*196.
Installation Instructions Sounder (Bell) Connections Notes This control complies with NFPA requirements for temporal pulse sounding of fire notification appliances. Temporal pulse sounding for a fire alarm consists of: 3 pulses – pause – 3 pulses – pause – 3 pulses–etc.. 1. Make sounder connections to alarm output terminals 3 (+) and 4 (–). For supervised output, continue with steps 2 and 3. 2. Cut the red Bell Supervision Jumper located above terminals 2 and 3 on the control board. 3.
Mounting and Wiring the Control Backup Battery Notes 1. Place the 12-volt backup battery in the cabinet. 2. After all connections to the control are completed and AC power has been applied, connect the red and black flying leads on the control board to the battery. Do not attach these leads to the battery terminals until all connections are completed. Battery Saver Feature: The battery will disconnect from the system after its voltage decreases below 9VDC.
Installation Instructions Hardwire Zones Notes Normally Open Zones/ Normally Open EOLR Zones 1. Connect open circuit devices in parallel across the loop; for EOLR zones, connect the EOLR across the loop wires at the last device. 2. Enable normally open/EOLR zones using Zone Programming mode, “Hardwire Type” prompt. • EOLR: If the EOLR is not at the end of the loop, the zone is not properly supervised and the system may not respond to an “open” on the zone. • Zone 1 is intended for EOLR only.
Mounting and Wiring the Control Smoke Detectors (continued) Notes 4-Wire Smoke Detectors 3. Connect 4-wire smoke detectors to any zone from 2 and higher as shown below. This control does not automatically reset power to 4-wire smoke detector zones, so you must use a relay (e.g., 4204, 4229), or on-board trigger to reset power (also required for fire verification). Do this by programming the designated relay/trigger as zone type 54 (fire zone reset); see OnBoard Trigger section for other information.
Installation Instructions Installing the RF Receiver Notes Use any ADEMCO 5800 Series Wireless Receivers, such as: RF Receiver No.
Mounting and Wiring the Control Transmitter Battery Life •See Wireless Transmitter paragraph in the Limitations of This Alarm System statement located at the end of this manual for information on transmitter battery life. •Some transmitters (e.g., 5802 and 5802CP) contain long-life but non-replaceable batteries, and no battery installation is required. At the end of their life, the complete unit must be replaced (and a new serial number enrolled by the control).
Installation Instructions Connecting Relay Modules Notes 1. Mount either remotely or in the control panel. 2. Connect to control’s keypad terminals using the connector harness supplied with the module. Use standard 4-conductor twisted cable for long wiring runs. 3. Set each module’s device address according to the table at right. 4. Connect the desired field wiring to the unit's relay contact terminals. • Use 4204 or 4229 modules. • Supervision: 4204 and 4229 modules are supervised against removal.
Mounting and Wiring the Control Powerline Carrier Devices Notes 1. Install the powerline carrier devices according to the instructions included with each. VISTA-20P: Up to 16 devices (if no relays are used) VISTA-15P: Up to 8 devices (if no relays are used) • When using Powerline Carrier devices, you must use a 4300 or 1321X10 Transformer instead of the 1321 Transformer. 2. Use Programming Mode to enter the device house ID in data field*27, and enter the unit code using *79 Output Device menu Mode.
Installation Instructions Phone Line/Phone Module Connections Notes 1. Connect incoming phone line and handset wiring to the main terminal block (via an RJ31X jack) as shown in the Summary of Connections diagram at the back of this manual. Wire colors represent the colors of the cable to the RJ31X jack. If using a phone module, continue with the following steps. 2.
Mounting and Wiring the Control Long Range Radio Connections Notes • Use compatible Long Range Radios (e.g., 7720PLUS, 7820, 7835C, or 7845C). Connect the data in/data out terminals and voltage input terminals of the Long Range Radio to the control's keypad connection points. Set the radio’s address to “03” following the instructions provided with the radio. AAV Connections Notes Refer to the connection diagrams below.
Installation Instructions 2-14
S E C T I O N 3 Programming Overview • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Programming You can program the system at any time, even at the installer's premises prior to the actual installation. Programming can also be performed remotely from the installer’s office/home, using an IBM personal computer, a modem, and Compass downloading software.
Installation Instructions Keypads Keypads are identified by predefined addresses (starting at address 16) as follows: Address Keypad Program Field 16 keypad 1* • always enabled for partition 1, all sounds enabled. 17 keypad 2 • data field *190 18 keypad 3 • data field *191 19 keypad 4 • data field *192 20 keypad 5 • data field *193 21 keypad 6 • data field *194 22 keypad 7 • data field *195 23 keypad 8 • data field *196 NOTE: First keypad is address 16. To enable keypads: 1.
Function Keys To assign functions to the function keys, use *57 Function Key menu mode. To assign emergency key functions (function key option “00”), first program the respective emergency zone number (95 for “A” key, 96 for “C” key, 99 for “B” key) with the desired zone type using *56 Zone Programming mode, then use *57 Function Key menu mode to assign the desired key.
Installation Instructions Type 06 24-hour Silent Alarm • Usually assigned to a zone containing an emergency button. • Sends a report to the central station but provides no keypad display or sounding. Type 07 24-hour Audible Alarm • Assign to a zone that has an emergency button. • Sends a report to the central station, and provides an alarm sound at the keypad, and an audible external alarm.
Type 24 Silent Burglary Type 77 Keyswitch Type 81 AAV Monitor Zone Types 90-93 Configurable • Usually assigned to all sensors or contacts on exterior doors and windows where bells and/or sirens are NOT desired. • Provides an instant alarm, with NO audible indication at any keypad or external sounder, if the zone is faulted when the system is armed in the Away, Stay, Instant, or Maximum modes. • A report is sent to the central station. • Assign to zone wired to a keyswitch.
Installation Instructions Interactive Mode Programming (∗56, *57, ∗58, ∗79, ∗80, ∗81, ∗82) Press [∗] + [Interactive Mode No.] (for example, ∗56) while in Program Mode. The Alpha display keypad will display the first of a series of prompts requesting entries. After making the appropriate entry, press the [∗] key to accept the entry and continue to the next prompt. Entering Interactive Mode Loading Factory Defaults/Initializing for Download Press ∗97 while in Program Mode.
S E C T I O N 4 Data Field Programming • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Data Field Programming The following pages list this control’s data fields in numerical order. Field numbers are listed in the left column followed by a “Title and Data Entries” column, which lists the valid entries for each field. Experienced installers can simply follow this column when programming the data fields.
Installation Instructions FIELD TITLE and DATA ENTRIES EXPLANATION *29 Long Range Radio Output If selected, all messages programmed to go to the primary telephone line receiver will also be sent to the connected 7720PLUS, 7820, 7835, or 7845 Radio (sent in Contact ID format). The data line is supervised as well as certain functions in the radio. If communication is lost or a trouble develops, an attempt will be made to send a message via both radio and telephone to the central station.
Dialer Programming (∗40 – ∗50) FIELD TITLE and DATA ENTRIES EXPLANATION *40 PABX Access Code To clear entries from field, press ∗40∗. If fewer than 6 digits need to be entered, exit by pressing [∗], which advances to the next field. *41 *42 *43 *44 *45 *46 *47 Enter up to 6 digits if PABX is needed to access an outside line. Do not fill unused spaces.
Installation Instructions FIELD TITLE and DATA ENTRIES EXPLANATION *54 Dynamic Signaling Delay Intended for use with Long Range Radio reporting. This field lets you select the time the panel should wait for acknowledgment from the first reporting destination (see ∗55) before it attempts to send a message to the second destination. Delays can be selected from 0 to 225 seconds, in 15-second increments. This delay is per message.
FIELD TITLE and DATA ENTRIES EXPLANATION *59 Exit Error Report Code If the system is armed and an entry/exit or interior zone is still open after the Exit Delay time has expired, an alarm will sound (keypad displays “EXIT ALARM”). If the system is disarmed before the end of the Entry Delay, the alarm sounding stops and no message is sent to the central station. The keypad will display “CA” (Fixed-Word display keypads) or “CANCELED ALARM” (Alpha display keypads).
Installation Instructions FIELD TITLE and DATA ENTRIES *72 Bypass Restore Report Code *73 AC Restore Report Code *74 Low Bat Restore Report Code *75 RF Xmtr Low Batt. Restore Code 0 = no report 1-F = see description above *59 0 = no report 1-F = see description above *59 0 = no report 1-F = see description above *59 0 = no report 1-F = see description above *59 EXPLANATION This is sent when a zone that has been bypassed is unbypassed. UL: Required for UL commercial burglar alarm installations.
FIELD *86 TITLE and DATA ENTRIES Cancel Verify *87 Misc. Fault Delay Time *88 Program Mode Lockout Options EXPLANATION When enabled (1 = yes), this feature causes a “CANCELED ALARM” display on the LCD keypad under the following conditions: • After the kissoff of the cancel message to the Central Station, indicating a successful transmission. • When an alarm is successfully canceled before the Central Station received the Alarm message. E.g.
Installation Instructions FIELD TITLE and DATA ENTRIES EXPLANATION *92 Phone Line Monitor Enable Entry 1: Sets the length of time a phone line fault must remain after detected before the second digit option is activated. Entry 1–Timeout: 0 = disabled 1-15 = 1 minute to 15 minutes respectively (2 = 2 min, 3 = 3 min, etc.; # + 10 =10 min, # + 11 = 11 min, # + 12 = 12 min, # + 13 = 13 min, # + 14 = 14 min, # + 15 = 15 min) Entry 2–Display/Sound: 0 = keypad display only when phone line is faulted.
Pager Programming Fields FIELD TITLE and DATA ENTRIES EXPLANATION *160 Pager 1 Phone No. If you enter fewer than 20 digits, exit by pressing [∗] and next field number. To clear entries from this field, press ∗160∗. *161 Pager 1 Characters Up to 16 optional characters may be sent as a prefix to the 7-digit system status code sent to pager #1 (if used). Phone number in field *160 must have been entered. If fewer than 16 characters, exit by pressing [∗] and next field number.
Installation Instructions FIELD TITLE and DATA ENTRIES EXPLANATION *164 Pager 2 Characters Enter up to 16 characters See field ∗161 for explanation of entries. If fewer than 16 characters, exit by pressing [∗] and next field number. To clear entries from this field, press ∗164∗. *165 Pager 2 Report Options Enter the types of reports to be sent to pager 2 for each partition. *166 Pager 3 Phone No. *167 Pager 3 Characters *168 Pager 3 Report Options *169 Pager 4 Phone No.
Configurable Zone Type Programming Fields The system allows you to define custom zone types (VISTA-20P supports 4 [types 90-93]; VISTA-15P supports 2 [types 90, 91]), based on the options described below. All configurable zone types can be programmed via the downloader. Configurable zone types 90 and 91 can also be programmed from a keypad using data fields *182-*185 described below. UL installations: Do not configure zones as fire alarm or UL burglar alarm zones.
Installation Instructions Configurable Zone Type Charts ENTRY 1 ENTRY 2 Response when system disarmed and zone is: Intact EOL Open Shorted RF zone normal 0 = normal 1 = alarm 2 = trouble 3 = fault RF zone N/A 0 = normal 4 = alarm 8 = trouble 12 = fault Auto Restore Vent Zone RF zn off-normal Entry 1 = EOL + Open 0 = normal 0 = no 0 = no 1 = alarm 4 = yes 8 = yes 2 = trouble 3 = fault see note 6 Entry 2 = Short + auto restore + vent zone ENTRY 3 ENTRY 4 Response when armed STAY and zone is: Int
Symphony (AUI) Enable FIELD TITLE and DATA ENTRIES EXPLANATION *189 Symphony (AUI) Enable APPLIES TO VISTA-20PS ONLY. Enter each AUI’s home partition. 0 = disabled 1 = partition 1 2 = partition 2 3 = common lobby NOTE: A minimum of one standard keypad must also be installed when AUI is used. Keypad Programming Fields NOTE: Each keypad must be assigned a unique address. Keypads programmed with the same address will give unpredictable results.
S E C T I O N 5 Zone Programming (✱56 and ✱58 Menu Modes) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Zone Programming ✱56 Zone Programming is used to program zones, zone types, report codes, enroll 5800 RF Wireless Transmitter serial numbers, and identify the type of loop input device(s).
Installation Instructions PROMPT 10 Zone Type Perimeter 03 VALID ENTRIES EXPLANATION Zone Type (ZT) Each zone must be assigned to a zone type, which defines the way in which the system responds to faults in that zone. Enter the Zone Type code from the list below: Note: If 00 is entered, Delete Zone ? will be displayed.
PROMPT 10 INPUT S/N: L A022-4064 1 10 INPUT S/N A022-4064 L ? VALID ENTRIES EXPLANATION Serial number Entry and Loop Number Entry Used only when enrolling wireless transmitters. a. Transmit two open/close sequences. If using a button-type transmitter, press and release the button twice, but wait about 4 seconds before pressing the button the second time. OR b. Manually enter the 7-digit serial number printed on the label of the transmitter.
Installation Instructions Completing Zone Programming When you have finished programming all zones, test each zone using the system’s TEST mode. Do not use the Transmitter ID Sniffer Mode for checking wireless transmitting devices, as it will only check for transmission of one zone on a particular transmitter, NOT the zones assigned to each additional loop.
PROMPT 10 INPUT S/N: AXXX-XXX L – VALID ENTRIES EXPLANATION Serial number Manually enter the serial number (found on the transmitter label), by typing digits in the “X” locations, using the [A] (advance) or [B] (back) keys as required. You can also perform two open and close sequences; for button-type transmitters that means pressing and releasing the button twice. NOTE: If you want to copy the previous zone’s serial number, press the [C] key.
Installation Instructions Wireless Key Programming Templates This procedure programs the wireless keys, but a key is not active until it is assigned to a user number (see System Operation section, assigning attributes command). If the D key was previously pressed (from *58 Menu mode) to enter and duplicate 5804 and/or 5804BD wireless keys, the following screens appear. PROMPT TEMPLATE ? 1–6 L T 01 23 02 22 1 03 04 21 23 PARTITION 1 VALID ENTRIES EXPLANATION Template Number 1.
Not Confirmed Entd A022-4063 Rcvd A022-4064 If the serial number transmitted does not match the serial number entered, a display similar to the one shown will appear. If the loop number does not match, it will also be displayed. If so, activate the button on the wireless key once again. If a match is not obtained (i.e., summary display does not appear), press the [#] key and then enter the correct serial number.
Installation Instructions 5-8
S E C T I O N 6 Output Device Programming (*79/*80 Menu Mode) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Output Device Programming Output Devices: The VISTA-20P system supports up to 16 relays and/or Powerline Carrier devices (X-10 devices) plus 2 built-in trigger outputs in any combination. These 18 “outputs” are assigned to system-wide output numbers (01-18). Use *79 Menu Mode to assign output numbers and map them to device addresses.
Installation Instructions Start Output Device Mapping by pressing *79 while in Data Programming Mode. The following prompts are displayed: ∗79 Menu Mode PROMPT ENTER OUTPUT NO. 00 = QUIT xx 17 OUT NORM LOW 0 = NO 1 = YES 0 XX OUTPUT TYPE DELETE 0 “A” XX UNIT No. yy “B” XX MODULE ADDR 07-15 yy 6-2 EXPLANATION Device Output Number This is the logical (or reference) relay number as used in the system.
*80 Menu Mode: Defining Output Functions Use this mode to program output function definitions (up to 48 functions) that provide automated control of any of the output devices, based on events occurring on individual zones or zones with certain zone types. Each output definition is identified by an output function number, and includes the following components: Output Definition Components Component Description Output Function No. A reference number that defines an output’s characteristics.
Installation Instructions Activated By 01 Activated By: Zone List 0 = delete 1 = zone list 2 = zone type 3 = zone number [∗] to continue Select where the initiating event for this output definition is to occur as follows: 0 = delete (deletes the output function and any previous programming;-see prompt below) 1 = zone list (go to “A” prompt) 2 = zone type (go to “B” prompt) 3 = zone number (go to “C” prompt) If you enter “0,” the following prompt appears: Press 1 to delete this output definition.
“C” Zone Number 01 Enter Zn No. 12 If zone number was selected, this screen appears. Enter the desired zone number associated with this output number. Press [✱] to continue. Enter the zone event that will activate this output. 01 Enter Event Restore 0 = restore; 1 = alarm/fault/trouble 0 Press [✱] to continue to the “Output Action” prompt 01 Output Action Close for 2 sec 1 Enter Output No. R02 02 02 A E P TRIG R02 1 1 3 ZL=1 Output Action Enter the desired device action as listed below.
Installation Instructions 6-6
S E C T I O N 7 Zone Lists (∗81) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Zone Lists (*81 Menu Mode) Zone lists let you group individual zones for use with certain system actions. The following table shows the available zone lists and their purposes: List No.
Installation Instructions Notes: • Any list may include any or all of the system's zone numbers. • A zone list can be assigned to more than one output relay. • When creating zone list 4 for cross zoning, include only zones assigned to zone types 3, 4, or 5. Do not include zones that have delays (entry/exit zones, interior w/delay) or 24-hour zones, as these zone types may produce unpredictable operation and may not function as intended.
S E C T I O N 8 Function Key Programming (✱57 Menu Mode) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Function Key Programming The system provides the ability to program each of the four keypad function keys to perform one of 12 system operations. The end user can then activate the function by simply pressing and holding the programmed key for 2 seconds. Typical functions (listed below) include single-button arming, turning lights on/off, or single-button paging.
Installation Instructions 8-2
S E C T I O N 9 Alpha Descriptor Programming (*82 Menu Mode) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Descriptor Programming The system lets you assign zone descriptors for protection zones, keypad panics, and RF receiver supervision faults. Each description can be composed of a combination of words (up to 3) selected from a vocabulary of 196 words stored in memory (see a following page).
Installation Instructions ✱ ZN 01 Flashing Cursor [∗] to continue ✱ ZN 01 B ACK First 3-Digit Index No. see index for entries [∗] to continue ✱ ZN 01 BACK ✱ ZN 01 BACK D OOR ✱ ZN 01 BACK DOOR Accept First Word 6 = save word and go to next word in this descriptor 8 = save word and end descriptor- go to next zone To delete or change the default descriptor for zone 1, press [✱] plus the same zone number (01). This will clear that descriptor and allow changes to be made at the flashing cursor.
Adding Custom Words (will not be annunciated by 4285/4286 Phone Module) You can add up to 10 installer-defined words to the built-in vocabulary, which can then be used when programming zone descriptors. Each of the 10 words can actually consist of a word string of one or more words, but no more than ten characters can be used for each word or word string. When adding custom words, the keypad keys perform the following functions: [4] Moves cursor one space to the left.
ALPHA VOCABULARY LIST (For Entering Zone Descriptors) 000 • 001 • 002 004 005 • 006 • 007 • 009 010 • • • • • • • 012 013 014 016 017 018 019 020 • 021 • 022 023 025 • 026 028 • 029 030 031 033 034 035 036 • 037 038 • 040 • 046 047 • 048 049 • 050 051 • 052 • 053 054 055 • 057 Note: (Word Space) –A– AIR ALARM ∗ ALLEY AMBUSH AREA APARTMENT ATTIC ∗ AUDIO –B– BABY ∗ BACK ∗ BAR BASEMENT ∗ BATHROOM ∗ BED BEDROOM ∗ BELL BLOWER BOILER BOTTOM BREAK BUILDING –C– CABINET CALL CAMERA CAR CASH CCTV CEILING CELLAR C
S E C T I O N 1 0 Creating Schedules • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Schedules The VISTA-20P system provides up to 32 schedules (VISTA-15P supports 8), which can be used to control 11 types of system events at pre-defined times. Sixteen schedules are intended for use by the end-user, and sixteen are reserved for the installer (VISTA-15P = 4 user schedules, 4 installer schedules).
Installation Instructions START SMTWTFS HH MMAM 0 0 1 0 0 0 0 START SMTWTFS HH MMAM 0 0 1 0 0 0 0 Start Time Enter the event’s start time and days of the week to occur. To select days, position the cursor under the desired days using the [∗] key to move forward, then press “1” to select the day. Stop Time Enter the event’s stop time and days of the week to occur. To select days, position the cursor under the desired days using the [∗] key to move forward, then press “1” to select the day.
S E C T I O N 1 1 System Communication • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Panel Communication with Central Station This system accommodates several formats for reporting alarms and other system conditions to the Central Station. The process of a successful transmission consists of both the method of communication between the control panel and the Central Station receiver; and the actual way the information is sent and displayed at the Central Station.
Installation Instructions The following table lists codes for reports sent in different formats: Type of Report Code for 3+1/4+1 Standard Code for 3+1/4+1 Expanded Alarm SSS(S) A SSS(S) A AAA(A) Z SSSS AZ Trouble SSS(S) T SSS(S) T TTT(T) t SSSS Tt Bypass SSS(S) B SSS(S) B BBB(B) b SSSS Bb AC Loss SSS(S) E SSS(S) E SSSS EAC Low Batt SSS(S) L Code for 4+2 EEE(E) AC SSS(S) L SSSS LLB LLL(L) LB Open SSS(S) O SSS(S) O OOO(O) U SSSS OU Close SSS(S) C SSS(S) C CCC(C) U SSSS CU Test
Ademco Contact ID® Reporting takes the following format: CCCC Q EEE GG ZZZ where: CCCC = Customer (subscriber) ID Q = Event qualifier, where: E = new event , and R = restore EEE = Event code (3 hexadecimal digits) Note: For a complete list of event codes, refer to the central office receiver manual. GG = Partition Number (system messages show “00”) ZZZ = Zone/contact ID number reporting the alarm, or user number for open/close reports. System status messages (AC Loss, Walk Test, etc.
11-4
S E C T I O N 1 2 System Operation • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Security Codes The VISTA-20P system supports up to 48 security codes (VISTA-15P supports 32 codes), which can each be assigned one of 5 authority levels. The authority level determines the functions each code can perform as follows: Authority Levels (authority levels can be assigned to users 3-49 only; users 1 and 2 cannot be changed) Level Installer User No.
Installation Instructions Keypad Functions The following is a brief list of system commands. For detailed information concerning system functions, refer to the User's Manual. Voice Keypads The 6150V/6160V Voice Keypads provide the following features: • Message Center, which lets the user record and playback one message. • Voice Status, which can announce system status by using the STATUS key. • Voice Chime, which can alert users to the opening of doors/windows while the system is disarmed.
Panic Keys There are three Panic keys (A, B, and C) that, if programmed, can be used to manually initiate alarms and send a report to the central station. Each key can be programmed for 24-hour Silent, 24-hour Audible, Fire, or Personal Emergency responses. The programmed Panic response is activated when the appropriate key is pressed for at least 2 seconds.
Installation Instructions Various System Trouble Displays Alpha Display Fixed Disp. Meaning CANCELED ALARM CA will appear if an exit or interior zone contained a fault during closing at the time the Exit Delay ended (e.g., exit door left open), but the system was disarmed during the Entry Delay time. The alarm sounder and keypad sound continuously, but stop when the system is disarmed. No message will be transmitted to the central station.
S E C T I O N 1 3 Testing the System • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Test Procedures After the installation is complete, you should perform the following tests: System Test: Checks that all zones have been installed properly and the system properly responds to faults. Dialer Test: Checks that the phone connection to the central station is working properly. Go/No Go Test: Checks that transmissions can be received from transmitters.
Installation Instructions Checking Transmitter Enrollment (Sniffer Mode) Use this mode to verify that all transmitters have been properly programmed. Make sure both partitions are disarmed before trying to enter this mode, since this is a system-wide command. 1. Press [Installer code] + [#] + 3. Note: If the communicator is in the process of sending a report to the central station, the system will not go into the Sniffer mode. If so, wait a few minutes, and try again.
Dialer Communication Test and Periodic Test Reports 1. Enter Installer Code + 5 [TEST], then press “1” at the prompt to start the Dialer Test. 1=DIAL, 0=WALK The following will be displayed (accompanied by 2 beeps) if test is successful: PHONE OKAY (“Cd” displayed on Fixed-Word Display Keypads) A Contact ID report will also be sent (code 601) If the dialer test is unsuccessful, the following is displayed: COMM FAILURE (“FC” displayed on Fixed-Word Display Keypads) 2.
Installation Instructions 13-4
S E C T I O N 1 4 Specifications & Accessories • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • SECURITY CONTROL 1. Physical: 12-1/2” W x 14-1/2” H x 3” D (318mm x 368mm x 76mm) 2. Electrical: VOLTAGE INPUT: 16.5VAC from plug-in 25VA transformer, Ademco No. 1321 (in U.S.A.) RECHARGEABLE BACKUP BATTERY: 12VDC, 4AH (sealed lead acid type). Charging Voltage: 13.8VDC. ALARM SOUNDER: 12V, 2.
Installation Instructions 2-Wire Smoke Detector: Detector Type Photoelectric w/heat sensor, direct wire Photoelectric, direct wire Photoelectric w/heat sensor, direct wire Photoelectric Photoelectric w/heat sensor Ionization, direct wire Ionization Photoelectric duct detector Ionization duct detector Low-profile, Photoelectric, w/135°F thermal Low-profile, Ionization type, direct wire 14-2 System Sensor Model No.
5800 Series Transmitter Input Loop Identification All of the transmitters illustrated below have one or more unique factory assigned input (loop) ID codes. Each of the input loops requires its own programming zone (e.g., a 5804's four inputs require four programming zones). LOOP 3 LOOP 2 LOOP 1 (REED) (PRIMARY) LOOP 2 LOOP 1 (TERMINALS) LOOP 1 LOOP 4 YOU MUST ENROLL THIS BUTTON 5801 ENROLL AS "UR" OR "RF" 3 (AUX.
Installation Instructions Compatible 5800 Series Transmitters Table (continued) Model 5817 Product Multi-Point Universal Transmitter 5818 Recessed Transmitter 5819 Shock Processor Transmitter RF 5819WHS 5819BRS Shock Processor Transmitter RF 5827 Wireless Keypad Uses House ID only 5827BD Wireless Two-Way Keypad Uses House ID only 5849 Glassbreak Detector RF 5890 PR Detector RF 5899 Magnets 14-4 Input Type RF RF Description Has three unique input (loop) codes: one for a “Primary” c
S E C T I O N 1 5 Regulatory Agency Statements • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • RADIO FREQUENCY EMISSIONS Federal Communications Commission (FCC) Part 15 This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Installation Instructions UL NOTICES 1. Entry Delay No. 1 and No. 2 (fields ✱35, ✱36) cannot be greater than 30 seconds for UL Residential Burglar Alarm installations, and entry delay plus dial delay should not exceed 1 minute. For UL Commercial Burglar Alarm installations, total entry delay may not exceed 45 seconds. 2. For UL Commercial Burglar Alarm (Grade AA) and UL Residential Burglar Alarm installations with line security, total exit delay time must not exceed 60 seconds.
S E C T I O N 1 6 Limitations and Warranty • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • WARNING THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced design security system, it does not offer guaranteed protection against burglary, fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a variety of reasons.
Installation Instructions WARNING THE LIMITATIONS OF THIS ALARM SYSTEM (Continued) The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate maintenance. This alarm system should be tested weekly to make sure all sensors and transmitters are working properly. The security keypad (and remote keypad) should be tested as well. Wireless transmitters (used in some systems) are designed to provide long battery life under normal operating conditions.
– INDEX – 1 B F 1321 AC Transformer....... 1-2, 2-4, 2-11 1321X10.................. 1-2, 2-4, 2-11, 14-2 15-Second Dialer Delay (Burglary) ... 4-3 Backup Battery............................. iii, 1-2 Battery Life....................................... 2-9 Battery Tests......................... 13-1, 13-3 Bell Supervision ............................... 2-4 Bell Supervision Jumper................... 2-4 Bypassing Zones............................ 12-2 Factory Defaults ...............................
Installation Instructions P S W PABX Access Code ......................... 4-2 Pager 1 Phone No..................... 4-8, 4-9 Pager Format ................................... 4-8 Pager Programming ................. 3-2, 4-8 Pager Programming Fields.............. 4-8 Pager Report Options ...................... 4-8 Panic Keys..................................... 12-3 Partitions.................................. 1-1, 3-1 Perimeter Burglary ........................... 3-3 Phone Line.........................
CONNECTION OF THE FIRE ALARM SIGNAL TO A FIRE ALARM HEADQUARTERS OR A CENTRAL STATION SHALL BE PERMITTED ONLY WITH THE PERMISSION OF THE LOCAL AUTHORITY HAVING JURISDICTION. THE BURGLAR ALARM SIGNAL SHALL NOT BE CONNECTED TO A POLICE EMERGENCY NUMBER. THIS EQUIPMENT SHOULD BE INSTALLED IN ACCORDANCE WITH THE NATIONAL FIRE PROTECTION ASSOCIATION'S STANDARD 72, CHAPTER 2 (NATIONAL FIRE PROTECTION ASSOCIATION, BATTERY-MARCH PARK, QUINCY,MA 02269).
ADEMCO LIMITED WARRANTY Alarm Device Manufacturing Company, a Division of Pittway Corporation, and its divisions, subsidiaries and affiliates ("Seller"), 165 Eileen Way, Syosset, New York 11791, warrants its products to be in conformance with its own plans and specifications and to be free from defects in materials and workmanship under normal use and service for 24 months from the date stamp control on the product or, for products not having an Ademco date stamp, for 12 months from date of original purchas