9,67$ 6( 6HFXULW\ 6\VWHP ,QVWDOODWLRQ DQG 6HWXS *XLGH * ARMED READY OFF ON OFF 1 MAX AWAY STAY 2 3 TEST BYPASS 4 5 6 INSTANT CODE CHIME 7 8 9 0 # READY * PANIC ® N7227V6 7/01
RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide Proper Coverage for the Protected Premises. Recommendations for Smoke and Heat Detectors With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted below.
Table of Contents • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Conventions Used In This Manual .........................................................................................vi Section 1 Introduction.......................................................................................................1–1 Features ..................................................................................................................................
VISTA-10SE Installation and Setup Guide Section 8 Alpha Descriptor Programming (✱ 82 Menu Mode)........................................8-1 About Alpha Descriptor Programming............................................................................................................8-1 Programming Zone Descriptors .......................................................................................................................8-1 Adding Custom Words.....................................................
List of Figures • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Figure 2-1 Figure 2-2 Figure 2-3 Figure 2-4 Figure 2-5 Figure 2-6 Figure 2-7 Figure 2-8 Figure 2-9 Figure 2-10 Figure 2-11 Figure 2-12 Figure 2-13 Figure 2-14 Figure 5-1 Figure 5-2 Figure 5-3 Installing the Cabinet Lock ...............................................................................................................2-1 Mounting the PC Board .......................................
Conventions Used In This Manual • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Before you begin using this manual, it is important that you understand the meaning of the following symbols: UL A UL note that includes specific information that must be followed if you are installing this system in a UL Listed application.
S E C T I O N 1 Introduction • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • The VISTA–10SE is a control that supports up to 22 hardwired and wireless zones, plus remote keypads. Features Basic Hardwired Zones Provides 6 basic hardwired zones having the following characteristics: • Zones 1-6 response time is 300–500 milliseconds. • Zone 3 programmable fast response time is 10–15 milliseconds. • EOLR supervision supporting N.O. or N.C.
VISTA-10SE Installation and Setup Guide Optional VIP Module • Supports the ADEMCO 4285/4286 VIP Module. • Provides access to the system via on-premises or offpremises phones for arming, disarming, etc., plus control of relay outputs. Optional Long-Range Radio Allows all messages that have been programmed to go to the primary telephone number to be reported additionally to a 7720 PLUS, 7820 or 7835C radio.
S E C T I O N 2 Installing the Control & Peripherals • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Notes: Use an ADEMCO No. N4445 Lock. The cabinet can be closed and secured without a lock by using 2 screws in the cover's edge. CHECK POSITION LOCKED 1. Mount the control cabinet to a sturdy wall in a clean, dry area that is not readily accessible to the general public using fasteners or anchors (not supplied), in the four cabinet mounting holes. 2.
VISTA-10SE Installation and Setup Guide Mounting Control with RF Receiver 7. Insert both grounding lugs (supplied with the receiver) through the top of the cabinet into the lefthand terminals of the antenna blocks (located at the upper edge of the receiver board), and secure them to the cabinet with the screws provided, as shown in Detail B. 8. Insert the receiver's antennas through the top of the cabinet, into the blocks' right-hand terminals, and tighten the screws.
Section 2 – Installing the Control & Peripherals Mounting the Keypads Wiring the Keypads 1. Make sure addressable-type keypads (6128, 6137, 6138, and 6139) are set to non-addressable mode (address 31), which is the factory default setting. Refer to the instructions provided with the keypad for address setting procedure. 1. Determine wire gauge by referring to the wiring length/gauge chart on the next page. 2. Mount the keypads at a height that is convenient for the user.
VISTA-10SE Installation and Setup Guide SUPPLEMENTARY POWER SUPPLY CONTROL TERMINAL STRIP – AUX. AUX. DATA DATA – + IN OUT 7 TO KEYPAD YEL WIRE 6 TO KEYPAD GRN WIRE IMPORTANT: MAKE THESE CONNECTIONS DIRECTLY TO SCREW TERMINALS AS SHOWN. 5 TO KEYPAD BLK WIRE TO KEYPAD GRN WIRE TO KEYPAD YEL WIRE TO KEYPAD BLK WIRE TO KEYPAD RED WIRE 4 TO KEYPAD RED WIRE + supp_pwr_supply-V0 Figure 2-5. Using a Supplementary Power Supply for Keypads Sounder (Bell) Connections 1. _ 4 ALARM OUTPUT NO.
Section 2 - Installing the Control & Peripherals 2. After approximately 1 minute, the initial displays revert to DISARMED...READY TO ARM for alpha keypads, or READY for fixed-word keypads (if there are no faulted zones). This 1-minute delay allows PIRs, etc. to stabilize. AC Powerup To turn on AC power, perform the following steps: 1. Plug the 1321/1321CN into a 24-hour, unswitched 120VAC outlet.
VISTA-10SE Installation and Setup Guide AC Power Outlet Ground: Available from 3-prong, 120VAC, power outlets only. To test the integrity of the ground terminal, use a threewire circuit tester with neon lamp indicators, such as the UL-Listed Ideal Model 61–035, or equivalent, available at most electrical supply stores.
Section 2 – Installing the Control & Peripherals The RF receiver must be at least 10 feet from any remote keypad to avoid interference from the microprocessors in those units. Installation and Setup of the 5881/5882 Receiver Installing the 5881/5882 Receiver RF System Installation Advisories Follow the guidelines below when installing the RF receiver. (Disregard if the receiver is mounted in the control cabinet.
VISTA-10SE Installation and Setup Guide Installing the 5800TM Module Installation of this module is necessary only if you are using one or more 5827BD Wireless Bi-directional keypads, or 5804BD Transmitters (wireless keys). Do not cut any of the jumpers on the 5800TM when using it with the VISTA-10SE. For additional information, refer to the 5800TM’s instructions. Mounting the 5800TM Module The 5800TM must be located near the RF receiver (between one and two feet away from the receiver’s antennas).
Section 2 – Installing the Control & Peripherals 4204 4 TYPICAL (SHOWN "OFF") RELAY 3 COVER TAMPER (REED) SWITCH 4-PIN KEYPAD PLUG RELAY 2 EITHER OR BOTH CAN BE USED 14 15 C NC NO C NC BLK GRN RED NO NO C 1 NC 16 YEL NC RELAY TB1 13 C 1 Using the Transmitter Sniffer Mode The Transmitter Sniffer mode is a procedure that verifies that all transmitters have been properly programmed. To verify programming, refer to SECTION 11: Testing the System.
VISTA-10SE Installation and Setup Guide If no touch tones are produced following access to the security system from on-premises (this problem may arise in rare cases), it may be necessary to reverse the wires connected to terminals 3 and 4 on the Phone module and the wires connected to terminals (17) and (18) on the control. The wiring diagram that follows shows the wiring connections that will provide proper operation in most cases.
INCOMING TELECOM LINE HANDSET 17 18 19 20 GROUND Section 2 – Installing the Control & Peripherals 21 RING PLUG INCOMING TELECOM LINE TIP RED (RING) GREEN (TIP) EARTH GROUND GREY (RING) BROWN (TIP) TERMINALS ON CONTROL TIP RJ31X JACK RING DIRECT CONNECT CORD PREMISES PHONES V10SE-024-V0 Figure 2-12.
VISTA-10SE Installation and Setup Guide EARTH GROUND CONTROL EAGLE SUPPLIED CABLE 4 17 18 19 20 21 5 RED (R) GREEN (T) GREY (R) BROWN (T) ➤ ➤ RJ31X CONTROL/ DIALER HEADER RED ON 123456 13 V+ 14 15 GND 16 BROWN 4204 RELAY 1 SHOWN OFF TO PREMISES HANDSET YELLOW DIP Switch INCOMING PHONE LINE NO NC C •• •• • NOTE: REFER TO AAV MODULE INSTRUCTIONS FOR CONNECTIONS TO AUDIO SPEAKERS AND MICROPHONE. EAGLE 1250 TIP RING AAV_conn-V0 Figure 2-13.
S E C T I O N 3 Programming Overview • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Programming You can program the system at any time, even at the installer's premises prior to the actual installation. Programming can also be performed remotely from the installer’s office/home, using an IBM personal computer, a modem, and Compass downloading software.
VISTA-10SE Installation and Setup Guide Type 05 Trouble by Day/ Alarm by Night Type 06 24-hour Silent Alarm Zone type 05 is usually assigned to a zone that contains foil-protected doors or windows; or covers a sensitive area (e.g., stock room, drug supply room, etc.) It can also be used on a sensor or contact in an area where immediate notification of an entry is desired. • Provides an instant alarm when armed in AWAY, STAY, INSTANT, or MAXIMUM (night) mode.
Section 3 – Programming Overview Mechanics of Programming To program the system from a keypad: • You must use a 2-line Alpha display keypad. • The panel must be disarmed. Data Field Programming Procedures Task Procedure Enter Program Mode A) Press both [✱] and [#] at the same time within 50 seconds after power is applied to the control, OR B) After power-up, enter [Installer code (4-1-1-1)] + 8 + 0.
VISTA-10SE Installation and Setup Guide 3-4
S E C T I O N 4 Data Field Programming • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Data Field Programming The following pages list this control’s data fields in numerical order. Field numbers are listed in the left column, followed by a “Title and Data Entries column, which lists the valid entries for each field. Experienced installers can simply follow this column when programming the data fields.
VISTA-10SE Installation and Setup Guide FIELD ✱27 TITLE and DATA ENTRIES EXPLANATION Output To Long-Range Radio 0 = not used 1 = using Long Range Radio output If selected, all messages programmed to go to the primary telephone line receiver will also be sent to the connected 7720PLUS, 7820, or 7835 Radio (sent in Contact ID® format). The data line is supervised as well as certain functions in the radio.
Section 4 - Data Field Programming FIELD TITLE and DATA ENTRIES EXPLANATION Secondary Phone No. Enter up to 12 digits. Do not fill unused spaces. 0–9, # + 11 for ‘✱’, # + 12 for ‘#’, # + 13 for a pause (2 seconds) If you enter fewer than 12 digits, exit by pressing [✱] and next field number (e.g., 43). To clear entries from field, press ✱42✱. See NOTE if field ✱41 also. ✱43 Subscriber Account No. Enter digits 0–9; # + 11 for B; # + 12 for C; # + 13 for D; # + 14 for E; or # + 15 for F.
VISTA-10SE Installation and Setup Guide Example 2. Pager displays: 1 2 3 4 – 0 0 1 – 0 0 5 This indicates that Subscriber No. 1234’s system is reporting an opening (001) by User 5 (005). Note that no Restore Reports are sent to the pager. Important: AAV should not be used when Paging or Alarm Reports are being sent to a secondary number.
Section 4 - Data Field Programming With ADEMCO Contact ID® Reporting: Enter any digit (other than 0) in the first box, to enable zone to report This is an "enabling" code only and is disregarded in the actual reporting to the central office. Entries in the second boxes will be ignored. A 0 (not # + 10) in the first box will disable the report.
VISTA-10SE Installation and Setup Guide If an exit or interior zone contains a fault as the exit delay ends, the local bell and keypad sound continuously. a) If the subscriber then disarms the system before the ensuing ENTRY delay ends, no message is transmitted to the central station, but a zone indication and "Canceled Alarm" or "CA" is displayed on the keypad.
Section 4 - Data Field Programming FIELD TITLE and DATA ENTRIES EXPLANATION ✱74 Low Bat Restore Report Code 0 = no report For both digits: 1-9, A-F (Refer to table on previous page for method of programming report codes.) This is a 2-digit entry field. This is sent when a system low battery condition is restored to normal. ✱75 RF Xmtr. Low battery Restore Code 0 = no report For both digits: 1-9, A-F (Refer to table on previous page for method of programming report codes.
VISTA-10SE Installation and Setup Guide If Priority (✱93, 2nd entry) is… And message is… Then… Primary Phone No. ("0" entered) Acknowledged before delay expires Message is removed from queue and no message is sent to LRR. Not acknowledged before delay expires Message is sent to both the Primary Phone Number and LRR.
Section 4 - Data Field Programming FIELD TITLE and DATA ENTRIES EXPLANATION ✱96 Initialize Download ID and Subscriber Account Number For Downloading Press ✱96 No data entry required. ✱97 SET ALL PROGRAM FIELDS TO DEFAULT VALUES (No data entry required; pressing ✱97 automatically loads all ADEMCO defaults). Do not use if previously programmed with other values. TO EXIT PROGRAMMING MODE (✱98 or ✱99) ✱98 EXITS PROGRAMMING MODE Prevents reentry by: INSTALLER Code + 8 + 0.
VISTA-10SE Installation and Setup Guide 4-10
S E C T I O N 5 Zone Programming (✱56 and ✱58 Menu Mode) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Zone Programming Programming Wireless Zones 5800 Series transmitters have built-in serial numbers that must be enrolled into the system using the ✱56 or ✱58 programming modes in this section, or input to the control via the downloader. Some transmitters, such as the 5816 and 5817, can support more than one “zone” (referred to as loops or inputs).
VISTA-10SE Installation and Setup Guide PROMPT È Zone Number 10 Zone Type Perimeter Zone Type 03 Ç VALID ENTRIES EXPLANATION Zone Type (ZT) Enter the Zone Type response (or change it, if necessary). Each zone must be assigned to a zone type, which defines the way in which the system responds to faults in that zone. Enter the Zone Type code (or change it, if necessary). Zone types are listed below. NOTE: If you enter 00, Delete Zone ? is displayed.
Section 5 - Zone Programming PROMPT 10 INPUT S/N A022-4064 L ? VALID ENTRIES EXPLANATION Loop Number Entry NOTE: If you use the [C] key to copy the previously enrolled serial number, the cursor moves to the Loop column (L) with the serial number displayed, and displays a question mark ‘?” for the loop number. [✱] to accept and continue Enter the loop number and press [✱].
VISTA-10SE Installation and Setup Guide 5800 Series Transmitter Input Loop Identification All the transmitters illustrated on this page have one or more unique factory-assigned input (loop) ID codes. Each of the input loops requires its own programming zone (e.g., a 5804's four input loops require four programming zones). LOOP 3 LOOP 2 LOOP 1 (REED) (PRIMARY) LOOP 2 LOOP 1 (TERMINALS) LOOP 1 LOOP 4 YOU MUST ENROLL THIS BUTTON 2 (AUX. CENTER) 3 LOOP 1 5802MN ENROLL AS "UR" OR "RF" (AUX.
Section 5 - Zone Programming ✱58 Expert Programming Mode Procedures This method is designed for use by installers with previous experience in programming control panels. Zone Programming involves: 1. Entering the programming mode by pressing ✱20 2. Pressing ✱22 (RF System) to enable reception of 5800 series transmitters 3. Pressing ✱58 to start expert mode zone programming 4. Making appropriate entries at the prompts 5. Confirming the serial number of wireless transmitter zones.
VISTA-10SE Installation and Setup Guide PROMPT VALID ENTRIES EXPLANATION XMIT TO CONFIRM Confirm PRESS ✱ TO SKIP [✱] to continue The prompt to confirm appears. This prompt will only appear if the first prompt after entering ✱58 was answered “Yes.” To confirm, activate the loop input or button that corresponds to this zone. The system checks for duplicate.
Section 5 - Zone Programming PROMPT VALID ENTRIES EXPLANATION 10 Zone Type Zone Disabled 00 Zone Type 4. Enter 00. This sets the zone type to Zone Disabled. The prompt at left appears confirming 00 entry in previous step. Delete Zone? 0 = No, 1 = Yes Delete Zone 0 [✱] to continue 0 = no (see explanation) 1 = yes (see explanation) 5. The prompt at left asks if you want to delete the zone.
VISTA-10SE Installation and Setup Guide NOTE: Be sure to remove one of the serial number labels from the new transmitter and affix it over the old serial number label in the ENROLLED TRANSMITTERS worksheet in the Programming Form.
Section 5 - Zone Programming PROMPT Keyd A022-4063 – Rcvd A022-4064 3 VALID ENTRIES EXPLANATION Not Confirmed If the serial number transmitted does not match the serial number entered, a display similar to the one at left appears. If it doesn't match, press any button on the transmitter once again. If a match is not obtained, press the [#] key and then enter the correct serial number (steps 7 through 10 above).
VISTA-10SE Installation and Setup Guide 5–10
S E C T I O N 6 Output Device Programming (✱80 Menu Mode) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Output Device Programming This system supports up to four relays (devices) when a 4204 relay module is connected. The following explanations will help you understand the programming of output devices when using ✱80 (this section) and ✱81 (SECTION 7: Zone Lists that follows).
VISTA-10SE Installation and Setup Guide STOP (STP) The "STOP" programming determines when and under what conditions the relay will be de-activated. The following options are available: 1. RESTORE ZONE LIST (ZL). If a "ZONE LIST" is used as the “Stop” event, the relay will de-activate when all the zones in that list restore from a previous fault, trouble, or alarm condition.
Section 6 - Output Device Programming PROMPT VALID ENTRIES EXPLANATION Enter Relay No. Upon pressing ✱80, this screen will appear. Enter the Relay Number 01, 02, 03, or 04 for a 4204 (or 00 to end these entries). Output Device Displays Enter Relay No. (00 = Quit) 01 The [✱] key is used to accept an entry and advance to the next prompt. The [#] key is used to revert back to the last question to check or change an entry. Press [✱] to go forward again.
VISTA-10SE Installation and Setup Guide PROMPT 02 Stop: No List Zn List 0 02 Stop: Not Used Zn Typ 00 VALID ENTRIES EXPLANATION STOP by Zone List If a zone list will be used to STOP, or restore, the relay action, enter the zone list (ZL) number 1, 2, or 3 (to be programmed in ✱81 mode). If not used, enter 0.
S E C T I O N 7 Zone Lists (✱81 Menu Mode) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Zone Lists Zone lists let you group individual zones for use with certain system actions. This interactive menu mode is used to program zone lists for output devices previously programmed in ✱80. Refer to the Programming Form worksheet (✱81) that programs the Zone Lists for Output Relays.
VISTA-10SE Installation and Setup Guide Notes: • Any list may include any or all of the system's zone numbers. • A zone list can be assigned to more than one output relay. • If you only want to review what has been programmed previously, press #81. The review can be advanced by using the ✱ key. When finished, press 00✱ to quit. No programmed values can be changed in this mode. When programming in ✱80 and ✱81 Interactive modes is completed, exit the programming mode by pressing ✱99.
S E C T I O N 8 Alpha Descriptor Programming (✱82 Menu Mode) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Alpha Descriptor Programming This Interactive mode section provides instructions for programming alpha descriptors and for adding custom words. This is recommended for systems using alpha keypads, and necessary if a 4285/4286 VIP Module is used. Alpha descriptors cannot be displayed on fixed-word keypads.
VISTA-10SE Installation and Setup Guide PROMPT PROCEDURE Default Descriptor ↓ ✱ZN 01 ZONE 01 If a descriptor was not entered previously for zone 01, the default descriptor for zone 01 will be displayed. Note that no entries can be made. Entries can be made only when the display contains a flashing cursor, which signifies the “entry mode.” Flashing Cursor (system is ready for entry of word). ↓ ✱ZN 01 6.
Section 8 – Alpha Descriptor Programming PROMPT PROCEDURE Program Alpha? 0 = No, 1 = Yes 0 14. Enter ✱00. The “Program Alpha?” prompt at left appears. Press 0 (No). The Alpha Pgm prompt appears. Press [✱] to continue 15. Press [✱] to continue exiting and to program another field. Alpha Pgm 82 16. Enter ✱99 to exit the Programming mode. Adding Custom Words You can add up to five installer-defined words to the built-in vocabulary.
VISTA-10SE Installation and Setup Guide ALPHA VOCABULARY LIST (For Entering Zone Descriptors) NOTE: Some rarely used words appearing in previously published lists have been deleted from the list below. Use only this list for 000 • 001 • 002 004 005 • 006 • 007 • 009 010 • • • • • • • 012 013 014 016 017 018 019 020 • 021 • 022 023 025 • 026 028 • 029 030 031 033 034 035 036 • 037 038 • 040 • 046 047 • 048 049 • 050 051 • 052 • 053 054 selecting zone descriptors.
S E C T I O N 9 System Communication • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Panel Communication with Central Station This section provides an explanation of formats this system accommodates for reporting alarms and other system conditions to the central station.
VISTA-10SE Installation and Setup Guide The following table lists codes for reports sent in different formats: Type of Report Alarm Code for 3+1/4+1 Standard SSS(S) A Code for 3+1/4+1 Expanded Trouble SSS(S) T SSS(S) B TTT(T) t SSSS Tt Bypass SSS(S) B SSS(S) B BBB(B) b SSSS Bb AC Loss SSS(S) E SSS(S) E EEE(E) AC SSSS EAC Low Bat SSS(S) L SSS(S) L LLL(L) LB SSSS LLB Open SSS(S) O SSS(S) O OOO(O) U SSSS OU Close SSS(S) C SSS(S) C CCC(C) U SSSS CU Test SSS(S) G SSS(S) G GGG(G)g S
Section 9 – System Communication ADEMCO Contact ID® Reporting takes the following format: CCCC Q EEE GG ZZZ where: CCCC = Customer (subscriber) ID Q = Event qualifier, where: E = new event , and R = restore EEE = Event code (3 hexadecimal digits) NOTE: For a complete list of event codes, refer to the central office receiver manual. GG = Always 00. ZZZ = Zone/Contact ID® number reporting the alarm, or user number for open/close reports. System status messages (AC Loss, Walk Test, etc.
VISTA-10SE Installation and Setup Guide 9-4
S E C T I O N 1 0 System Operation • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Security Codes The system supports up to seven security codes; Installer, Master, four secondary user, and Duress, described as follows: Code Description of Code Function and Programming The factory default Installer Code is "4-1-1-1", but may be changed in field ✱20. The Installer code cannot be used to disarm the security system if it was not used to arm the system.
VISTA-10SE Installation and Setup Guide Panic Keys There are three individual panic keys and/or, on some keypads, panic key pairs. If programmed, they can be used to manually initiate alarms and send a report to the central station. Each key (or key pair) can be individually programmed for 24-hour Silent, Audible, Personal, or Fire Emergency responses.
S E C T I O N 1 1 Testing the System • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Local Tests After the security system installation is complete, test the system as follows: 1. 2. 3. 4. 5. 6. With the system in the disarmed state, check that all zones are intact. If a NOT READY message is displayed, press the [✱] key to display the faulted zone(s). Restore faulted zone(s) if necessary, so that the READY message is displayed.
VISTA-10SE Installation and Setup Guide Go/No Go Test Mode By keying Installer code + [#] + [4], a mode similar to the test mode is entered, but the wireless receiver gain is reduced. Checking in this mode not only assists in determining good mounting locations for the transmitters when the system is being installed, but also verifies that the RF transmission has sufficient signal amplitude margin for the installed system. 1. Enter the Installer code + [#] + [4]. 2.
Section 11 – Testing the System Other Displays (fixed-word keypad displays are in parentheses) Busy-Standby (dI). If this remains displayed for more than 1 minute, the system is disabled. Modem Comm (CC) The system is in communication with the central station for change of function or status verification. Comm. Failure (FC) A communication failure has occurred. Open Circuit (OC) The keypad is not receiving signals from the control and sees an open circuit.
VISTA-10SE Installation and Setup Guide Troubleshooting Guide (continued) SYSTEM (including Wireless) SYMPTOM 1. 2. 3. 4. 5. 11-4 Transmitter signal not received at 5881 Receiver Transmitter zone number appears during Transmitter Sniffer test but does not clear. Low Battery message on keypad Periodic beep(s) from keypad. With 5800 system, no response to a transmitter in normal operation, although zone number clears during Transmitter Sniffer test. POSSIBLE CAUSE REMEDY 1a.
Section 11 – Testing the System Troubleshooting Guide (continued) SYSTEM (including Wireless) SYMPTOM 6. 7. 8. 9. Nuisance or phantom alarm. Intrusion alarm for no apparent reason. Repeated low battery signal. Local bell and keypad sound continuously after arming. 10. Continuous beeping at the keypad, accompanied by a display of Bell Failure on alpha keypads, or CHECK 70 on Fixed-Word keypads. POSSIBLE CAUSE REMEDY 5b.
VISTA-10SE Installation and Setup Guide 11-6
S E C T I O N 1 2 Remote Programming and Control (Downloading) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Remote Programming The VISTA–10SE can be remotely programmed from an IBM compatible Personal Computer (PC), a modem, and ADEMCO’s Compass Windows downloading software. Programming the control from a remote location is protected against compromise by someone attempting to defeat the system, using multi-levels of security protection: 1.
VISTA-10SE Installation and Setup Guide 12-2
S E C T I O N 1 3 Specifications and Accessories • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • VISTA-10SE Security Control 1. Physical: 12-1/2" W x 14-1/2" H x 3" D (318mm x 368mm x 76mm) 2. Electrical: VOLTAGE INPUT: 16.5VAC from plug-in 25VA transformer, ADEMCO No. 1321 RECHARGEABLE BACKUP BATTERY: 12VDC, 4AH-17.2AH (Sealed Lead Acid).
VISTA-10SE Installation and Setup Guide Specifications and Accessories (continued) Compatible Devices 6127 REMOTE KEYPAD 1. Physical: 5-3/4" W x 4-3/4" H x 1" D (146mm x 121mm x 26mm). 2. Electrical: Voltage Input: 12VDC; Current Drain: 20mA. 3. Interface Wiring: To control panel's keypad connection points. RED: +12VDC input aux power GREEN: Data Out to Control YELLOW: Data In from Control BLACK: Ground 6128 REMOTE KEYPAD 1. Physical: 5-3/4" W x 4-3/4" H x 1" D (146mm x 121mm x 26mm). 2.
Section 13 - Specifications and Accessories Specifications and Accessories (continued) 4285 and 4286 VIP Modules 1. Physical: 6-1/2" W x 4-1/4" H x 1-1/4" D (169mm x 108mm x 32mm). 2. Electrical: Voltage Input: 12VDC; 4285 Current Drain: 160mA 4286 Current Drain: 300mA. 3. Device Address: Permanently set to address 4. 4. Interface Wiring: See 4285/4286 VIP MODULE paragraph in . 5. Telephone Line Connections: See 4285/4286 VIP MODULE paragraph in SECTION 2. Long Range Radios – 7720/7820 PLUS/7835C 1.
VISTA-10SE Installation and Setup Guide Specifications and Accessories (continued) Compatible Sounders (continued) ADEMCO 745X3 Voice Siren Driver 12-volt voice siren driver with English, Spanish, and French voice messages. Separate messages for fire and burglary. Use with 8-ohm speaker. UL Listed. 1100mA current drain. NOTE: Requires special power wiring, using additional components. ADEMCO 705–820, 5-inch Round Speaker 20-watt, 8-ohm indoor or outdoor speaker. Requires a driver.
A P P E N D I X A Regulatory Agency Statements • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • FEDERAL COMMUNICATIONS COMMISSION (FCC) PART 15 STATEMENT This equipment has been tested to FCC requirements and has been found acceptable for use.
VISTA-10SE Installation and Setup Guide UL NOTICES 1. This is a "Grade A" residential system. 2. The 4285/4286 VIP Module and 7720PLUS, 7820, or 7835C Long-Range Radios are not approved for use in UL installations. 3. The Entry Delay (field ✱38) cannot be greater than 45 seconds for UL installations. 4. The maximum number of reports per armed period (field ✱92) must be unlimited (set to 1) for UL installations. 5. Periodic testing (field ✱49) must be at least every 24 hours (set to 1) for UL installations.
A P P E N D I X B Limitations and Warranties • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • WARNING THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced design security system, it does not offer guaranteed protection against burglary, fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a variety of reasons. For example: • Intrusion detectors (e.g.
VISTA-10SE Installation and Setup Guide ADEMCO LIMITED WARRANTY Alarm Device Manufacturing Company, a Division of Pittway Corporation, and its divisions, subsidiaries and affiliates (“Seller”), 165 Eileen Way, Syosset, New York 11791, warrants its products to be in conformance with its own plans and specifications and to be free from defects in materials and workmanship under normal use and service for 24 months from the date stamp control on the product or, for products not having an ADEMCO date stamp, for
INDEX • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • 24-hour Audible Alarm................................................... 3-2 24-hour Auxiliary Alarm ................................................. 3-2 24-hour Silent Alarm...................................................... 3-2 4204 relay module........................................................ 6–2 487-12 Regulated Supply ..............................................
Index Limited Warranty ........................................................... B-2 Local Tests .................................................................. 11-1 Lock............................................................................... 2-1 Long-Range Radio ............................................... 1-2, 2-11 Loop ............................................................................. 5–1 Low Bat Message........................................................ 11-2 LRR ..........
+ – ALARM OUTPUT 10.5-13.8VDC, 2A MAX. (600mA MAX. FOR UL USAGE, INCLUDING AUX. POWER) STEADY FOR BURGLARY/PANIC, TEMPORAL SOUNDING FOR FIRE (e.g. USE ADEMCO 740 SOUNDER, 702 OR 719 SIREN, OR 12V BELL) CONNECTION OF THE FIRE ALARM SIGNAL TO A FIRE ALARM HEADQUARTERS OR A CENTRAL STATION SHALL BE PERMITTED ONLY WITH THE PERMISSION OF THE LOCAL AUTHORITY HAVING JURISDICTION. THE BURGLAR ALARM SIGNAL SHALL NOT BE CONNECTED TO A POLICE EMERGENCY NUMBER.
165 Eileen Way, Syosset, New York 11791 Copyright © 2001 PITTWAY CORPORATION ¬1 9 ^l N7227V6 7/01