ADEMCO VISTA-10P ADEMCO VISTA-10PSIA Security Systems Installation and Setup Guide K0735V3 10/04 Rev.
RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide Proper Coverage for the Protected Premises. Recommendations For Smoke And Heat Detectors With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted below.
Table Of Contents • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Features and Installation Highlights ...............................................................................................1-1 Capabilities .............................................................................................................................................1-1 Functions.........................................................................................................................
Table Of Contents • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Menu Mode Programming...................................................................................................................5-1 Zone Programming Overview (∗56 and ∗58 Menu Modes)................................................................5-1 ∗56 Zone Programming Procedure......................................................................................................
S E C T I O N 1 Features and Installation Highlights • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • SIA Installations: The VISTA-10PSIA is a certified SIA-compliant control that meets SIA specifications for False Alarm Reduction. The VISTA-10P is not certified as SIA compliant, but can be programmed for False Alarm Reduction. To program for False Alarm Reduction, follow the SIA Guidelines noted in the applicable programming fields.
Installation and Setup Guide NOTE: All devices and accessories used in a Canadian installation must be Listed for use in Canada. Important Installation Highlights (Installer Please Read) • This system uses addressable keypads and Relay Modules (see table of addresses in Programming Overview section). • Keypads must be set for addresses 16-23 (first keypad is address 16, which is different from previous controls) and programmed in data fields *190-*196.
S E C T I O N 2 Mounting and Wiring the Control • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Cabinet and Lock 1. Mount the control cabinet to a sturdy wall in a clean, dry area, which is not readily accessible to the general public, using fasteners or anchors (not supplied) with the four cabinet mounting holes. 2. Remove cabinet door, then remove the lock knockout from the door. Insert the key into the lock. 3.
Installation Instructions Mounting Board with RF Receiver 1. a. Remove the receiver board from its case, then insert the top of the board into the slots at the top of the cabinet, as shown in Detail A in Figure 3. Make sure that the board rests on the correct row of tabs. b. Swing the base of the board into the mounting clips and secure it to the cabinet with the accompanying screws. c. Insert the top of the control's board into the slot in the clips and position two clips at the lower edge of the board.
Mounting and Wiring the Control Wiring to Keypads 1. Connect keypads to the keypad terminals as shown on the Summary of Connections diagram. Determine wire size using the Wire Run Chart below. 2. Set keypad addresses. Refer to the address setting instructions included with the keypads and set each keypad device address according to the chart at right. 3. Program the keypad addresses and sound options in data fields *190-*196. IMPORTANT: Each keypad must be assigned a unique address, starting at address 16.
Installation Instructions Sounder (Bell) Connections This control complies with NFPA requirements for temporal pulse sounding of fire notification appliances. Temporal pulse sounding for a fire alarm consists of: 3 pulses – pause – 3 pulses – pause – 3 pulses–etc.. TERMINALS ON CONTROL BOARD 4 _ ALARM OUTPUT TERMINALS EXTERNAL ALARM SOUNDER _ + 3 OBSERVE POLARITY + 2 CUT RED JUMPER ON CONTROL BOARD TO ENABLE BELL (SOUNDER) SUPERVISION.
Mounting and Wiring the Control CALIFORNIA STATE FIRE MARSHALL (CSFM) AND UL RESIDENTIAL FIRE 24-HOUR BATTERY BACKUP REQUIREMENTS The California State Fire Marshal and UL have regulations which require that all residential fire alarm control panels must be provided with a backup battery which has sufficient capacity to operate the panel and its attached peripheral devices for 24 hours in the intended standby condition, followed by at least 4 minutes in the intended fire alarm signaling condition.
Installation Instructions Hardwire Zones Normally Open Zones/ Normally Open EOLR Zones 1. Connect open circuit devices in parallel across the loop; for EOLR zones, connect the EOLR across the loop wires at the last device. 2. Enable normally open/EOLR zones using Zone Programming mode, “Hardwire Type” prompt. Normally Closed Zones/Normally Closed EOLR Zones 1. Connect closed circuit devices in series in the high (+) side of the loop; for EOLR zones, connect the EOLR in series following the last device. 2.
Mounting and Wiring the Control Installing the RF Receiver You can any ADEMCO 5800 Series Wireless Receivers, including: RF Receiver No. of Zones 5881L/5882L up to 8 5881M/5882M up to 16 (transmitter zone numbers = 9-24; button zone numbers = 49-56) 5883, 6150RF up to 16 (transmitter zone numbers = 9-24; button zone numbers = 49-56) 1. Set Device Address to “00” as described in its instructions (set all switches to the right, “off” position). 2.
Installation Instructions Installing the Transmitters 1. To be sure reception of the transmitter's signal at the proposed mounting location is adequate, perform a Go/No Go Test, described in the Testing the System section. 2. Install transmitters in accordance with the instructions provided with each. 3. Set 5827, 5827BD, 5804BD wireless keypads to the programmed House ID (field *24), using its DIP switches (5827) or follow the instructions provided with the device.
Mounting and Wiring the Control 4 5 (GREEN) KEY 3 (RED) 1 OUTPUT 18 If a keyswitch is used on: • an installation that transmits opening and closing signals, the keyswitch zone must be programmed to send opening and closing signals. 5-PIN TRIGGER CONNECTOR +12 AUX. A UL Listed keyswitch is required for fire installations and UL commercial and residential burglar alarm installations.
Installation Instructions On-Board Triggers (BLACK) KEY 5 (GREEN) (RED) 4 GND (-) If on-board triggers are used, the wiring between the control unit and the UL Listed device must be run in conduit, be no more than 3 feet apart and have no intervening barriers or walls. 3 OUTPUT 18 UL 1 +12 AUX. You can use a 4-wire cable as shown.
Mounting and Wiring the Control UL The 4285 and 4286 modules are UL Listed only for use on residential fire and UL residential burglar alarm installations. Phone Module Problems If no touch tones are produced following access to the security system from on-premises (this problem may arise in rare cases), it may be necessary to reverse the wires connected to terminals 3 and 4 on the phone module and the wires connected to terminals (21) & (22) on the control.
Installation Instructions Audio Alarm Verification Connections (AAV, “listen-In”) Refer to the connection diagrams below. One diagram shows connections when a 4285/4286 Phone Module is used, the other shows connections when the 4285/4286 is not used. Connections use one of the on-board triggers.
S E C T I O N 3 Programming Overview • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Programming You can program the system at any time, even at the installer's premises prior to the actual installation. Programming can also be performed remotely from the installer’s office/home, using an IBM personal computer, a modem, and Compass downloading software.
Installation Instructions Wireless Receiver, Transmitters, and Wireless Keys (keyfobs) Receiver: Set the receiver’s address to “00” using its DIP switches, then set the following options: *22 RF Jam Option† *24 RF House ID Code (if using wireless keypads) *67 Transmitter Low Battery Report Code† † These fields must be enabled for Residential Fire, UL Residential Burglar Alarm, and UL *75 Transmitter Low battery restore report code† Commercial Burglar Alarm installations.
Zone Type Definitions You must assign a zone type to each zone, which defines the way in which the system responds to faults in that zone. Zone types are defined below.
Installation Instructions Type 22 Disarm (BR only) • Works as a dynamic monitor of a zone fault/trouble (not alarm). In the case of a short/open, the message, "*ALARM*-24 Hr. Non-Burg. -#XXX " (where XXX is the zone number) will be sent to the Central Station. The system keypad will display a “check” message indicating the appropriate zone (but keypad beeping does not occur). Upon restoral of the zone, the message, "*RESTORE*-24 Hr. Non-Burg. #XXX " will be sent to the Central Station.
Mechanics of Programming Data Field Programming Procedures (You must use a 2-line Alpha display keypad) Task Procedure Entering Program Mode A) Press both [∗] and [#] at the same time within 50 seconds after power is applied to the control, OR B) After power-up, enter [Installer code (4-1-1-2)] + 8 0 0. (method “B” is disabled if you exit the program mode using ∗98) Go to a Data Field Press [∗] + [Field Number] (for example, ∗21).
Installation Instructions Table of Device Addresses This Device RF Receiver Long Range Radio 4286 Voice Module 4204 Relay Module Keypads: keypad 1 keypad 2 keypad 3 keypad 4 keypad 5 keypad 6 keypad 7 keypad 8 5800TM Module Uses Address 00 03 04 12 Reports as†† 100 103 104 112 16 17 18 19 20 21 22 23 28 n/a n/a n/a n/a n/a n/a n/a n/a n/a Enabled By… *56 zone programming: input device type entry automatic if output to long range radio field *29 enabled automatic if phone module access code field *28 en
S E C T I O N 4 Data Field Programming • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Data Field Programming The following pages provide explanations of this control’s data fields and is intended to be used in conjunction with the Programming Guide. Refer to the Programming Guide for the specific option choices for each data field. Use the blank programming form to record the data for this installation.
Installation Instructions Zone Sounds & Timing FIELD TITLE and EXPLANATION *31 Single Alarm Sounding Per Zone Select whether or not the system limits alarm sounding to once per arming period for a given zone. VISTA-10PSIA: If “0” selected, “alarm sounding per zone” will be the same as the “number of reports in armed period” set in field *93 (1 if one report, 2 if 2 reports, unlimited for zones in zone list 7).
Dialer Programming FIELD TITLE and EXPLANATION *40 PABX Access Code Enter the PABX code, if used. To clear entries from field, press ∗40∗. If fewer than 6 digits need to be entered, exit by pressing [∗], which advances to the next field. Call Waiting: If the subscriber’s phone service has “call waiting” (and is not using PABX), enter “*70” (“# + 11”) plus “# + 13” (pause) as the PABX entry to disable “call waiting” during control panel calls.
Installation Instructions *55 Dynamic Signaling Priority UL Installations: For UL Commercial Burglary installations that use a DACT and LRR, the DACT must be programmed for priority (option “0”). Intended for use with Long Range Radio reporting (field ∗29 OUTPUT TO LONG RANGE RADIO must be enabled). Select the initial reporting destination for messages as follows: Primary Dialer First selected (0): • If acknowledged before delay expires (see ∗54), then message will not be sent to LRR.
FIELD TITLE and EXPLANATION *62 AC Loss Report Code *63 Low Bat Report Code *64 Test Report Code Enter the appropriate report code. Timing of this report is random with up to a 4-hour delay. If AC restores before the report goes out, there is no “AC RESTORE” report. UL: Required for UL commercial burglar alarm installations and for residential fire alarm installations. Enter the appropriate report code; sent when a low-battery condition exists in the system’s battery.
Installation Instructions FIELD TITLE and EXPLANATION *76 Test Restore Report Code Enter the appropriate report code, which is sent when the Test mode is exited. UL: Required for UL commercial burglar alarm installations and for residential fire alarm installations.
FIELD TITLE and EXPLANATION *89 Event Log Full Report Code *90 Event Log Enables *91 Enter the appropriate report code, which is sent when the event log is 80% full (if an event log enable is made in field ∗90). If the log becomes full, new messages overwrite the oldest messages in the log. Select the types of events (up to 32 events) the system should log. The downloader operator can then upload the log and view or print out all or selected categories of the log.
Installation Instructions FIELD TITLE and EXPLANATION *96 Command to Initialize CSID and Subscriber Account Number *97 Command to Reset System to Factory Default Values This is a command function, not a data field. Use this command, if necessary, to reset all subscriber account numbers and the internal CSID to the factory default values. This is a command function, not a data field. Pressing ∗97 resets all data fields to the factory default values (shown on the Program Form).
Configurable Zone Type Programming Fields The system allows you to define a custom zone type, based on the options described below. This configurable zone types can be programmed via the downloader or from a keypad using data fields *182-*183 described below. UL installations: Do not configure zones as fire alarm or UL burglar alarm zones.
Installation Instructions Configurable Zone Type Charts ENTRY 1 ENTRY 2 Response when system disarmed and zone is: Intact EOL Open Shorted RF zone normal RF zone N/A 0 = normal 1 = alarm 2 = trouble 3 = fault Auto Restore Vent Zone RF zn off-normal 0 = normal 4 = alarm 8 = trouble 12 = fault see note 4 Entry 1 = EOL + Open 0 = normal 1 = alarm 2 = trouble 3 = fault Entry 2 = Short + auto restore + vent zone ENTRY 3 ENTRY 4 Response when armed STAY and zone is: Intact EOL Open Shorted RF zone no
Keypad Programming Fields NOTE: Each keypad must be assigned a unique address. Keypads programmed with the same address will give unpredictable results. Address 16 is reserved for keypad 1, which is automatically set with all sounds enabled.
Installation Instructions 4-12
S E C T I O N 5 Menu Mode Programming • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Zone Programming Overview (∗ ∗56 and ∗58 Menu Modes) Use ✱56 Zone Programming to program zones, zone types, report codes, enroll 5800 RF Wireless Transmitter serial numbers, and identify the type of loop input device(s).
Installation Instructions Enter the report code for this zone, which consists of 2 hexadecimal digits, each in turn consisting of 2 numerical digits. For example, for a report code of “10,” enter 01 and 00. For Contact ID®, entering any non-zero entry as the first digit enables the report code for 10 Report Code 1st 01 2nd 00 10 this zone. Refer to the System Communication section for information about report codes and formats.
Entd A022-4063 1 Rcvd A022-4064 1 Zn ZT RC In: L 10 03 10 RF: 1s PROGRAM ALPHA? 0 = NO 1 = YES 0 E N TE R Z N N U M. ( 0 0 = Q U I T) 1 1 If the serial number transmitted does not match the serial number entered, a display similar to the one shown appears. If the loop number does not match, it will also be displayed. If so, activate the loop input or button on the transmitter once again. If a match is not obtained (i.e.
Installation Instructions Zn ZT RC IN: L 10 00 10 RF 1 A summary screen with the selected zone’s current programming appears. Begin programming zone information as follows: Enter Zone Type (ZT; see Zone Types listed in *56 Menu Mode “Zone Type” prompt), Report Code (RC), and Input Device Type (IN)* sequentially (Loop Number (L) is entered at the next prompt). • Use the [A] (Advance) and [B] (Back) keys on the keypad to move the cursor within the screen.
INPUT S/N AXXX-XXXX Manually enter the serial number printed on the label for the wireless key or press and release the button to transmit its serial number. Press [∗] to accept the serial number. The system will check for duplicate. If necessary, press the [#] key to back up without saving, and re-enter the serial number. Use the [A] key to move forward within the screen, and the [B] key to move backward.
Installation Instructions Output Device Programming Overview (*79/*80 Menu Mode) Output Devices: The system supports up to 4 relays plus 2 built-in trigger outputs. These “output devices” are assigned to system-wide output numbers (01-04, 17, 18). Relays are identified by the relay module’s device address and the relay position on the module (i.e. the physical relay number, 1-4, on the module). Built-in triggers are identified by the output number, 17 for Trigger 1 and/or 18 for Trigger 2.
*80 Menu Mode: Defining Output Functions Use this mode to program output function definitions (up to 12 functions) that provide automated control of any of the output devices, based on events occurring on individual zones or zones with certain zone types. Each output definition is identified by an output function number, and includes the following components: Output Definition Components Component Description Output Function No. A reference number that defines an output’s characteristics.
Installation Instructions “A” 01 Zn List 1 If zone list was selected, this screen appears. Otherwise skip to the next prompt.
Zone List Overview (∗ ∗81 Menu Mode) Zone lists let you group individual zones for use with certain system actions. The following table shows the available zone lists and their purposes: List No. Used for… 1, 2 general purpose 3 chime-by-zone 4 cross zones 5 night stay zones 6 general purpose VISTA-10PSIA: dial delay disable 7 general purpose VISTA-10PSIA: unlimited reports 8 9 general purpose zones that activate Pager 1 Zone List Programming Zone List programming involves: 1.
Installation Instructions Function Key Programming Overview (∗ ∗57 Menu Mode) The system provides the ability to program each of the four keypad function keys to perform one of 12 system operations. The end user can then activate the function by simply pressing and holding the programmed key for 2 seconds. Typical functions (listed below) include single-button arming, turning lights on/off, or single-button paging. Programming Function Keys Function key programming involves: 1.
About Descriptor Programming Overview (∗ ∗82 Menu Mode) The system lets you assign zone descriptors for protection zones, keypad panics, and RF receiver supervision faults. Each description can be composed of a combination of words (up to 3) selected from a vocabulary of 196 words stored in memory (see a following page). In addition, up to 10 installer-defined words can be added to those already in memory.
Installation Instructions Enter the 3-digit number for the next word. In the example, the word is DOOR, whose number is “057.” See index for entries. [∗] to continue ✱ ZN 01 BACK D OOR Save second word of descriptor: 6 = save word and go to next word in this descriptor 8 = save word and end descriptor if this is the only word of the descriptor - go to summary screen The two words in the example have now been entered.
ALPHA VOCABULARY LIST (For Entering Zone Descriptors) 000 • 001 • 002 004 005 • 006 • 007 • 009 010 • • • • • • • 012 013 014 016 017 018 019 020 • 021 • 022 023 025 • 026 028 • 029 030 031 033 034 035 036 • 037 038 • 040 • 046 047 (Word Space) –A– AIR ALARM ∗ ALLEY AMBUSH AREA APARTMENT ATTIC ∗ AUDIO –B– BABY ∗ BACK ∗ BAR BASEMENT ∗ BATHROOM ∗ BED BEDROOM ∗ BELL BLOWER BOILER BOTTOM BREAK BUILDING –C– CABINET CALL CAMERA CAR CASH CCTV CEILING CELLAR CENTRAL CIRCUIT CLOSED ∗ COMPUTER CONTACT –D– DAUGHTER
Installation Instructions Programming Installer and User Schedules The system provides 2 schedules (one for the installer, one for the end user), which can be used to control 11 types of system events at pre-defined times. Start Scheduling mode by entering installer code + [#] + [6] [4] while in normal operating mode. NOTE: The master code can only access schedules 01 and events 00-07. PROMPT ENTER SCHED NO.
GROUP NUMBER X START SMTW TFS HH MMAM 0 0 1 0 0 0 0 STOP SMTW TFS HH MMAM 0 0 1 0 0 0 0 REPEAT OPTION 0-4 X RANDOMIZE 0=NO 1=YES X This prompt appears if event “2” (user access) was selected. Otherwise it is skipped. 1-8 = group number [∗] to continue to the “Start” prompt Enter the event’s start time and days of the week to occur.
Installation Instructions 5-16
S E C T I O N 6 System Communication and Operation • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • System Communication Overview This system accommodates several formats for reporting alarms and other system conditions to the Central Station. The process of a successful transmission consists of both the method of communication between the control panel and the Central Station receiver; and the actual way the information is sent and displayed at the Central Station.
Installation Instructions The following table lists codes for reports sent in different formats: Type of Report Code for 3+1/4+1 Standard Code for 3+1/4+1 Expanded Alarm SSS(S) A SSS(S) A AAA(A) Z SSSS AZ Trouble SSS(S) T SSS(S) T TTT(T) t SSSS Tt Bypass SSS(S) B SSS(S) B BBB(B) b SSSS Bb AC Loss SSS(S) E SSS(S) E SSSS EAC Low Batt SSS(S) L Code for 4+2 EEE(E) AC SSS(S) L SSSS LLB LLL(L) LB Open SSS(S) O SSS(S) O OOO(O) U SSSS OU Close SSS(S) C SSS(S) C CCC(C) U SSSS CU Test
Ademco Contact ID® The Ademco Contact ID® Reporting Format comprises the following: 4-digit or 10-digit subscriber number (depending on format selected. 1-digit event qualifier (“new” or “restore”). 3-digit event code. 3-digit zone number, user number, or system status number (see the following page).
Installation Instructions User Security Codes The system supports up to 16 security codes, which can each be assigned one of 4 authority levels. The authority level determines the functions each code can perform as follows: Authority Levels (authority levels can be assigned to users 3-16 only; users 1 and 2 cannot be changed) Level Installer User No.
Keypad Functions The following is a brief list of system commands. For detailed information, see the User's Manual. Voice Keypads The 6150V/6160V Voice Keypads provide the following features: • Message Center, which lets the user record and playback one message. • Voice Status, which can announce system status by using the STATUS key. • Voice Chime, which can alert users to the opening of doors/windows while the system is disarmed.
Installation Instructions Panic Keys There are three Panic keys (A, B, and C) that, if programmed, can be used to manually initiate alarms and send a report to the central station by pressing and holding the appropriate key for at least 2 seconds. Each key can be programmed for 24-hour Silent, 24-hour Audible, Fire, or Personal Emergency responses.
S E C T I O N 7 Testing the System • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Test Procedures After the installation is complete, you should perform the following tests: System Test: Checks that all zones have been installed properly and the system properly responds to faults. Dialer Test: Checks that the phone connection to the central station is working properly. Go/No Go Test: Checks that transmissions can be received from transmitters.
Installation Instructions NOTES: • All BR type units must physically be activated to clear the display. • When one button of a transmitter (RF, UR, or BR) is activated, all zones assigned to other buttons on that transmitter are cleared. This also applies to 5816 and 5817 transmitters, which have multiple loops (zones). • Any transmitter that is not “enrolled” will not turn off its zone number.
S E C T I O N 8 Specifications & Accessories • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • SECURITY CONTROL Physical: 12-1/2” W x 14-1/2” H x 3” D (318mm x 368mm x 76mm) Electrical: VOLTAGE INPUT: 16.5VAC from plug-in 25VA transformer, Ademco No. 1321 (in U.S.A.) RECHARGEABLE BACKUP BATTERY: 12VDC, 4AH (sealed lead acid type). Charging Voltage: 13.8VDC. ALARM SOUNDER: 12V, 2.
Installation Instructions 5800 Series Transmitter Input Loop Identification All of the transmitters illustrated below have one or more unique factory assigned input (loop) ID codes. Each of the input loops requires its own programming zone (e.g., a 5804's four inputs require four programming zones).
Compatible 5800 Series Transmitters Table (continued) Model 5817 Product Multi-Point Universal Transmitter Input Type RF 5818 Recessed Transmitter 5819 Shock Processor Transmitter RF 5819WHS 5819BRS Shock Processor Transmitter RF 5827 Wireless Keypad Uses House ID only 5827BD Wireless Two-Way Keypad Uses House ID only 5849 Glassbreak Detector RF 5890 PR Detector RF 5899 Magnets RF Description Has three unique input (loop) codes: one for a “Primary” contact loop with programmable op
Installation Instructions 8-4
S E C T I O N 9 Regulatory Agency Statements • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • RADIO FREQUENCY EMISSIONS Federal Communications Commission (FCC) Part 15 This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Installation Instructions UL NOTICES Entry Delay No. 1 and No. 2 (fields ✱35, ✱36) cannot be greater than 30 seconds for UL Residential Burglar Alarm installations, and entry delay plus dial delay should not exceed 1 minute. For UL Commercial Burglar Alarm installations, total entry delay may not exceed 45 seconds. 2. For UL Commercial Burglar Alarm (Grade AA) and UL Residential Burglar Alarm installations with line security, total exit delay time must not exceed 60 seconds.
S E C T I O N 1 0 Limitations and Warranty • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • WARNING THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced design security system, it does not offer guaranteed protection against burglary, fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a variety of reasons.
Installation Instructions WARNING THE LIMITATIONS OF THIS ALARM SYSTEM (Continued) The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate maintenance. This alarm system should be tested weekly to make sure all sensors and transmitters are working properly. The security keypad (and remote keypad) should be tested as well. Wireless transmitters (used in some systems) are designed to provide long battery life under normal operating conditions.
– INDEX – 1321 ................................... 1-1, 2-4 24-Hour Audible Alarm .............. 3-3 24-Hour Silent Alarm ................. 3-3 3+1 and 4+1 Standard Formats. 6-1 4204 1-2, 2-5, 2-6, 2-9, 3-1, 5-6, 8-1 4229 ................................... 2-6, 3-1 4285 Phone Module 1-1, 2-12, 5-11 4286 Phone Module 1-1, 2-12, 5-11 4-Wire Smoke Detectors ........... 2-6 5800 Series Transmitters 2-8, 8-2, 8-3 5800TM......... 2-7, 2-8, 8-1, 8-2, 8-3 5801 ................................... 2-8, 8-2 5802 ....
Installation Instructions T Tamper Switch ............ 2-8, 2-9, 9-2 Telco Line ........................... 2-11, 3 Test Mode .......................... 7-1, 7-2 Test Restore Report Code......... 4-6 Transmitter Battery Life ............. 2-8 Transmitter Input Types ............ 5-2 Trouble by Day/ ......................... 3-3 Trouble Displays................. 6-4, 6-6 10-4 V Vocabulary List ........................ 5-11 W Wireless Key Templates............ 5-4 Wiring Length/Gauge Chart .......
CONNECTION OF THE FIRE ALARM SIGNAL TO A FIRE ALARM HEADQUARTERS OR A CENTRAL STATION SHALL BE PERMITTED ONLY WITH THE PERMISSION OF THE LOCAL AUTHORITY HAVING JURISDICTION. THE BURGLAR ALARM SIGNAL SHALL NOT BE CONNECTED TO A POLICE EMERGENCY NUMBER. THIS EQUIPMENT SHOULD BE INSTALLED IN ACCORDANCE WITH THE NATIONAL FIRE PROTECTION ASSOCIATION'S STANDARD 72, CHAPTER 2 (NATIONAL FIRE PROTECTION ASSOCIATION, BATTERY-MARCH PARK, QUINCY,MA 02269).
LIMITED WARRANTY Honeywell International Inc.